Amana

AMVM97

Furnace · ComfortBridge · modulating · communicating VS · 97% AFUE

Modulating ComfortBridge 97% cousin of AMVC96. Same triple 7-seg IFC language (idle/Ht, E/b/d) but capacity is 0–100% through a modulating valve and a variable inducer — not two-stage W1/W2 solenoids. Sister of Goodman GMVM97. Do not apply AMVC96 two-stage staging tests.

Not AMVC96 / GMVC96 (two-stage valve, two-speed inducer, W1/W2 or Ht1/Ht2 staging). Not AR9T96 (9-speed tap, conventional 24V). If the gas valve has two discrete solenoids and the inducer is two-speed, leave this page.

Walk this in Diagnose

This plate

Input / AFUE
Up to 97% · 60–120 kBtu family · modulating heat
Staging
Modulating gas valve 0–100% · variable-speed inducer · pressure-band prove (not a W1/W2 tee)
Blower
Communicating variable-speed ECM (serial CFM, no tap plugs)
Heat exch.
Stainless tubular primary + stainless secondary
Ignition
120 VAC silicon nitride HSI
Vent
PVC 2-pipe or 1-pipe
Control
ComfortBridge IFC · triple 7-segment + menu buttons + CoolCloud Bluetooth
Tstat
ComfortBridge / communicating preferred — stat requests percent capacity, not W2. 24V fallback exists; CFM still from IFC tables.
Sister SKU
Goodman GMVM97 same IFC · AMVC96 is the two-stage cousin

This board

ComfortBridge IFC · three 7-segment digits + menu buttons

  • Same triple 7-seg and E/b/d language as AMVC96. Status words (idle, Ht, CF) are run states, not faults. Capacity is a percent, not Ht1 vs Ht2 staging.
  • E2 / E9 are pressure-band / inducer proves as the variable inducer ramps — not ‘the low PS vs high PS tee’ from a two-stage collector. Do not start teeing hoses or looking for a W2 solenoid.
  • Shared-data memory card is required after an IFC swap (d0/d4). Use the AMVM97 card, not an AMVC96 two-stage card.
  • Force high fire from the IFC menu / CoolCloud gas-pressure test (GPT), not by jumping W2. There is no second-stage solenoid to energize.
  • 24V fallback may accept a W call. The valve still modulates from IFC tables. A W2 wire does not create high fire.

Sequence

  1. Call. Communicating stat requests a percent capacity. This is not a W2 close. On 24V fallback a W call starts heat; the IFC still picks the firing rate from its tables.
  2. Variable inducer / prove. Inducer ramps to the pressure band for that rate. E2 = will not prove the running band (trap, hose, vent, inducer). E9 = will not make the high-capacity draft band. These are not a low-tee vs high-tee two-stage test.
  3. HSI / modulating valve. Nitride warm-up, then the modulating valve opens to the requested percent. Open igniter / no-ground → E7. Flame must prove. Failures stack toward E0.
  4. Blower. Serial ECM CFM follows capacity from the IFC tables. Same b0/b1/d0 motor-and-card rules as AMVC96. No tap plugs.
  5. Modulate. Valve and inducer track load. Do not expect a discrete low-to-high step. High-fire manifold is a menu/GPT test, not a W2 jump.
  6. Satisfied. Valve closed, inducer post-purge, blower delay. Unexpected flame → E4.

Faults on this IFC

  • idle / Ht / CF

    Status, not a fault

    info

    Normal run states. idle = standby. Ht = heat running (capacity is a percent, not Ht1/Ht2 stages). CF = continuous fan.

    • Do not replace the board because it says Ht or CF.
    • Ht that never climbs off a low rate is a prove / valve / menu problem, not a ‘stuck Ht1’ two-stage code.
  • E0

    System / ignition lockout

    lockout

    Failed to sense flame after 3 retries. 1-hour auto reset.

    • Watch one full try: inducer ramp, HSI, valve, flame, µA.
    • Gas supply. Modulating valve actually opening (not a stuck two-stage solenoid test).
    • Rod and ground. Do not sit on hourly resets.
  • E2

    Pressure-band open / inducer will not prove

    lockout

    Variable inducer is running and the pressure switch / band for that rate never made. Same 96% trap/hose/vent physics as other Amana condensing furnaces — not ‘unplug the low-fire tee.’

    • Inducer actually spinning and ramping? 120 VAC and a speed change.
    • Trap, collector, and condensate first.
    • Hose dry, on the correct port, not pinched. Cracked hose fakes an open band.
    • Vent/intake ice, bird screen, long run, wind.
  • E3

    Open primary / aux / rollout limit

    warn

    Limit opened. Airflow or overfire. Rollout is still a manual-reset hazard.

    • IFC heat CFM, not a tap. Filter, coil, static.
    • Firing rate vs plate — a valve stuck toward 100% will limit.
    • Limit ohms after it cools. Recurring rollout → exchanger / burners / flue.
  • E4

    Flame sensed with no call for heat

    hazard

    Rod sees flame with the modulating valve commanded closed.

    • Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
    • Rod shorted to ground or IFC flame circuit.
  • E5

    Open 24V fuse

    warn

    Low-voltage fuse open. Operation inhibited except the display.

    • 24 V short on the stat harness, humidifier, EAC, or a leftover data pair on R/C.
    • Unplug the harness and replace the fuse. Repeat blow = board or valve harness.
  • E6

    Low flame-sense µA

    warn

    Flame present, signal below threshold. Lazy flame at a low modulating rate is a common miss.

    • Clean rod, chassis ground.
    • Manifold at the rate the IFC is actually firing, not just a ‘high-fire’ number.
    • LP conversion and orifice.
  • E7

    Igniter open / no-ground

    lockout

    Igniter open, unplugged, or ground check failed.

    • Nitride ohms per sticker. 120 VAC during warm-up.
    • Burner-box ground. Cracked element.
  • E9

    High-capacity pressure band open

    lockout

    Inducer will not make the high-rate draft band. This is not ‘the high-fire PS tee on a two-stage collector.’ The unit may run at a reduced percent and never reach high fire.

    • Force high fire from the IFC / CoolCloud GPT menu — do not jump W2.
    • Inducer actually at high speed? Variable inducer that will not climb is E9 with a good switch.
    • Vent sized for high fire on this cabinet. Trap that only loads at high rate.
    • Hose and switch for the high band. Do not tee it to a two-stage mindset.
  • EA

    Reversed polarity / poor ground

    lockout

    L1/N reversed or chassis ground missing. Furnace will not operate.

    • Hot and neutral at the IFC.
    • Burner-box ground screw.
  • EE

    No 115V to control / internal / door switch

    lockout

    No line voltage, door switch open, or internal control condition. This is power, not a data-pair code.

    • Switch, breaker, door switch. 115 VAC at L1/N.
    • If the IFC is alive and the stat is dark, that is the data pair — not EE.
  • b0

    ECM blower not running

    lockout

    IFC commanded the serial ECM and does not detect it running.

    • 14-pin harness at motor and IFC. No tap plugs.
    • Do not install an AR9T96 9-speed or an AMVC96 motor of the wrong HP.
    • Wheel free, 120 VAC to the motor.
  • b1

    ECM communications lost

    lockout

    IFC cannot talk to the variable-speed blower.

    • 14-pin seated, pins straight.
    • Motor vs IFC: known-good motor still b1 = IFC serial driver.
  • b2 / b3 / b9

    Motor HP / limiting / low CFM

    warn

    b2 = motor HP does not match the shared-data set. b3 = motor folding back on power/speed/temp. b9 = airflow below calculated minimum.

    • Correct AMVM97 motor and memory card.
    • Static, filter, coil. CFM follows modulating rate — a brick duct still b9s.
    • Wrong CoolCloud outdoor type / CFM table.
  • d0 / d4

    Shared data / memory card

    lockout

    d0 = no shared-data set on a replacement IFC. d4 = wrong-model card.

    • Install the AMVM97 card, not an AMVC96 two-stage card.
    • GMVM97 twin card is the usual cross. AVPTC / AR9T96 cards are d4.
    • Empty tables will not drive the serial ECM or calculate CFM.

Workflows

Identify AMVM97 vs AMVC96

First minute. Data plate dirty, or the last tech treated it as two-stage.

  1. Data plate: AMVM97 / GMVM97 = stay here. AMVC96 / GMVC96 = two-stage ComfortBridge — leave this page.
  2. Gas valve: one modulating body (stepper / servo). Two discrete solenoids = AMVC96, not this chart.
  3. Inducer: variable speed that ramps with rate. A two-speed inducer that only has low/high is AMVC96.
  4. Do not jump W2 to ‘force high.’ Use CoolCloud or the IFC GPT / gas-pressure test menu.
  5. Triple 7-seg + 14-pin serial ECM is shared with AMVC96 — the valve and inducer are how you tell them apart, not the display.

No heat (stat requests %, not W2)

Communicating stat shows a heat request, furnace idle or E0/E2/E7.

  1. Photograph the triple display and the stat (requested percent, not a W2 icon) before you pull a wire.
  2. Communicating or 24V fallback? A W call on fallback still does not create a W2 high-fire path.
  3. Data pair polarity if communicating. Door switch / 115 VAC (EE). 24V fuse (E5).
  4. Inducer ramping? Silent → inducer / IFC. Running and E2 → trap, hose, vent, pressure-band switch — not a low-fire tee.
  5. HSI glow? No + E7 → igniter/ground. Glow, no flame → gas cock and modulating valve actually opening.
  6. Flame then drop → E6 / E0. Low-rate lazy flame is common — check µA at the rate it is firing.
  7. Motor silent + b0/b1 → 14-pin and card (d0) before a board. Do not hang a 9-speed tap motor here.

E2 / E9 on a modulator

Will not light, or runs but never reaches high rate.

  1. These are pressure-band / inducer codes. Do not apply the AMVC96 ‘LPS tap vs HPS tap’ tee lecture.
  2. Trap and collector first. Variable inducer that hunts or drops out of band looks like intermittent E2.
  3. Force high fire from GPT / CoolCloud to reproduce E9. If the inducer never climbs, it is the inducer, not a high-fire switch tee.
  4. Vent sized for high fire. A 2" run that proved at 40% will fail at 100%.
  5. Then ohm the switch at that inducer speed. Closed and still E2/E9 = IFC input.

Test points

Data pair
OEM communicating voltage / polarity — never 24 VAC between the data pins.
Modulating valve
Single modulating body. High-fire manifold from IFC/CoolCloud GPT, not a W2 jump. Plate wins.
Inducer
Variable speed. Must ramp with requested rate. 120 VAC present; speed change on a high-fire menu test.
Pressure band
Switch(es) prove draft at the running band. Not a two-stage low/high tee.
Flame rod
µA per this IFC sticker at the rate it is firing, not only at high fire.
Motor harness
14-pin serial ECM. No tap plugs. Correct AMVM97 HP / card.
Memory card
AMVM97 (or GMVM97 twin) after an IFC swap. AMVC96 card is d4.

Gotchas

  • Looks like AMVC96 until you look at the valve. Two-stage staging tests and W2 jumps waste the call.
  • E2/E9 are pressure-band / inducer, not the AR9T96/AMVC96 low-tee vs high-tee story.
  • GMVM97 is the Goodman-badge twin. Same chart. GMVC96 is the two-stage twin — wrong page.
  • d0 after a board swap needs the AMVM97 card. An AMVC96 card will d4 and the motor will sit.
  • Low-rate E6 is not always a dirty rod. Confirm manifold at the percent the IFC is actually firing.

Related plates

  • amana-amvc96 — Two-stage ComfortBridge cousin — dual solenoids, two-speed inducer, E1/E2 vs E8/E9 tees. Do not use that staging playbook here.
  • goodman-gmvm97 — Goodman-badge twin. Same modulating ComfortBridge IFC.