ComfortBridge communicating 96% two-stage furnace with a serial variable-speed ECM and a triple 7-segment IFC. Dual pressure switches and a two-speed inducer still exist — E1/E2 are low fire, E8/E9 are high fire. Sister of Goodman GMVC96. This is not AR9T96 (9-speed tap, single 7-seg), not ARVT96 (newer ComfortBridge R-32 plate — ARVT96 memory card, 0.5" heat-ESP hard limit), and not AMVM97 (modulating valve + variable inducer).
Not AR9T96 / GR9T96 (9-speed tap ECM, conventional 24V, single 7-seg E0–E9, 2-second recall hold). Not ARVT96 / ADVT96 (newer ComfortBridge two-stage VS R-32 — same E/b/d language, different memory card and a 0.5" heat-ESP hard limit on that SS). Not AMVM97 / GMVM97 (modulating 0–100% valve, variable inducer — do not run W1/W2 staging tests). Not AM9S96 (single-stage flash).
Two-stage gas valve · two-speed inducer · dual pressure switches
Blower
Communicating variable-speed ECM (serial CFM, no tap plugs)
Heat exch.
Stainless tubular primary + stainless secondary
Ignition
120 VAC silicon nitride HSI
Vent
PVC 2-pipe or 1-pipe · 40 ng/J Low NOx (not SCAQMD after 2019)
Control
ComfortBridge IFC · triple 7-segment + menu buttons + CoolCloud Bluetooth
Tstat
ComfortBridge / communicating preferred · 24V W1/W2 fallback (CFM still from IFC tables)
Sister SKU
Goodman GMVC96 same IFC · AMVM97 is the modulating cousin · AVPTC matching communicating AHU
This board
ComfortBridge IFC · three 7-segment digits + menu buttons
Three digits, not the AR9T96 single 7-seg. Status words (idle, Ht1, Ht2, CF, CL1, CL2) are run states, not faults. Do not replace a board because it says Ht1.
Faults are letter+digit: E0–E9, EA, EE, b0–b9, d0/d4. Write the exact token off THIS door card — ComfortBridge menus moved between board generations.
Shared-data memory card is required after an IFC swap. d0 = no card / empty set. d4 = wrong-model card. The replacement board will not drive the serial ECM without the correct AMVC96 card.
ComfortBridge Bluetooth / CoolCloud is the menu for CFM, outdoor type, and (on an AHU) electric heat. On this furnace the heat CFM still comes from IFC tables, not 9-speed taps.
24V fallback exists (W1/W2/Y/G). CFM still comes from the IFC tables, not tap plugs. A leftover data pair shorted to R/C will look like a dead bus.
A communicating outdoor on the same bus changes what a ‘no Y’ complaint means — the IFC may be the thermostat.
Sequence
Call. Communicating stat requests heat capacity. On 24V fallback, W1/W2 behave like a two-stage furnace but blower CFM still comes from the IFC tables, not taps.
Prove limits. IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.
Low inducer / LPS. Two-speed inducer starts low. Low-stage PS must close. Already closed with inducer off → E1. Never closes (5 min then 1-hour lockout) → E2. Same physics as AR9T96, E1/E2 on this board.
HSI / low-fire valve. Silicon nitride warm-up, then first-stage solenoid. Open igniter / no-ground → E7. Flame must prove at the rod. Failures stack toward E0 (3 retries, 1-hour auto reset).
Blower. Serial ECM ramps to the IFC heat CFM table. No tap plugs. Silent motor → b0/b1. Wrong motor HP vs the shared-data set → b2. Do not hang an AR9T96 9-speed motor on this harness.
High fire. Communicating capacity or W2. Inducer goes high. High-stage PS must close (E9 if open — no high fire; E8 if it was already closed — runs low only). Second-stage solenoid opens.
Normal run states on the triple display. idle = standby. Ht1 / Ht2 = low / high heat. CF = continuous fan. CL1 / CL2 = cooling stage.
Do not replace the board because it says Ht1 or CF.
CF is continuous-fan CFM, not a capacitor.
Ht1 forever with a high-fire request → staging / E8–E9 path, not a ‘bad Ht1 code.’
E0
System / ignition lockout
lockout
Control failed to sense flame after 3 full ignition retries and shut off gas. Auto-resets after 1 hour (or a tstat cycle).
Watch one full try: inducer, HSI glow, valve click, flame, µA.
Gas supply and manifold (low then high).
Ground and flame-rod cleanliness.
Do not sit on hourly resets — find which step dies.
E1
Low-stage PS stuck closed
lockout
Low-stage pressure switch is made with the inducer off. Control waits for the fault to clear.
Unplug the LPS. If the code changes, the switch is welded or the hose is holding residual draft.
Hose routed downhill to the collector? Water in the hose fakes a closed switch.
IFC input shorted — only after the switch ohms open.
E2
Low-stage PS stuck open
lockout
Inducer is on low and the low-stage switch did not close within 5 minutes. Then 1-hour lockout and retry.
Inducer spinning? 120 VAC at the inducer on a heat call.
Collector box, inducer outlet, and condensate trap — this 96% will not make pressure with a full trap.
PVC intake/exhaust (bird screen, ice, long run, wind).
LPS hose cracked or on the wrong port (low vs high tap).
E3
Open primary / aux / rollout limit
warn
A limit opened. Both blowers typically run until it recloses. Airflow or overfire — not a charge problem. Rollout is still a manual-reset hazard.
IFC heat CFM setting, not a 9-speed tap.
Filter, blower wheel, A-coil, return size, total external static.
Manifold pressure on low and high vs rating plate.
Limit ohms after it cools. Recurring rollout → exchanger / burners / flue before you reset and leave.
E4
Flame sensed with no call for heat
hazard
Rod sees flame with both solenoids de-energized. Control runs circulator and inducer and will not fire again.
Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
Rod shorted to ground or IFC flame circuit.
Treat as a hazard until the valve is proven closed.
E5
Open 24V fuse
warn
Low-voltage fuse on the IFC is open. All furnace operation is inhibited except the error display.
24 V short on W, Y, G, humidifier, EAC, or a leftover data pair landed on R/C.
Unplug the tstat / data harness and replace the fuse. If it blows again the short is on the board or gas-valve harness.
E6
Low flame-sense µA
warn
Flame is present but the micro-amp signal is below the IFC threshold.
Clean rod with a non-scratch pad — not sandpaper.
Chassis ground to burner box and IFC.
Manifold pressure / orifice / LP conversion.
E7
Igniter open / no-ground
lockout
Igniter is open, not connected, or the IFC failed its ground check on the igniter circuit.
Igniter ohms cold (confirm sticker — nitride, not a 80% Norton chart).
120 VAC to igniter during warm-up.
Cracked nitride element. Burner-box ground screw and painted-cabinet star washer.
E8
High-stage PS stuck closed
lockout
High-stage pressure switch is made with the inducer not on high. Furnace runs low only regardless of demand.
This is the second switch — do not confuse with E1.
Welded HPS or water-filled hose.
IFC calling high when it should be low — W2 shorted to W1 on 24V fallback.
E9
High-stage PS stuck open
lockout
Inducer on high, high-stage switch never closes. Classic ‘runs on low, will not go high.’
Inducer actually changes speed on a high-fire request? Listen / amp it.
HPS hose on the high-fire tap, not teed to the low switch.
Vent capacity / wind / shared chase. High fire needs more draft than E2 ever saw.
Condensate backing into the collector only under high fire.
EA
Reversed polarity / poor ground
lockout
L1/N reversed or chassis ground missing. HSI and flame sense both suffer. Furnace will not operate.
Hot and neutral at the IFC, not just the disconnect.
Burner box to IFC ground screw.
24V transformer leads swapped on a replacement IFC.
EE
No 115V to control / internal / door switch
lockout
No line voltage reaching the IFC, door switch open, or an internal control condition. This is power, not a ComfortBridge data-pair code.
Furnace switch, breaker, and blower-door switch fully made.
115 VAC at L1/N on the IFC.
Do not confuse EE on this board with a comms complaint — check the data pair separately if the stat is dark and the IFC is alive.
b0
ECM blower not running
lockout
IFC commanded the serial ECM and does not detect it running. Furnace will not operate.
14-pin harness seated at motor and IFC. No tap plugs on this motor.
120 VAC to the motor, wheel free, no wet winding.
Do not install an AR9T96 9-speed motor as a ‘cheaper ECM’ — it will not talk this serial bus.
b1
ECM communications lost
lockout
IFC cannot communicate with the variable-speed blower. Furnace will not operate.
Same 14-pin harness — pins bent, corrosion, half-seated.
Motor vs IFC: if a known-good motor still b1s, the IFC serial driver is the fault.
Power-cycle once to see if it is a hard loss or a glitch after a static event.
b2
Motor HP mismatch vs shared-data set
lockout
Connected motor horsepower does not match the value in the furnace shared-data set. Furnace will not operate.
Wrong replacement motor for this cabinet size.
Wrong memory card after an IFC swap (see d0/d4).
Do not ‘make it work’ with a different HP ECM — ComfortBridge CFM tables are card-specific.
b3
Motor limiting (power / speed / temp)
warn
ECM is folding back on power, speed, or temperature. Furnace keeps running at reduced CFM.
Filter, coil, and total external static vs the AMVC96 blower chart.
Return undersized or a 5" media cabinet the installer added.
High ambient around the motor (closet, no ventilation).
b4 / b5 / b7
Motor trip / locked rotor / failed start
lockout
b4 = lost rotor or overload trip (shuts down and retries). b5 = locked rotor after 10 start attempts. b7 = motor parameters missing or failed to start after 40 attempts.
Wheel rub, debris in the housing, seized bearings.
Static so high the motor cannot start the wheel.
Harness intermittents look like b7. Prove the 14-pin before a motor or IFC.
Adjacent b-codes on some door cards are the same family — same harness/static/motor path.
b9
Low indoor airflow
warn
Indoor airflow fell below the calculated minimum. Furnace stages down (high to low) and will halt if CFM reaches 0.
IFC heat/cool CFM setting vs the coil and the outdoor.
TES. A communicating motor will ramp into a brick and then b9 / E3.
d0 / d4
Shared data / memory card
lockout
d0 = IFC has no shared-data set (replacement board, missing card) and cannot drive the serial ECM or calculate CFM. d4 = card rejected (wrong model card).
After an IFC swap the AMVC96 memory card must be installed and seated.
A GMVC96 card usually twins; an AMVM97, AVPTC, or AR9T96 card is d4.
Do not run the furnace on empty shared data and guess CFM.
Workflows
No heat on ComfortBridge
Communicating stat shows a heat call, furnace idle or locked, or the display is dark.
Photograph the triple display and the stat error before you pull a wire or kill power.
Is the IFC in communicating mode or 24V fallback? That changes every next step. Leftover data wires on a converted job shorted to R/C will take the bus down.
If communicating: data-pair polarity and splices (never 24 VAC between the data pins), one master, and whether the outdoor is crashing the bus.
If 24V fallback: W1 at the IFC (R to W ~24 VAC), then inducer / dual PS / HSI as a two-stage 96%.
Door switch in? 115 VAC at L1 (EE if not). 24 VAC across the fuse (E5 if open).
Inducer on low? Silent → inducer / IFC output. Running and E2 → trap, hose, LPS, vent. E1 with inducer off → unplug LPS.
HSI glow? No glow + E7 → igniter / ground. Glow but no flame → gas cock, valve 24 VAC, manifold. Flame then drop → E6 / E0.
Motor silent with a heat call and b0/b1 → 14-pin harness and static before a board. Do not install an AR9T96 9-speed motor.
b0 / b1 / b-family motor
Display is b0, b1, b2, b3, b4, b5, b7, or b9. Blower silent or folding back.
14-pin serial harness at the motor and at the IFC. Fully seated, no bent pins, no tap adapters.
This is not an AR9T96 9-speed. A tap-plug ECM will not run and will throw b0/b1/b2. Do not install one as a ‘cheaper ECM.’
Total external static vs the AMVC96 chart for this cabinet. b3/b9 are airflow, not a bad motor.
b2 or d0/d4 after a parts-runner motor or IFC — HP and shared-data card must match this SKU.
Wheel free? Rub, wet winding, or locked rotor is b4/b5. Forty failed starts is b7 — find why it will not spin before you shotgun the IFC.
Replace motor and IFC only after comms, static, and the memory card are proven.
d0 after a board swap
Replacement IFC, display d0 or d4, motor will not run.
A replacement ComfortBridge IFC ships without this furnace’s shared-data set. d0 is expected until the card is in.
Install the correct AMVC96 memory card (Goodman GMVC96 twin card is the usual cross). Seat it fully.
d4 = wrong card. An AMVM97, AVPTC, AR9T96, or generic ‘96%’ card will be rejected.
After the card takes, verify CoolCloud / IFC menu outdoor type and CFM before you leave. Empty tables give you a running furnace that limits or b9s all winter.
E2 / E9 draft (dual PS still exist)
No heat, or runs on low only. Display E2 or E9.
ComfortBridge did not delete the dual pressure switches. E2 is low-fire prove, E9 is high-fire prove — two hoses, two taps, never teed.
Trap and collector first. A drowned 96% looks like E2 overnight and E9 on the first cold morning that actually calls high.
Inducer actually on (E2) or actually on high (E9)? 120 VAC and a speed change. A dead high-speed winding is E9 with a perfect HPS.
Hoses: LPS on the low tap, HPS on the high tap. Water in a hose fakes E1/E8. Cracked hose fakes E2/E9.
Vent/intake: bird screen, ice, long 2" on a 100–120 kBtu high fire, wind on a sidewall pair.
Then ohm the switch with that inducer speed running. If it closes and the IFC still E2/E9s, the IFC input is the fault.
Test points
Data pair
OEM communicating voltage / polarity — never 24 VAC between the data pins.
Motor harness
14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.
Flame rod
µA per this IFC sticker, not the AR9T96 card. Rising while running is the goal.
LPS / HPS
Both NO. Two hoses, two taps, never teed. Closed only when that inducer speed is making the collector setpoint.
Manifold low / high
Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
HSI
Nitride, 120 VAC during warm-up. Cold ohms per sticker.
Memory card
Seated AMVC96 (or GMVC96 twin) card after any IFC swap. d0 empty, d4 wrong card.
24V fuse / door
Fuse intact (E5). Door switch made, 115 VAC at L1 (EE if not).
Gotchas
Techs treat AMVC96 like AR9T96 and start counting a single 7-seg or looking for heat taps. There are none. Triple display + 14-pin serial motor.
EE on this board is line voltage / door / internal — not a ComfortBridge comm code. A dark stat with a live IFC is a data-pair problem, not EE.
E2 vs E9: fixing the trap clears low fire and the callback is ‘still no high fire’ because the HPS hose was never on the high tap. Dual PS still exist.
AMVM97 looks identical in the basement and is modulating. W1/W2 staging tests and E8/E9-as-a-tee will lie. Confirm the valve and the data plate.
GMVC96 is the Goodman-badge twin. Same IFC, same card family, same chart. GM9S96 / GR9T96 are not.
Door cards differ by board generation. A 2014 AMVC96 card is wrong on a later triple-display replacement IFC — read the sticker in THIS blower.
24V fallback does not turn this into a tap furnace. CFM still comes from the IFC tables. Wrong CoolCloud outdoor type / CFM is an E3/b9 generator.
Related plates
amana-arvt96 — Newer ComfortBridge two-stage VS R-32 plate. Same E/b/d language — ARVT96 memory card, 0.5" heat-ESP hard limit. Do not drop this AMVC96 card into that cabinet.
amana-amvm97 — Modulating cousin — 0–100% valve and variable inducer. Do not apply AMVC96 two-stage staging tests.
goodman-gmvc96 — Goodman-badge twin. Same ComfortBridge IFC and the same E/b/d chart.
amana-ar9t96 — 9-speed tap, conventional 24V, single 7-seg. Do not use that chart on this communicating VS IFC.
amana-avptc — Matching ComfortBridge communicating air handler — electric heat, no gas, no inducer.