EcoNet inverter AC
E1 / E2
E1 / E2
Rheem / Ruud RA19AY Prestige. EcoNet on E1 and E2. RA14AZ / RA16 / RA17 are 24V — different diagrams.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFEcoNet pair
EcoNet control and a communicating indoor.
EcoNet control
E1 / E2 data. R and C still feed the control.
- R24V hot24V
- CCommon24V
- E1EcoNetData
- E2EcoNetData
Communicating indoor
R96V / matching AH on EcoNet. R96T 24V is a mixed pair.
- E1EcoNetData
- E2EcoNetData
Prestige outdoor
Inverter. No dual cap.
- E1EcoNetData
- E2EcoNetData
Outdoor line — inverter drive
208/230 into the drive. No contactor slam. DC bus can stay live after the disconnect.
- L1Line to the driveLine
- L2Line to the driveLine
- GNDEquipment groundLine
Landing
- DataControl E1/E2indooroutdoor
EcoNet data. Not Y.
- LineL1 / L2drive
208/230
Prove it
- EcoNet control sees the outdoor.
- E1 / E2 polarity per the silk on THIS outdoor.
Do not
- Do not apply this to RA14AZ / RA16 / RA17.
- Do not land 24V Y on E1.
E1 / E2 are the published EcoNet pair.