Procedures
Charge8 min

Recovery and evacuation

EPA 608 path: recover, repair, evacuate, weigh in. No venting, no ‘just a hiss.’

Recovery

  • Identify refrigerant. Use a tank that is empty or same gas, in date, and not overfilled (80% by weight).
  • Purge hoses into the recovery path, not the air. Core tools save time and reduce loss.
  • Push-pull on large charges. Standard recovery on small splits. Watch tank temperature and pressure.

Evacuation

  • New or freshly opened system: evacuate to 500 microns or the OEM spec, then isolate and watch decay.
  • Decay that rises fast and stalls high is moisture or a leak. Decay that rises then flattens can be outgassing — hold longer.
  • Change vacuum pump oil when it milks. A dirty pump will not make micron.
  • Never use the compressor as a vacuum pump.

Weigh-in

  • Nameplate charge is for factory line-set length. Add or subtract per OEM feet of liquid line.
  • A2L (R-32, R-454B): charge limits, no open flame, leak-check before applying power.