987T
Evolution · two-stage · communicating · 97%
Bryant Evolution two-stage 97%. Twin of Carrier 59TN7. Discrete 31/32, ABCD bus. Not 987M modulating and not 986T (previous Evolution two-stage).
Not 987M modulating. Not 986T previous two-stage Evolution. Not 927T Preferred 24V.
AFUE
Up to 96.7–97% Evolution two-stage
Sister SKU
Carrier 59TN7
This board
Evolution IFC + two-digit codes (two-stage, not modulating)
- Evolution wall control Last 10 first. Board two-digit still flashes 24, 31, 32, 33, 13, 34, 14, 41.
- 31/32 are discrete low vs high pressure switches — opposite of 987M, where 31/42 is a band.
- ABCD polarity, one Evolution control, C required. Do not land a 24V Preferred stat on ABCD.
Evolution events first. Board last-status if the stat is dead.
Universal swap
Evolution two-stage. No universal.
Silk: Evolution
White-Rodgers
—ICM
—Honeywell
—- Any 50A55-843 / 50A65-843 / 50M56U-843 / 50M56X-843 / S9200U1000 universal — those are conventional 24V HSI, not this data bus.
- ICM280 / 2811 / 2810 / 282B — wrong IFC family.
- 927T Preferred. 987M modulating card.
After you pull the dead card
- 1OEM Evolution two-stage IFC. Pair the ABCD bus.
Field wiring
Written landings for Bryant 987T. Not a factory schematic.
59MN7 / 59TN6 / 987M / 986T class. Four-wire communicating furnace. D is 24V hot, not W and not Y.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
This indoor
Current Evolution two-stage.
ABCD only
Infinity or Evolution wall control and a matching outdoor.
Infinity / Evolution control
A/B data, C common, D 24V hot.
- ADataData
- BDataData
- C24V common24V
- D24V hot — not W24V
Infinity / Evolution IFC
Same ABCD. Do not convert it to 24V by landing W and walking away.
- ADataData
- BDataData
- CCommon24V
- D24V hot24V
Landing
- DataStat A/BIFC A/Boutdoor A/B
Data
- 24VStat C/DIFC C/D
24V common / hot. D is not Y or W.
IFC harness — communicating two-stage
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + dual PS
Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.
- IND LO/HITwo-speed inducerLine
- LPSLow prove24V
- HPSHigh prove24V
HSI + two-stage valve
Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.
- HSI120V igniterLine
- MV / HV24V low / high solenoids24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Low then high
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- Wall-control equipment list. The furnace and outdoor both present.
- ABCD polarity. C still required.
Do not
- Do not land W on a spare screw to make it 24V.
- A 926T / 59TP6 / 59SC5 is the other diagram.
ABCD is the published Infinity / Evolution control.
Sequence
- 1
Call
Wall control requests a stage over ABCD. Valve is still two-stage (low then high).
- 2
Low prove
Low inducer → low PS (32). Same physics as 926T, different bus.
- 3
High prove
High inducer → high PS (31 on the high call). Second solenoid.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
24
Fuse
24 V fuse.
1 Find the 24 V short before you replace the fuse
On Bryant 987T an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. ABCD miswire, HUM/EAC, valve harness.
Expect: Fuse out. 24 V transformer still good. Harness isolated.
2 Replace the fuse with the harness off
New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC).
Expect: Fuse holds with harness off. Dies when the shorted lead lands.
3 If it blows with the harness off
Short is on the Bryant 987T IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.
Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.
31
High / active-stage PS
High-fire or active-stage prove failed.
1 Prove inducer and the live code
Do not pull power — that clears the Bryant 987T active code. Write 31. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Does the inducer actually go high?
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. High-fire hose not teed to the low switch.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Vent capacity on 100/120 cabinets.
Expect: LPS / HPS: Two NO switches. 32 vs 31. Never teed.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
32
Low-fire PS
Low-stage draft not proven.
1 Prove inducer and the live code
Do not pull power — that clears the Bryant 987T active code. Write 32. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap, collector, low hose, attic PVC.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Fix 32 before you chase 34.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: LPS / HPS: Two NO switches. 32 vs 31. Never teed.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
33 / 13
Limit
Airflow or rollout.
1 Treat this as flame outside the exchanger
Do not reset the Bryant 987T rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Evolution heat CFM, filter, coil. Rollout manual reset.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Bryant 987T is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
34 / 14
Ignition
No flame prove.
1 Watch one full try — do not reset
Write the Bryant 987T code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, rod. Fix 32 first if both store.
Expect: Call → Low prove → High prove
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.
Expect: Inlet and manifold on the plate. 24 VAC only during trial.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.
Expect: Stable µA after light-off. No new PS/limit code.
ABCD
Communication
Wall control or outdoor dropped.
1 Data pair, not 24 V
On Bryant 987T indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. A/B/C/D, polarity, C, one master.
Expect: Pair continuous, not shorted to chassis, polarity per the diagram.
2 Power both ends, then the outdoor status
Indoor transformer and outdoor control both alive. Read the outdoor LED / 7-seg. Water in the outdoor control is the usual dead-end after a storm.
Expect: Both controls powered. Outdoor showing a comm or address state, not a blank board.
3 Address / bias, then the control
Communicating plates need a matching indoor address and sometimes a terminating bias. Swap is last: known-good pair + power both ends + correct address.
Expect: Indoor sees the outdoor. No comm code after a power cycle.
Workflows
987T vs 987M vs 986T
Evolution condensing.
1 Prove the call and the live code
987M = modulating, pressure band. 987T / 986T = two-stage, discrete 31/32.
Expect: Write whatever Evolution IFC + two-digit codes (two-stage, not modulating) is showing. Evolution events first. Board last-status if the stat is dead.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
987T is the current two-stage Evolution. 986T is the previous plate.
Expect: Low prove: Low inducer → low PS (32). Same physics as 926T, different bus.
3 Confirm with a number, then the next part
987T is the current two-stage Evolution. 986T is the previous plate.
Expect: ABCD: Evolution pair. D is not W. · LPS / HPS: Two NO switches. 32 vs 31. Never teed.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
ABCD
Evolution pair. D is not W.
LPS / HPS
Two NO switches. 32 vs 31. Never teed.
Gotchas
- 986T stays in the bench as the previous Evolution two-stage.
Related plates
Install this plate
Install Bryant 987T as Evolution · two-stage · communicating · 97%.
Evolution · two-stage · communicating · 97%
This plate — not the sister SKU
- Not 987M modulating. Not 986T previous two-stage Evolution. Not 927T Preferred 24V.
- 986T stays in the bench as the previous Evolution two-stage.
IFC on this door
- Evolution wall control Last 10 first. Board two-digit still flashes 24, 31, 32, 33, 13, 34, 14, 41.
- 31/32 are discrete low vs high pressure switches — opposite of 987M, where 31/42 is a band.
- ABCD polarity, one Evolution control, C required. Do not land a 24V Preferred stat on ABCD.
Hardware
- AFUE: Up to 96.7–97% Evolution two-stage
- Sister SKU: Carrier 59TN7
First fire
- 1987M = modulating, pressure band. 987T / 986T = two-stage, discrete 31/32.
- 2987T is the current two-stage Evolution. 986T is the previous plate.
Do not on Bryant 987T
- Not 987M modulating. Not 986T previous two-stage Evolution. Not 927T Preferred 24V.
- 986T stays in the bench as the previous Evolution two-stage.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Bryant document searchLiterature searchEnter the full Bryant plate (926TB60100V21, 987MA…). Owner PDFs are public; many I/Os are dealer-gated.Open manufacturer PDF
- Bryant document searchLiterature searchSearch Bryant 987T on the maker’s literature page.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Distributor HX claims sheet
dealerUSFurnace heat exchanger claims — serial in/out of range
Serial 2993A00001 – 1808A99999 (in-range); later serials are standard warranty
Primary or secondary heat exchanger failure · Distributor claim path
CE Canada Bryant trade-in 2025–26
ended seasonCanadaHigh-efficiency gas furnace trade-in — Bryant Canada
2025-04 (ended 2026-04-30)
Failed 340–355 family secondary within 20 years of install · Trade-in (ended)
Residential limited warranty
warranty sheetCarrier / Bryant registered heat-exchanger terms
Current 59-series / Evolution / Preferred registered warranty · Limited warranty certificate
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal