EcoNet furnace
E1 / E2 — or 24V
Rheem / Ruud R96V / R98V / R98MV / R972V / R801V. EcoNet on E1/E2. R96TA / R801S stay on the 24V furnace diagram.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
EcoNet communicating
EcoNet control and a communicating outdoor (RA19AY class).
EcoNet control
E1/E2 data. R and C still feed the control.
- R24V hot24V
- CCommon24V
- E1EcoNetData
- E2EcoNetData
EcoNet IFC
E1/E2 to the outdoor. 24V strip still exists for a conventional job.
- E1EcoNetData
- E2EcoNetData
- R24V24V
- CCommon24V
Landing
- DataControl E1/E2IFC E1/E2outdoor E1/E2
EcoNet data
24V on an EcoNet-capable IFC
Conventional stat. Leave E1/E2 empty.
Conventional stat
W/W2/Y/G on the 24V strip.
- RHot24V
- CCommon24V
- WHeat24V
- YCool24V
- GFan24V
Landing
- 24VStat WIFC W · Stat Youtdoor Y
~24 VAC
IFC harness — communicating two-stage
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + dual PS
Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.
- IND LO/HITwo-speed inducerLine
- LPSLow prove24V
- HPSHigh prove24V
HSI + two-stage valve
Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.
- HSI120V igniterLine
- MV / HV24V low / high solenoids24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Low then high
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- EcoNet control lists this furnace.
- R96TA / R801S do not have this bus.
Do not
- Do not land 24V Y on E1.
- Do not read TA 45 onto a VA door.
E1 / E2 are the published EcoNet pair.