Furnace · two-stage 24V
R / C / W1 / W2 / Y / G
Two-stage conventional furnace. W1 low fire, W2 high fire. Outdoor staging is Y or Y1/Y2 — separate from the gas valve.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → R120V / 24V
- 2Low. W1 → inducer LOW → LPS → HSI → valve LOWFirst fire
- 3High. W2 → inducer HIGH → HPS → valve HIGHSecond solenoid
- 4Flame. Rod → IFCµA DC both stages
- 5Blow. IFC → heat blowerAfter flame
24V two-stage heat
Door has W1 and W2. Not Infinity. Not ComfortBridge.
Two-stage thermostat
A single-W stat never proves high fire. That is not a weak inducer.
- R24V hot24V
- CCommon24V
- W1Low-fire heat24V
- W2High-fire heat24V
- Y / Y1Cool24V
- Y2Outdoor high if the condenser is two-stage24V
- GFan24V
Two-stage IFC
W2 is high fire. Do not tee the pressure-switch hoses because there are two stages.
- RHot24V
- CCommon to outdoor24V
- W1Low fire24V
- W2High fire24V
- YCool out24V
- GBlower / cool tap24V
Landing
- 24VStat W1IFC W1
Low fire
- 24VStat W2IFC W2
High fire. Missing W2 = stuck on low.
- 24VStat YIFC Youtdoor Y
Cool
- 24VC throughout
Common
IFC harness — two-stage heat
W1 then W2. Low-fire prove is not high-fire prove.
Transformer + fuse
Same 24V transformer as single-stage. Fuse still kills the whole strip.
- L1 / N120VLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout. A limit trip is not an E9 / 32 pressure-switch story.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + two pressure switches
W1 = inducer low + LPS. W2 = inducer high + HPS. Separate hoses. Do not tee.
- IND LO120V low-speed inducerLine
- IND HI120V high-speed inducerLine
- LPSLow-fire prove24V
- HPSHigh-fire prove24V
- HOSESOne hose per switch. Never tee LPS and HPS24V
HSI + two-stage valve
Igniter 120V. Low solenoid on W1. Second solenoid on W2 after HPS closes.
- HSI120V igniterLine
- MV / LO24V low-fire solenoid24V
- HV / HI24V high-fire solenoid24V
- FLAMEµA DC on the rod24V
9-speed tap ECM
F01–F09 on the harness. Heat tap and cool tap are separate. Not a 14-pin serial motor and not a run cap.
- F01–F09Speed taps on the IFC / harness24V
- HEATDefault often F02 — F01 is an E3 generator on many 9-speed doors24V
- COOL / Y / GCool tap. Wrong tap freezes the coil and looks like LPS outdoors.24V
Landing
- LineW1IFCinducer LOWLPS
120V inducer, 24V prove
- LineIFCHSIvalve LOW
120V igniter, 24V low solenoid
- 24VW2inducer HIGHHPSvalve HIGH
Missing W2 = stuck on low
- 24VFlame rodIFC
µA DC
- LineIFCheat blower
After flame. Motor class on this plate.
Prove it
- W1 then W2 at the IFC under a 2-heat call.
- If it never stages, W2 is missing at the board — not a bad gas valve until that is proven.
Do not
- Do not convert this to Infinity by landing W on a random terminal.
- Do not apply AMVC / ARVT ComfortBridge menus or a memory card.
926T / 59TP6 / AR9T96 / GR9T96 / S9V2 / EL296E class. Same landing on 80% metal-vent cousins — the vent is not the wire.