Models
Yorkfurnace

TM9T

York/JCI 96% · two-stage · multi-speed

York/Coleman/Luxaire TM9T is the multi-speed / tap-blower twin of the TM9V. Same JCI green/amber/red two-stage 96% flash chart. Airflow complaints are heat/cool taps, not a VS CFM menu.

Not TM9V (variable-speed — CFM lives in the IFC menu). Not TM8V (80% metal vent). Not Carrier 59TP6. Not Amana AR9T96.

AFUE

Two-stage 96% condensing · PVC 2-pipe

Staging

Two-stage gas valve · two-speed inducer · two pressure switches

Blower

Multi-speed / constant-torque · heat and cool taps, not a VS menu

Control

Same JCI / Coleman-York multi-color LED IFC as TM9V

Badge

Coleman TM9T and Luxaire TM9T use this same IFC

This board

JCI / Coleman-York IFC · green / amber / red LED

  • Same LED language as TM9V. Slow green idle, slow amber heat call, red counts 1–12, rapid red twinning, rapid amber weak flame, steady red control failure.
  • 1/4 s on, 1/4 s off, 2 s pause between counts. Rapid colors are not counts.
  • Two-stage 96%: two pressure switches. 3-red is still trap/PVC first.
  • The difference is the blower — taps, not a VS CFM menu. Read the tap chart on THIS TM9T door.

Active code repeats until the fault clears or 24 V is removed. Write color + count before you cycle power.

Universal swap

No universal

Two-stage. The WR single-stage kits (50A55 / 50M56U) are the wrong staging even if older York used those boards.

Silk: 50A55 · 50A65 · 50A66

White-Rodgers

ICM

Honeywell

  • 50A55-843 / 50M56U-843 / S9200U1000 (single-stage).
  • TM9V VS board. ICM2813 unless the silk is a listed SureLight / 50A66 number — it usually is not.

After you pull the dead card

  1. 1OEM York/JCI two-stage multi-speed IFC. Do not down-stage this cabinet with a single-stage universal.

Field wiring

Written landings for York TM9T. Not a factory schematic.

Furnace · two-stage 24V
R / C / W1 / W2 / Y / GGas furnace

Two-stage conventional furnace. W1 low fire, W2 high fire. Outdoor staging is Y or Y1/Y2 — separate from the gas valve.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → R120V / 24V
  2. 2Low. W1 → inducer LOW → LPS → HSI → valve LOWFirst fire
  3. 3High. W2 → inducer HIGH → HPS → valve HIGHSecond solenoid
  4. 4Flame. Rod → IFCµA DC both stages
  5. 5Blow. IFC → heat blowerAfter flame

This indoor

JCI 96% two-stage multi-speed.

24V two-stage heat

Door has W1 and W2. Not Infinity. Not ComfortBridge.

Two-stage thermostat

A single-W stat never proves high fire. That is not a weak inducer.

  • R24V hot24V
  • CCommon24V
  • W1Low-fire heat24V
  • W2High-fire heat24V
  • Y / Y1Cool24V
  • Y2Outdoor high if the condenser is two-stage24V
  • GFan24V

Two-stage IFC

W2 is high fire. Do not tee the pressure-switch hoses because there are two stages.

  • RHot24V
  • CCommon to outdoor24V
  • W1Low fire24V
  • W2High fire24V
  • YCool out24V
  • GBlower / cool tap24V

Landing

  • 24VStat W1IFC W1

    Low fire

  • 24VStat W2IFC W2

    High fire. Missing W2 = stuck on low.

  • 24VStat YIFC Youtdoor Y

    Cool

  • 24VC throughout

    Common

IFC harness — two-stage heat

W1 then W2. Low-fire prove is not high-fire prove.

Transformer + fuse

Same 24V transformer as single-stage. Fuse still kills the whole strip.

  • L1 / N120VLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout. A limit trip is not an E9 / 32 pressure-switch story.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + two pressure switches

W1 = inducer low + LPS. W2 = inducer high + HPS. Separate hoses. Do not tee.

  • IND LO120V low-speed inducerLine
  • IND HI120V high-speed inducerLine
  • LPSLow-fire prove24V
  • HPSHigh-fire prove24V
  • HOSESOne hose per switch. Never tee LPS and HPS24V

HSI + two-stage valve

Igniter 120V. Low solenoid on W1. Second solenoid on W2 after HPS closes.

  • HSI120V igniterLine
  • MV / LO24V low-fire solenoid24V
  • HV / HI24V high-fire solenoid24V
  • FLAMEµA DC on the rod24V

Blower — read the motor

PSC has a cap. 9-speed has F-taps. Serial VS has a harness and no cap. Do not mix those playbooks.

  • PSCCap + 3–5 speed leads24V
  • 9-SPDF01–F09 taps24V
  • VSFat serial plug, no cap24V

Landing

  • LineW1IFCinducer LOWLPS

    120V inducer, 24V prove

  • LineIFCHSIvalve LOW

    120V igniter, 24V low solenoid

  • 24VW2inducer HIGHHPSvalve HIGH

    Missing W2 = stuck on low

  • 24VFlame rodIFC

    µA DC

  • LineIFCheat blower

    After flame. Motor class on this plate.

Prove it

  • W1 then W2 at the IFC under a 2-heat call.
  • If it never stages, W2 is missing at the board — not a bad gas valve until that is proven.

Do not

  • Do not convert this to Infinity by landing W on a random terminal.
  • Do not apply AMVC / ARVT ComfortBridge menus or a memory card.

926T / 59TP6 / AR9T96 / GR9T96 / S9V2 / EL296E class. Same landing on 80% metal-vent cousins — the vent is not the wire.

Sequence

  1. 1

    W1

    Inducer low → low-fire PS must close (3-red / 2-red) → HSI → low-fire valve → flame → blower on the selected HEAT tap.

  2. 2

    W2

    Inducer high → high-fire PS → second solenoid. Blower may stay on the same heat tap — this is not a VS ramp.

  3. 3

    Limit path

    Wrong heat tap is the 4-red generator on TM9T. There is no CFM menu to ‘turn up’ — move the tap, then check static and rise.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

Slow green

Normal, no heat call

info

IFC powered, idle.

  1. 1 Confirm this is not a fault

    On the York TM9T this readout (Slow green) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the York TM9T IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: No W at the IFC if the house is cold.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch JCI / Coleman-York IFC · green / amber / red LED through one cycle and write the first real fault that replaces this status word.

    Expect: W1: Inducer low → low-fire PS must close (3-red / 2-red) → HSI → low-fire valve → flame → blower on the selected HEAT tap.

Slow amber

Normal, heat call

info

IFC sees W and is sequencing or running heat.

  1. 1 Confirm this is not a fault

    On the York TM9T this readout (Slow amber) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the York TM9T IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: Stay and watch if burners are out.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch JCI / Coleman-York IFC · green / amber / red LED through one cycle and write the first real fault that replaces this status word.

    Expect: W1: Inducer low → low-fire PS must close (3-red / 2-red) → HSI → low-fire valve → flame → blower on the selected HEAT tap.

Rapid red

Twinning / 24V phasing

lockout

TWIN miswire or 24 V phasing.

  1. 1 Is this cabinet actually twinned?

    On a standalone York TM9T, nothing belongs on the TWIN terminal. A leftover jumper throws this. Nothing on TWIN unless the job is actually twinned.

    Expect: TWIN empty on a single cabinet.

  2. 2 Twinned pair must be the same IFC family

    Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin.

    Expect: Same model family, same IFC, kit installed per the twinning sheet.

  3. 3 Phasing and 24 V

    Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.

    Expect: In-phase 24 V. Continuous twin lead.

Rapid amber

Flame sense < 1.5 µA

warn

Weak rod current. Normal ~3.7 µA; lockout < 0.1 µA.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on York TM9T during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod, ground, manifold. Read µA at the test pad.

    Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold on the rating plate. Solid burner-box ground.

  3. 3 Prove it is not a switch opening

    Watch the live York TM9T display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

4 amber

Y without G

warn

Cool call missing G.

  1. 1 Is the wheel free?

    Spin the York TM9T blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Stat wiring. Not a PS code.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data.

    Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu.

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.

    Expect: Static on the blower chart. Matching motor / shared-data card.

1 red

Flame sensed, no call for heat

hazard

Flame with valve de-energized.

  1. 1 Shut the gas cock first

    On York TM9T the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve is a hazard.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

2 red

Pressure switch stuck closed

lockout

PS made with inducer off.

  1. 1 Unplug the switch with the inducer off

    On York TM9T this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the switch. Water in the hose. Which of the two switches?

    Expect: Code changes when the harness is open.

    If fail: Wrong switch, or the IFC input is shorted.

    If pass: Switch/hose path. Go to step 2.

  2. 2 Water in the hose vs a welded switch

    Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off.

    Expect: Hose empty. Switch opens with no draft.

  3. 3 IFC input last

    If the switch ohms open, the hose is dry, and the code does not change with the harness off, the York TM9T IFC input is shorted. Do not keep swapping switches.

    Expect: Known-good open switch + open harness = code gone. If not, IFC.

3 red

PS failed to close after inducer

lockout

96% trap / collector / PVC / inducer — same draft physics as TM9V.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the York TM9T active code. Write 3 red. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap, collector, hose on the correct tap, PVC ice/wind, inducer 120 VAC.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Two PS. High-fire-only 3-red is the high hose / vent capacity.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: LPS / HPS: Two NO switches. Never teed.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

4 red

Limit open

warn

Airflow or overfire. On TM9T this is almost always the heat tap, not a VS menu.

  1. 1 Airflow before you touch the limit

    On York TM9T a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Read the heat tap on the motor / IFC harness and match it to the TM9T tap chart and the rise range on the plate.

    Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu.

  2. 2 Measure static and temperature rise

    Total external static vs the York TM9T blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Do not open a TM9V CFM menu — there isn’t one.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Filter, wheel, coil, return, TES. A new media cabinet on a low heat tap will 4-red all winter.

    Expect: Manifold on plate. Limit closed when cool.

5 red

Rollout open

hazard

Manual-reset rollout. Flame containment.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the York TM9T rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, flue, secondary. Reset only after the cause.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on York TM9T is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

6 red

PS opened 4 times this call

lockout

Intermittent draft drop. One-hour lockout.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the York TM9T active code. Write 6 red. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap that refills, wind, hose, high-fire vent capacity.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: LPS / HPS: Two NO switches. Never teed.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

7 red

Flame not established after 3 tries

lockout

Ignition retries exceeded.

  1. 1 Watch one full try — do not reset

    Write the York TM9T code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI glow and 120 VAC, gas, rod µA, ground.

    Expect: W1 → W2 → Limit path

  2. 2 Gas and the valve

    Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.

    Expect: Inlet and manifold on the plate. 24 VAC only during trial.

  3. 3 Flame prove, then the lockout timer

    Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.

    Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

8 red

Flame lost 5 times

lockout

Flame dropped after prove.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on York TM9T during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. µA, gas sag, draft collapse when the blower starts on that heat tap.

    Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold on the rating plate. Solid burner-box ground.

  3. 3 Prove it is not a switch opening

    Watch the live York TM9T display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

9 red

Reversed polarity / grounding

lockout

L1/N or chassis ground.

  1. 1 Hot and neutral at the IFC, not the disconnect

    On York TM9T polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC, burner ground.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

10 red

Flame sensed, no call (some boards)

hazard

Same as 1-red on later revisions.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on York TM9T during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Door card on THIS IFC. Valve leak.

    Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold on the rating plate. Solid burner-box ground.

  3. 3 Prove it is not a switch opening

    Watch the live York TM9T display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

11 red

Limit open >5 min · hard lockout

lockout

Blower never moved enough air to reclose the limit.

  1. 1 Airflow before you touch the limit

    On York TM9T a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Is the tap motor actually running? Capacitor / ECM module / wheel.

    Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu.

  2. 2 Measure static and temperature rise

    Total external static vs the York TM9T blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Heat tap too low for this cabinet + coil.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Cycle 24 VAC only after airflow is real.

    Expect: Manifold on plate. Limit closed when cool.

12 red

Open igniter circuit

lockout

HSI path open.

  1. 1 Ohms at the igniter, then at the IFC

    On York TM9T measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the plug and at the IFC. Cracked nitride.

    Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

Steady red

Control failure

lockout

Internal IFC fault.

  1. 1 Write the live code and watch one cycle

    On York TM9T read JCI / Coleman-York IFC · green / amber / red LED before you pull power. Write Steady red exactly. Watch one full sequence and note which step dies. Power and fuse first, then replace the control.

    Expect: W1: Inducer low → low-fire PS must close (3-red / 2-red) → HSI → low-fire valve → flame → blower on the selected HEAT tap.

  2. 2 Prove the circuit this code names

    Use the York TM9T door card and the test points on this plate. Isolate the named switch, sensor, or output with a meter — do not swap the IFC first.

    Expect: A measured open, short, or out-of-range reading — not a guess.

  3. 3 Confirm with a number, then the next part

    If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.

    Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu.

Workflows

4-red limit on TM9T taps

Heat runs then drops, or 11-red after a long limit.

  1. 1 Prove the call and the live code

    Confirm the plate says TM9T, not TM9V. If it is V, leave this page — the VS menu is the adjustment.

    Expect: Write whatever JCI / Coleman-York IFC · green / amber / red LED is showing. Active code repeats until the fault clears or 24 V is removed. Write color + count before you cycle power.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Photograph the heat tap. Match it to the TM9T door chart for this cabinet size and the installed coil.

    Expect: W2: Inducer high → high-fire PS → second solenoid. Blower may stay on the same heat tap — this is not a VS ramp.

  3. 3 Confirm with a number, then the next part

    Rise vs plate. A tap that ‘sounds quiet’ is often below the rise range. TES, filter, coil. Then the board fuse. Do not install a TM9V VS motor as a ‘better ECM’ without the matching IFC.

    Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu. · Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

3-red no heat

Inducer on, no light-off.

  1. 1 Prove the call and the live code

    Same 96% trap/PVC path as TM9V. Dump the trap first.

    Expect: Write whatever JCI / Coleman-York IFC · green / amber / red LED is showing. Active code repeats until the fault clears or 24 V is removed. Write color + count before you cycle power.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Two hoses, two switches. High-fire-only fail is not the low-fire switch.

    Expect: W2: Inducer high → high-fire PS → second solenoid. Blower may stay on the same heat tap — this is not a VS ramp.

  3. 3 Confirm with a number, then the next part

    Then inducer 120 VAC and the PVC termination.

    Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu. · Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Heat tap

Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu.

Flame sense

Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

LPS / HPS

Two NO switches. Never teed.

Gotchas

  • Techs treat TM9T like TM9V and hunt a CFM menu that does not exist.
  • Same LED as TM8V — if the vent is metal you are on the 80% chart.
  • Coleman/Luxaire TM9T is this page. The badge does not change taps vs VS.

Related plates

Install this plate

Install TM9T as the same JCI 96% two-stage flash language with a multi-speed tap blower.

Cat IV PVC · two-stage · dual PS · CT / tap motor · same LED as TM9V

Motor

  • Heat and cool taps. Limit/airflow is taps, not the TM9V VS menu.
  • Same 3-red PVC physics as TM9V.

First fire

  1. 1Set heat tap, W1/W2, rise vs the TM9T chart.

Do not on York TM9T

  • Do not look for a VS CFM menu.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • York residential gas furnacesLiterature searchTM9 / TM8 family listing (Coleman / Luxaire share the JCI IFC). UPGNet holds the I/O.Open manufacturer PDF
  • York / Bosch Home ComfortLiterature searchSearch York TM9T on the maker’s literature page.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    dealer

    York furnace warranty

    Registered TM8 / TM9 furnace warranty · Dealer claims portal

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal