Models
Rheemfurnace

R951V

Endeavor · single-stage · VS · EcoNet · 92–95%

Rheem Endeavor single-stage VS EcoNet (R951V 95%, R921V 92%). One solenoid. Still condensing. Not R951T CT and not R972V two-stage.

Not R951T / R921T CT. Not R972V two-stage. Not R801V 80%.

AFUE

92% or 95% single-stage VS (read the plate)

Staging

One fire rate · one PS

This board

Rheem 2-digit IFC (VA / Endeavor)

  • Read THIS door card. VA / Endeavor often split low-pressure: 45 LPS open at HIGH inducer speed, 46 LPS open at LOW inducer speed, 57 high PS open, 93 internal.
  • Also on this IFC: 10 one-hour lockout, 11 failed ignition, 12 low flame, 13 flame lost, 14 unexpected flame, 22 limit, 26 reversed polarity, 33 rollout, 58/59 condensate, 61 blower.
  • Do not apply the R96TA rule ‘45 = all low PS’ blindly. On many VA cards 45 is high-inducer LPS, 46 is low-inducer LPS.
  • EcoNet pair (when landed) is data, not 24V. A blank EcoNet stat is not automatically a dead IFC.

Write the two-digit code before a power cycle. Stat history if EcoNet is the thermostat. Board menu if equipped.

Universal swap

No universal

Single-stage VS EcoNet. Not a 50A55.

White-Rodgers

ICM

Honeywell

  • 50A55-843. R951T CT board assumed.

After you pull the dead card

  1. 1OEM Endeavor VS IFC.

Field wiring

Written landings for Rheem R951V. Not a factory schematic.

EcoNet furnace
E1 / E2 — or 24VGas furnace

Rheem / Ruud R96V / R98V / R98MV / R972V / R801V. EcoNet on E1/E2. R96TA / R801S stay on the 24V furnace diagram.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC120V
  2. 2Call. Data pair or 24V W → IFCBus or 24V
  3. 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
  4. 4Ignite. IFC → HSI → valve120V igniter
  5. 5Blow. IFC → serial ECMNo tap, no cap

This indoor

95% VS EcoNet-capable. R951T is the 24V CT cousin.

EcoNet communicating

EcoNet control and a communicating outdoor (RA19AY class).

EcoNet control

E1/E2 data. R and C still feed the control.

  • R24V hot24V
  • CCommon24V
  • E1EcoNetData
  • E2EcoNetData

EcoNet IFC

E1/E2 to the outdoor. 24V strip still exists for a conventional job.

  • E1EcoNetData
  • E2EcoNetData
  • R24V24V
  • CCommon24V

Landing

  • DataControl E1/E2IFC E1/E2outdoor E1/E2

    EcoNet data

24V on an EcoNet-capable IFC

Conventional stat. Leave E1/E2 empty.

Conventional stat

W/W2/Y/G on the 24V strip.

  • RHot24V
  • CCommon24V
  • WHeat24V
  • YCool24V
  • GFan24V

Landing

  • 24VStat WIFC W · Stat Youtdoor Y

    ~24 VAC

IFC harness — communicating two-stage

Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.

Transformer + fuse

24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.

  • L1 / N120VLine
  • R / C24V strip24V
  • FUSEOn the IFC24V

24V safety chain

Limit / rollout / door still open the heat path. Codes are on THIS IFC language.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + dual PS

Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.

  • IND LO/HITwo-speed inducerLine
  • LPSLow prove24V
  • HPSHigh prove24V

HSI + two-stage valve

Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.

  • HSI120V igniterLine
  • MV / HV24V low / high solenoids24V
  • FLAMEµA DC24V

Serial variable-speed ECM

IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.

  • SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
  • CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V

Landing

  • LineCallIFCinducerprove

    Low then high

  • LineIFCHSIvalve

    120V igniter, 24V or serial valve

  • 24VFlame rodIFC

    µA DC

  • DataIFCserial blower

    No F-taps. No PSC cap.

Prove it

  • EcoNet control lists this furnace.
  • R96TA / R801S do not have this bus.

Do not

  • Do not land 24V Y on E1.
  • Do not read TA 45 onto a VA door.

E1 / E2 are the published EcoNet pair.

Sequence

  1. 1

    W1 / low

    Inducer low → 46 if the low-inducer LPS never closes (VA split). HSI → valve → 11/12/13 if flame fails.

  2. 2

    W2 / high

    Inducer high → 45 if the high-inducer LPS never closes on cards that split 45/46 → 57 if the high-pressure / exhaust switch never closes.

  3. 3

    Water

    58/59 still mean 96% drain. Pull water before you chase 45/46/57 parts.

  4. 4

    EcoNet

    Optional. Many VA jobs still run 24V W. Data-pair polarity matters only when the EcoNet stat is the control.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

10

One-hour lockout

lockout

Hardened ignition or PS retries.

  1. 1 Watch one full try — do not reset

    Write the Rheem R951V code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. Read the code under it (11, 45, 46, 57). Do not just wait the hour.

    Expect: W1 / low → W2 / high → Water → EcoNet

  2. 2 Gas and the valve

    Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.

    Expect: Manifold: Low and high vs plate.

  3. 3 Flame prove, then the lockout timer

    Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.

    Expect: Stable µA after light-off. No new PS/limit code.

11

Failed ignition

lockout

Trial without prove.

  1. 1 Watch one full try — do not reset

    Write the Rheem R951V code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, rod, 24 VAC at the valve.

    Expect: W1 / low → W2 / high → Water → EcoNet

  2. 2 Gas and the valve

    Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence. Same prove logic as TA — the motor and the 45/46 card are what changed.

    Expect: Manifold: Low and high vs plate.

  3. 3 Flame prove, then the lockout timer

    Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.

    Expect: Stable µA after light-off. No new PS/limit code.

12

Low flame sense

warn

Weak µA.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Rheem R951V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Rod, ground, manifold.

    Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold: Low and high vs plate.

  3. 3 Prove it is not a switch opening

    Watch the live Rheem R951V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

13

Flame lost

warn

Dropped after prove.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Rheem R951V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Vent after blower-on, manifold, rod.

    Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold: Low and high vs plate.

  3. 3 Prove it is not a switch opening

    Watch the live Rheem R951V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

14

Unexpected flame

hazard

Flame with valve off.

  1. 1 Shut the gas cock first

    On Rheem R951V the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

22

Limit open

warn

Overtemp / airflow.

  1. 1 Airflow before you touch the limit

    On Rheem R951V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). VS heat CFM, filter, coil, rise.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Rheem R951V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. 61 if the VS motor is the cause — this is not a TA tap motor.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).

    Expect: Manifold: Low and high vs plate.

26

Reversed polarity

lockout

L1/N or ground.

  1. 1 Hot and neutral at the IFC, not the disconnect

    On Rheem R951V polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC. Chassis ground.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

33

Rollout

hazard

Flame containment. Manual reset.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Rheem R951V rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, flue. Do not keep resetting.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Rheem R951V is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

45

Low PS open at HIGH inducer speed

lockout

On VA / Endeavor cards that split low-pressure: the LPS did not close while the inducer is on high. This is not TA ‘45 = all low PS.’

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Rheem R951V active code. Write 45. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Confirm the door card on THIS cabinet before you treat 45 as intake/low-fire.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. High-inducer LPS hose, inducer actually on high, vent load at high speed.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. 58/59 first if stored.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

46

Low PS open at LOW inducer speed

lockout

LPS did not close on low inducer. This is the VA low-fire / low-inducer half of the split TA never printed.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Rheem R951V active code. Write 46. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Low-inducer LPS path, intake, trap, inducer low speed.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Do not swap the 45 switch first because a TA chart said ‘45 is low.’

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

57

High pressure switch OPEN

lockout

High-pressure / exhaust switch open.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Rheem R951V active code. Write 57. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Exhaust, high-fire hose, inducer high.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. 46 vs 45 vs 57 are three different moments — write the order.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

58 / 59

Condensate / water

lockout

96% drain or water switch.

  1. 1 Float and the pan

    On Rheem R951V a drain / float code is water until proven otherwise. Pan full? Float stuck? Secondary drain piped? Trap, pump, slope, ice. Water first, then 45/46/57.

    Expect: Pan dry after you clear it. Float moves freely.

  2. 2 Trap and the pump

    Indoor trap primed and flowing. Condensate pump actually pumping, check valve not stuck. On a furnace, a drowned collector will also throw PS codes — clear both.

    Expect: Trap flowing. Pump discharges. No water in the collector.

  3. 3 Then the switch circuit

    If the pan is dry and the code stays, ohm the float / condensate switch and the IFC input. Do not jump a wet-switch input as a repair.

    Expect: Switch closed when dry. Code gone.

61

Blower

lockout

VS motor / CFM fault.

  1. 1 Is the wheel free?

    Spin the Rheem R951V blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Harness, VS comms at the motor, static.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. A TA CT motor will not run correctly on this IFC.

    Expect: Command present. Motor amps in range, not locked.

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.

    Expect: Static on the blower chart. Matching motor / shared-data card.

93

Internal control

lockout

IFC self-fault.

  1. 1 Write the live code and watch one cycle

    On Rheem R951V read Rheem 2-digit IFC (VA / Endeavor) before you pull power. Write 93 exactly. Watch one full sequence and note which step dies. Stored stack first. Wet board, polarity (26), persistent input.

    Expect: W1 / low: Inducer low → 46 if the low-inducer LPS never closes (VA split). HSI → valve → 11/12/13 if flame fails.

  2. 2 Prove the circuit this code names

    Do not confuse 93 with an EcoNet-stat blank.

    Expect: A measured open, short, or out-of-range reading — not a guess.

  3. 3 Confirm with a number, then the next part

    If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.

    Expect: Door card: 45 vs 46 printed as high-inducer LPS vs low-inducer LPS on VA/Endeavor. Photograph it.

Workflows

R951V vs R951T

Endeavor 95%.

  1. 1 Prove the call and the live code

    V = constant CFM EcoNet motor. T = constant torque, usually 24V only.

    Expect: Write whatever Rheem 2-digit IFC (VA / Endeavor) is showing. Write the two-digit code before a power cycle. Stat history if EcoNet is the thermostat. Board menu if equipped.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    One PS. Trap / PVC. 92% R921V still condenses.

    Expect: W2 / high: Inducer high → 45 if the high-inducer LPS never closes on cards that split 45/46 → 57 if the high-pressure / exhaust switch never closes.

  3. 3 Confirm with a number, then the next part

    One PS. Trap / PVC. 92% R921V still condenses.

    Expect: Door card: 45 vs 46 printed as high-inducer LPS vs low-inducer LPS on VA/Endeavor. Photograph it. · EcoNet pair: Data, not 24 VAC. Polarity. Unused pair on a 24V job should not be landed on W.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Door card

45 vs 46 printed as high-inducer LPS vs low-inducer LPS on VA/Endeavor. Photograph it.

EcoNet pair

Data, not 24 VAC. Polarity. Unused pair on a 24V job should not be landed on W.

Motor

VS ECM. A TA CT motor is the wrong part.

Manifold

Low and high vs plate.

Gotchas

  • R921V is 92% — still a collector, not an 80% chimney.

Related plates

Install this plate

Install Rheem R951V as Endeavor · single-stage · VS · EcoNet · 92–95%.

Endeavor · single-stage · VS · EcoNet · 92–95%

This plate — not the sister SKU

  • Not R951T / R921T CT. Not R972V two-stage. Not R801V 80%.
  • R921V is 92% — still a collector, not an 80% chimney.

IFC on this door

  • Read THIS door card. VA / Endeavor often split low-pressure: 45 LPS open at HIGH inducer speed, 46 LPS open at LOW inducer speed, 57 high PS open, 93 internal.
  • Also on this IFC: 10 one-hour lockout, 11 failed ignition, 12 low flame, 13 flame lost, 14 unexpected flame, 22 limit, 26 reversed polarity, 33 rollout, 58/59 condensate, 61 blower.
  • Do not apply the R96TA rule ‘45 = all low PS’ blindly. On many VA cards 45 is high-inducer LPS, 46 is low-inducer LPS.
  • EcoNet pair (when landed) is data, not 24V. A blank EcoNet stat is not automatically a dead IFC.

Hardware

  • AFUE: 92% or 95% single-stage VS (read the plate)
  • Staging: One fire rate · one PS

First fire

  1. 1V = constant CFM EcoNet motor. T = constant torque, usually 24V only.
  2. 2One PS. Trap / PVC. 92% R921V still condenses.

Do not on Rheem R951V

  • Not R951T / R921T CT. Not R972V two-stage. Not R801V 80%.
  • R921V is 92% — still a collector, not an 80% chimney.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • Rheem residential furnacesLiterature searchR96T / R96V / R801V / R802V / R98MV product cards. I/O is typically MyRheem / PTS dealer.Open manufacturer PDF
  • Rheem supportLiterature searchOwner docs and registration. Full I/O is not hosted as a public PDF for most Endeavor plates.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    dealer

    Rheem furnace warranty

    Registered Endeavor / Classic furnace warranty · Dealer claims portal

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal