Infinity / Evolution inverter HP
ABCD + RV / defrost on the drive
25VNA4 / 280ANV. Same ABCD as 24VNA6 — plus a reversing valve and defrost on the outdoor drive.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFABCD heat pump
Infinity / Evolution HP outdoor.
Infinity / Evolution wall control
Four-wire ABCD. D is 24V hot, not Y.
- ADataData
- BDataData
- C24V common24V
- D24V hot — not a cool call24V
Infinity / Evolution indoor
Same ABCD. Indoor CFM is serial. A Comfort 59SC5 does not belong here.
- ADataData
- BDataData
- C24V common24V
- D24V hot24V
Outdoor communicating drive
ABCD (or the outdoor comm harness). No Y contactor. No dual cap.
- ADataData
- BDataData
- C24V common24V
- D24V hot — still not Y24V
Outdoor line — inverter drive
208/230 into the drive. No contactor slam. DC bus can stay live after the disconnect.
- L1Line to the driveLine
- L2Line to the driveLine
- GNDEquipment groundLine
Landing
- DataABCD throughout
Data + 24V C/D. No O/B stat wire on most of these.
- 24VRV and defrost
On the outdoor drive. Not a furnace function.
Prove it
- Same ABCD prove as 24VNA6, then confirm this plate is the HP (RV + outdoor coil sensor).
Do not
- Do not use this on 24VNA6 / 191VAN. Those have no RV.
- Do not charge it like a 24ACC6 piston unit.
Included so the HP twin is not silently reused as the AC diagram.