Wiring

Single-stage HP · Y + O/B

24V Y / C / O or B

24V Y / C / O or B

GSZ14 class. Contactor + dual cap + defrost board + reversing valve. O/B direction is board-specific — do not assume Carrier O-on-cool.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

24V heat pump

Single-stage HP outdoor with a defrost board.

Heat-pump thermostat

Y, O/B, C, W/E aux. Confirm O vs B on THIS board.

  • R24V hot24V
  • CCommon24V
  • YCompressor24V
  • O/BReversing valve24V
  • GIndoor fan24V
  • W/EAux / emergency24V

Defrost board + contactor

Y to the board / coil. O/B to the RV solenoid per the diagram on the door.

  • YCompressor request24V
  • CCommon24V
  • O/BRV — read the silk24V

Outdoor line

208/230 through the disconnect to the contactor line side.

  • L1LineLine
  • L2LineLine
  • GNDEquipment groundLine

Dual run capacitor

C / FAN / HERM on the can. An inverter outdoor does not have this part.

  • CCommon — both windingsCap
  • FANOutdoor fanCap
  • HERMCompressorCap

Landing

  • 24VStat Yindooroutdoor Y

    ~24 VAC compressor

  • 24VStat O/Boutdoor RV

    Energize direction is THIS board, not a Carrier habit.

Prove it

  • Y–C at the outdoor under a compressor call.
  • O/B voltage vs the door: energized in cool or heat on THIS silk.

Do not

  • Do not use the GSX16 AC diagram. There is an RV and a defrost board here.
  • Do not assume O-on-cool.

O/B polarity is the #1 callback. Read the outdoor diagram.