ComfortLink furnace
ComfortLink data pair
Trane XC95m / XC80 / XL95 class. Communicating indoor. S9V2 is 24V CoF/Ht1 — different diagram.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
ComfortLink pair
Communicating stat and outdoor (XV18 / XV20i) on the same bus.
ComfortLink control
Data pair. English events. Not Y.
- DATA+ComfortLinkData
- DATA−ComfortLinkData
- R24V if needed24V
- CCommon24V
ComfortLink IFC
Do not diagnose this indoor with S9V2 E2.1.
- DATA+ComfortLinkData
- DATA−ComfortLinkData
Landing
- DataStat pairIFC pairoutdoor pair
Data. Not 24 VAC Y.
IFC harness — communicating two-stage
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + dual PS
Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.
- IND LO/HITwo-speed inducerLine
- LPSLow prove24V
- HPSHigh prove24V
HSI + two-stage valve
Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.
- HSI120V igniterLine
- MV / HV24V low / high solenoids24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Low then high
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- ComfortLink event list. Indoor and outdoor both on the bus.
Do not
- Do not use the S9V2 / S9X2 24V diagram on XC95m.
- Do not land W on a random terminal to force heat.
DATA+/DATA− means the ComfortLink pair on the silk.