Procedures
Airflow4 min

Condensate overflow

A wet switch is a symptom. Find why the water is not leaving.

Path

  • Primary drain pitched, trapped where the OEM requires a trap, vented if the trap will siphon.
  • Secondary / pan switch should break Y or R per local practice — know what you are jumping before you jump it.
  • Pumps: check the reservoir, float, check valve, and lift height vs rating.

Why it backs up

  • Algae in the trap, a sagged vinyl line, a crushed riser, or a dry trap pulling air.
  • A plugged primary with a disconnected secondary is how you stain a ceiling.