Wiring

Infinity / Evolution inverter AC

ABCD

ABCD

Four-wire communicating inverter air conditioner. Capacity is serial. No contactor, no dual cap, no reversing valve, no defrost.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

ABCD only

Infinity or Evolution wall control plus a matching indoor.

Infinity / Evolution wall control

Four-wire ABCD. D is 24V hot, not Y.

  • ADataData
  • BDataData
  • C24V common24V
  • D24V hot — not a cool call24V

Infinity / Evolution indoor

Same ABCD. Indoor CFM is serial. A Comfort 59SC5 does not belong here.

  • ADataData
  • BDataData
  • C24V common24V
  • D24V hot24V

Outdoor communicating drive

ABCD (or the outdoor comm harness). No Y contactor. No dual cap.

  • ADataData
  • BDataData
  • C24V common24V
  • D24V hot — still not Y24V

Outdoor line — inverter drive

208/230 into the drive. No contactor slam. DC bus can stay live after the disconnect.

  • L1Line to the driveLine
  • L2Line to the driveLine
  • GNDEquipment groundLine

Landing

  • DataStat A/Bindoor A/Boutdoor A/B

    Data pair. Not 24 VAC Y.

  • 24VStat Cindoor Coutdoor C

    24V common. Still required.

  • 24VStat Dindoor Doutdoor D

    24V hot. D is not Y.

  • LineL1 / L2drive

    208/230. No contactor.

Prove it

  • Wall-control event list first. Bus fault vs drive fault — do not gauge up on a comm code.
  • ABCD landing and polarity. C is still required at the wall control.

Do not

  • Do not land conventional Y on D and walk away.
  • Do not ohm a defrost sensor or an RV solenoid. That is 25VNA4 / 280ANV.
  • Do not change a dual run cap that is not in this cabinet.

Carrier 24VNA6 / 26VNA1 and Bryant 191VAN / 180B. 187B is Evolution two-stage on the same ABCD bus, not this inverter.