Models
Rheemfurnace

R98V

Prestige / Endeavor · modulating 98% · EcoNet

Rheem Prestige / Endeavor modulating 98% EcoNet furnace. The communicating EcoNet thermostat is the system. Capacity is a percent, not W1/W2. 11/12/13 still mean ignition/flame. 22 is limit. 45/57 are draft at a firing rate (modulating inducer / pressure), not a simple two-switch tee. 93 is internal.

Not R96VA two-stage. An EcoNet stat on R96VA is optional; on R98V it is native. Do not treat this as a two-stage 45/46/57 card and do not ‘convert it to 24V’ as a fix.

AFUE

98% modulating

Heat

Modulating valve · variable inducer · capacity is %

Control

EcoNet communicating — the wall control is part of the IFC

Blower

Variable-speed ECM on the EcoNet system

Sister SKU

R98MV · R97V / R97MV · Ruud U98V · Prestige / Endeavor

This board

EcoNet IFC + communicating stat (Prestige / Endeavor)

  • Read the EcoNet thermostat diagnostics first. The wall control names the fault. Board 2-digit codes still appear.
  • EcoNet comm / control faults live on the stat and the data pair. 11 / 12 / 13 are still ignition and flame. 22 is limit. 93 is internal.
  • 45 / 57 here are draft at a firing rate — modulating inducer and pressure, not R96TA/VA two discrete switches on a tee.
  • Do not land a 24V stat on the EcoNet pair and call it repaired.

EcoNet stat event history is the real log. Write board digits if the stat is dead, then restore comm before you guess.

Universal swap

No universal

EcoNet communicating modulating IFC. No universal.

White-Rodgers

ICM

Honeywell

  • Any 50A55-843 / 50A65-843 / 50M56U-843 / 50M56X-843 / S9200U1000 universal — those are conventional 24V HSI, not this data bus.
  • ICM280 / 2811 / 2810 / 282B — wrong IFC family.
  • R96VA two-stage card. ICM288 / ICM292A.

After you pull the dead card

  1. 1OEM EcoNet IFC. Pair the communicating thermostat.

Field wiring

Written landings for Rheem R98V. Not a factory schematic.

EcoNet furnace
E1 / E2 — or 24VGas furnace

Rheem / Ruud R96V / R98V / R98MV / R972V / R801V. EcoNet on E1/E2. R96TA / R801S stay on the 24V furnace diagram.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC120V
  2. 2Call. Data pair or 24V W → IFCBus or 24V
  3. 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
  4. 4Ignite. IFC → HSI → valve120V igniter
  5. 5Blow. IFC → serial ECMNo tap, no cap

This indoor

Prestige modulating. EcoNet.

EcoNet communicating

EcoNet control and a communicating outdoor (RA19AY class).

EcoNet control

E1/E2 data. R and C still feed the control.

  • R24V hot24V
  • CCommon24V
  • E1EcoNetData
  • E2EcoNetData

EcoNet IFC

E1/E2 to the outdoor. 24V strip still exists for a conventional job.

  • E1EcoNetData
  • E2EcoNetData
  • R24V24V
  • CCommon24V

Landing

  • DataControl E1/E2IFC E1/E2outdoor E1/E2

    EcoNet data

24V on an EcoNet-capable IFC

Conventional stat. Leave E1/E2 empty.

Conventional stat

W/W2/Y/G on the 24V strip.

  • RHot24V
  • CCommon24V
  • WHeat24V
  • YCool24V
  • GFan24V

Landing

  • 24VStat WIFC W · Stat Youtdoor Y

    ~24 VAC

IFC harness — communicating two-stage

Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.

Transformer + fuse

24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.

  • L1 / N120VLine
  • R / C24V strip24V
  • FUSEOn the IFC24V

24V safety chain

Limit / rollout / door still open the heat path. Codes are on THIS IFC language.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + dual PS

Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.

  • IND LO/HITwo-speed inducerLine
  • LPSLow prove24V
  • HPSHigh prove24V

HSI + two-stage valve

Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.

  • HSI120V igniterLine
  • MV / HV24V low / high solenoids24V
  • FLAMEµA DC24V

Serial variable-speed ECM

IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.

  • SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
  • CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V

Landing

  • LineCallIFCinducerprove

    Low then high

  • LineIFCHSIvalve

    120V igniter, 24V or serial valve

  • 24VFlame rodIFC

    µA DC

  • DataIFCserial blower

    No F-taps. No PSC cap.

Prove it

  • EcoNet control lists this furnace.
  • R96TA / R801S do not have this bus.

Do not

  • Do not land 24V Y on E1.
  • Do not read TA 45 onto a VA door.

E1 / E2 are the published EcoNet pair.

Sequence

  1. 1

    Call

    EcoNet stat requests a % capacity. Valve and inducer modulate; blower CFM follows. This is not W1 then W2.

  2. 2

    Prove

    Variable inducer must hit the pressure band for that firing rate. 45/57 are a band miss, not ‘swap the low switch.’

  3. 3

    Ignition

    Still HSI + flame rod. 11/12/13 still mean no prove / weak / lost flame.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

EcoNet

EcoNet comm / control

lockout

Stat, indoor, or data pair dropped. The communicating thermostat is the system.

  1. 1 Data pair, not 24 V

    On Rheem R98V indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. Data-pair landing and polarity. EcoNet is not R/W.

    Expect: Pair continuous, not shorted to chassis, polarity per the diagram.

  2. 2 Power both ends, then the outdoor status

    Indoor transformer and outdoor control both alive. Read the outdoor LED / 7-seg. Water in the outdoor control is the usual dead-end after a storm. 24 VAC still required at the control — comm dead is not ‘no transformer’ until you measure.

    Expect: Both controls powered. Outdoor showing a comm or address state, not a blank board.

  3. 3 Address / bias, then the control

    Communicating plates need a matching indoor address and sometimes a terminating bias. Swap is last: known-good pair + power both ends + correct address. One EcoNet control. Do not stack a 24V stat on the data pins.

    Expect: Indoor sees the outdoor. No comm code after a power cycle.

11 / 12 / 13

Ignition / flame

lockout

11 failed ignition, 12 low flame sense, 13 flame lost. Same meanings as the two-stage Rheem IFCs.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Rheem R98V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. HSI, gas, rod, ground, manifold at the commanded rate — a valve that will not come off minimum looks like 11/13.

    Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Do not treat these as EcoNet comm codes.

    Expect: Manifold on the rating plate. Solid burner-box ground.

  3. 3 Prove it is not a switch opening

    Watch the live Rheem R98V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

22

Limit open

warn

Overtemp / airflow.

  1. 1 Airflow before you touch the limit

    On Rheem R98V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). EcoNet heat CFM, filter, coil, rise.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Rheem R98V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. A 24V fallback (if someone forced one) will not modulate airflow correctly and will trip 22.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).

    Expect: Manifold on plate. Limit closed when cool.

45 / 57

Draft at a firing rate

lockout

Modulating inducer / pressure did not prove at the commanded %. Not a simple two-switch tee like R96TA or the VA 45/46 split.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Rheem R98V active code. Write 45 / 57. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Vent, trap, collector, inducer throughout the rate, pressure hose / transducer path.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Do not replace ‘the low PS’ off an R96TA card.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Watch whether the fault appears only at higher % — that is vent capacity, not a dead switch.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

93

Internal control

lockout

IFC self-fault.

  1. 1 Write the live code and watch one cycle

    On Rheem R98V read EcoNet IFC + communicating stat (Prestige / Endeavor) before you pull power. Write 93 exactly. Watch one full sequence and note which step dies. Stat log + board digits. Persistent 93 after a clean power-up is the control.

    Expect: Call: EcoNet stat requests a % capacity. Valve and inducer modulate; blower CFM follows. This is not W1 then W2.

  2. 2 Prove the circuit this code names

    Wet board from a 98% leak, polarity, leftover 24V landing on the data pair.

    Expect: A measured open, short, or out-of-range reading — not a guess.

  3. 3 Confirm with a number, then the next part

    If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.

    Expect: EcoNet pair: Communicating data. Not 24 VAC. Polarity. One master control.

Workflows

EcoNet no-heat

Homeowner says the thermostat died, or the furnace sits idle with a heat call on the EcoNet control.

  1. 1 Prove the call and the live code

    Stat diagnostics first. The EcoNet wall control is the system — do not skip it for a 2-digit glance.

    Expect: Write whatever EcoNet IFC + communicating stat (Prestige / Endeavor) is showing. EcoNet stat event history is the real log. Write board digits if the stat is dead, then restore comm before you guess.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Do not convert this furnace to 24V as a fix. You lose modulation and you may lock the IFC.

    Expect: Prove: Variable inducer must hit the pressure band for that firing rate. 45/57 are a band miss, not ‘swap the low switch.’

  3. 3 Confirm with a number, then the next part

    24 VAC present? Then data-pair polarity. Then indoor/stat on the bus. If the board shows 11/12/13, that is still ignition/flame — run a trial. If it shows 45/57, that is draft at a rate, not TA low/high switches. 93 with a live EcoNet log pointing at the control: board, not a pressure switch.

    Expect: EcoNet pair: Communicating data. Not 24 VAC. Polarity. One master control. · Capacity: Percent on the stat / IFC, not W1/W2 staging.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Identify vs R96VA

First minute on a Prestige / Endeavor 96/98% that might be two-stage.

  1. 1 Prove the call and the live code

    R98V: modulating valve, capacity in %, EcoNet stat is native, no W1/W2 two-stage story.

    Expect: Write whatever EcoNet IFC + communicating stat (Prestige / Endeavor) is showing. EcoNet stat event history is the real log. Write board digits if the stat is dead, then restore comm before you guess.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    R96VA: two-stage, 45/46/57 discrete PS on many cards, EcoNet optional, 24V W fallback is normal.

    Expect: Prove: Variable inducer must hit the pressure band for that firing rate. 45/57 are a band miss, not ‘swap the low switch.’

  3. 3 Confirm with a number, then the next part

    If you can stage W1 then W2 on a conventional stat and the valve is two-solenoid, you are not on R98V. Use the R96VA chart.

    Expect: EcoNet pair: Communicating data. Not 24 VAC. Polarity. One master control. · Capacity: Percent on the stat / IFC, not W1/W2 staging.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

EcoNet pair

Communicating data. Not 24 VAC. Polarity. One master control.

Capacity

Percent on the stat / IFC, not W1/W2 staging.

45 / 57

Draft band at the commanded rate. Not TA 45=intake / 57=exhaust, not VA 45-vs-46.

Gotchas

  • R96VA with an EcoNet stat still two-stages. This furnace modulates. The badge and the valve tell you which chart to open.
  • R97V / R97MV / R98MV / U98V / Prestige wear this communicating modulating story.
  • Forcing 24V W ‘just to get heat’ is how these IFCs get replaced next week.

Related plates

Install this plate

Install R98V / R98MV as Prestige modulating 98%. EcoNet wall control is native.

Cat IV PVC · modulating % · EcoNet required · VS ECM · R97V / Ruud U98V cousins

Control

  • EcoNet stat is part of the IFC. Do not convert this to 24V two-stage as a repair.
  • 45/57 on a modulating card are draft at a firing rate, not a two-switch TA tee.

First fire

  1. 1Pair EcoNet first. Min-fire, then ramp. Confirm percent on the control.

Do not on Rheem R98V

  • Do not apply R96VA optional-EcoNet 45/46/57 as the primary card.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • R98MV product pageProduct pageEndeavor Prestige modulating 98% (R98MV / R98V family).Open manufacturer PDF
  • Rheem residential furnacesLiterature searchR96T / R96V / R801V / R802V / R98MV product cards. I/O is typically MyRheem / PTS dealer.Open manufacturer PDF
  • Rheem supportLiterature searchOwner docs and registration. Full I/O is not hosted as a public PDF for most Endeavor plates.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    dealer

    Rheem furnace warranty

    Registered Endeavor / Classic furnace warranty · Dealer claims portal

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal