Amana

AMVC96

Furnace · ComfortBridge · two-stage · communicating VS · 96% AFUE

ComfortBridge communicating 96% two-stage furnace with a serial variable-speed ECM and a triple 7-segment IFC. Dual pressure switches and a two-speed inducer still exist — E1/E2 are low fire, E8/E9 are high fire. Sister of Goodman GMVC96. This is not AR9T96 (9-speed tap, single 7-seg), not ARVT96 (newer ComfortBridge R-32 plate — ARVT96 memory card, 0.5" heat-ESP hard limit), and not AMVM97 (modulating valve + variable inducer).

Not AR9T96 / GR9T96 (9-speed tap ECM, conventional 24V, single 7-seg E0–E9, 2-second recall hold). Not ARVT96 / ADVT96 (newer ComfortBridge two-stage VS R-32 — same E/b/d language, different memory card and a 0.5" heat-ESP hard limit on that SS). Not AMVM97 / GMVM97 (modulating 0–100% valve, variable inducer — do not run W1/W2 staging tests). Not AM9S96 (single-stage flash).

Walk this in Diagnose

This plate

Input / AFUE
Up to 96% · 40–120 kBtu family · two-stage heat
Staging
Two-stage gas valve · two-speed inducer · dual pressure switches
Blower
Communicating variable-speed ECM (serial CFM, no tap plugs)
Heat exch.
Stainless tubular primary + stainless secondary
Ignition
120 VAC silicon nitride HSI
Vent
PVC 2-pipe or 1-pipe · 40 ng/J Low NOx (not SCAQMD after 2019)
Control
ComfortBridge IFC · triple 7-segment + menu buttons + CoolCloud Bluetooth
Tstat
ComfortBridge / communicating preferred · 24V W1/W2 fallback (CFM still from IFC tables)
Sister SKU
Goodman GMVC96 same IFC · AMVM97 is the modulating cousin · AVPTC matching communicating AHU

This board

ComfortBridge IFC · three 7-segment digits + menu buttons

  • Three digits, not the AR9T96 single 7-seg. Status words (idle, Ht1, Ht2, CF, CL1, CL2) are run states, not faults. Do not replace a board because it says Ht1.
  • Faults are letter+digit: E0–E9, EA, EE, b0–b9, d0/d4. Write the exact token off THIS door card — ComfortBridge menus moved between board generations.
  • Shared-data memory card is required after an IFC swap. d0 = no card / empty set. d4 = wrong-model card. The replacement board will not drive the serial ECM without the correct AMVC96 card.
  • ComfortBridge Bluetooth / CoolCloud is the menu for CFM, outdoor type, and (on an AHU) electric heat. On this furnace the heat CFM still comes from IFC tables, not 9-speed taps.
  • 24V fallback exists (W1/W2/Y/G). CFM still comes from the IFC tables, not tap plugs. A leftover data pair shorted to R/C will look like a dead bus.
  • A communicating outdoor on the same bus changes what a ‘no Y’ complaint means — the IFC may be the thermostat.

Sequence

  1. Call. Communicating stat requests heat capacity. On 24V fallback, W1/W2 behave like a two-stage furnace but blower CFM still comes from the IFC tables, not taps.
  2. Prove limits. IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.
  3. Low inducer / LPS. Two-speed inducer starts low. Low-stage PS must close. Already closed with inducer off → E1. Never closes (5 min then 1-hour lockout) → E2. Same physics as AR9T96, E1/E2 on this board.
  4. HSI / low-fire valve. Silicon nitride warm-up, then first-stage solenoid. Open igniter / no-ground → E7. Flame must prove at the rod. Failures stack toward E0 (3 retries, 1-hour auto reset).
  5. Blower. Serial ECM ramps to the IFC heat CFM table. No tap plugs. Silent motor → b0/b1. Wrong motor HP vs the shared-data set → b2. Do not hang an AR9T96 9-speed motor on this harness.
  6. High fire. Communicating capacity or W2. Inducer goes high. High-stage PS must close (E9 if open — no high fire; E8 if it was already closed — runs low only). Second-stage solenoid opens.
  7. Satisfied. Valve off, inducer post-purge, blower heat-off delay. Unexpected flame after valve-off → E4.

Faults on this IFC

  • idle / Ht1 / Ht2 / CF / CL1 / CL2

    Status, not a fault

    info

    Normal run states on the triple display. idle = standby. Ht1 / Ht2 = low / high heat. CF = continuous fan. CL1 / CL2 = cooling stage.

    • Do not replace the board because it says Ht1 or CF.
    • CF is continuous-fan CFM, not a capacitor.
    • Ht1 forever with a high-fire request → staging / E8–E9 path, not a ‘bad Ht1 code.’
  • E0

    System / ignition lockout

    lockout

    Control failed to sense flame after 3 full ignition retries and shut off gas. Auto-resets after 1 hour (or a tstat cycle).

    • Watch one full try: inducer, HSI glow, valve click, flame, µA.
    • Gas supply and manifold (low then high).
    • Ground and flame-rod cleanliness.
    • Do not sit on hourly resets — find which step dies.
  • E1

    Low-stage PS stuck closed

    lockout

    Low-stage pressure switch is made with the inducer off. Control waits for the fault to clear.

    • Unplug the LPS. If the code changes, the switch is welded or the hose is holding residual draft.
    • Hose routed downhill to the collector? Water in the hose fakes a closed switch.
    • IFC input shorted — only after the switch ohms open.
  • E2

    Low-stage PS stuck open

    lockout

    Inducer is on low and the low-stage switch did not close within 5 minutes. Then 1-hour lockout and retry.

    • Inducer spinning? 120 VAC at the inducer on a heat call.
    • Collector box, inducer outlet, and condensate trap — this 96% will not make pressure with a full trap.
    • PVC intake/exhaust (bird screen, ice, long run, wind).
    • LPS hose cracked or on the wrong port (low vs high tap).
  • E3

    Open primary / aux / rollout limit

    warn

    A limit opened. Both blowers typically run until it recloses. Airflow or overfire — not a charge problem. Rollout is still a manual-reset hazard.

    • IFC heat CFM setting, not a 9-speed tap.
    • Filter, blower wheel, A-coil, return size, total external static.
    • Manifold pressure on low and high vs rating plate.
    • Limit ohms after it cools. Recurring rollout → exchanger / burners / flue before you reset and leave.
  • E4

    Flame sensed with no call for heat

    hazard

    Rod sees flame with both solenoids de-energized. Control runs circulator and inducer and will not fire again.

    • Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
    • Rod shorted to ground or IFC flame circuit.
    • Treat as a hazard until the valve is proven closed.
  • E5

    Open 24V fuse

    warn

    Low-voltage fuse on the IFC is open. All furnace operation is inhibited except the error display.

    • 24 V short on W, Y, G, humidifier, EAC, or a leftover data pair landed on R/C.
    • Unplug the tstat / data harness and replace the fuse. If it blows again the short is on the board or gas-valve harness.
  • E6

    Low flame-sense µA

    warn

    Flame is present but the micro-amp signal is below the IFC threshold.

    • Clean rod with a non-scratch pad — not sandpaper.
    • Chassis ground to burner box and IFC.
    • Manifold pressure / orifice / LP conversion.
  • E7

    Igniter open / no-ground

    lockout

    Igniter is open, not connected, or the IFC failed its ground check on the igniter circuit.

    • Igniter ohms cold (confirm sticker — nitride, not a 80% Norton chart).
    • 120 VAC to igniter during warm-up.
    • Cracked nitride element. Burner-box ground screw and painted-cabinet star washer.
  • E8

    High-stage PS stuck closed

    lockout

    High-stage pressure switch is made with the inducer not on high. Furnace runs low only regardless of demand.

    • This is the second switch — do not confuse with E1.
    • Welded HPS or water-filled hose.
    • IFC calling high when it should be low — W2 shorted to W1 on 24V fallback.
  • E9

    High-stage PS stuck open

    lockout

    Inducer on high, high-stage switch never closes. Classic ‘runs on low, will not go high.’

    • Inducer actually changes speed on a high-fire request? Listen / amp it.
    • HPS hose on the high-fire tap, not teed to the low switch.
    • Vent capacity / wind / shared chase. High fire needs more draft than E2 ever saw.
    • Condensate backing into the collector only under high fire.
  • EA

    Reversed polarity / poor ground

    lockout

    L1/N reversed or chassis ground missing. HSI and flame sense both suffer. Furnace will not operate.

    • Hot and neutral at the IFC, not just the disconnect.
    • Burner box to IFC ground screw.
    • 24V transformer leads swapped on a replacement IFC.
  • EE

    No 115V to control / internal / door switch

    lockout

    No line voltage reaching the IFC, door switch open, or an internal control condition. This is power, not a ComfortBridge data-pair code.

    • Furnace switch, breaker, and blower-door switch fully made.
    • 115 VAC at L1/N on the IFC.
    • Do not confuse EE on this board with a comms complaint — check the data pair separately if the stat is dark and the IFC is alive.
  • b0

    ECM blower not running

    lockout

    IFC commanded the serial ECM and does not detect it running. Furnace will not operate.

    • 14-pin harness seated at motor and IFC. No tap plugs on this motor.
    • 120 VAC to the motor, wheel free, no wet winding.
    • Do not install an AR9T96 9-speed motor as a ‘cheaper ECM’ — it will not talk this serial bus.
  • b1

    ECM communications lost

    lockout

    IFC cannot communicate with the variable-speed blower. Furnace will not operate.

    • Same 14-pin harness — pins bent, corrosion, half-seated.
    • Motor vs IFC: if a known-good motor still b1s, the IFC serial driver is the fault.
    • Power-cycle once to see if it is a hard loss or a glitch after a static event.
  • b2

    Motor HP mismatch vs shared-data set

    lockout

    Connected motor horsepower does not match the value in the furnace shared-data set. Furnace will not operate.

    • Wrong replacement motor for this cabinet size.
    • Wrong memory card after an IFC swap (see d0/d4).
    • Do not ‘make it work’ with a different HP ECM — ComfortBridge CFM tables are card-specific.
  • b3

    Motor limiting (power / speed / temp)

    warn

    ECM is folding back on power, speed, or temperature. Furnace keeps running at reduced CFM.

    • Filter, coil, and total external static vs the AMVC96 blower chart.
    • Return undersized or a 5" media cabinet the installer added.
    • High ambient around the motor (closet, no ventilation).
  • b4 / b5 / b7

    Motor trip / locked rotor / failed start

    lockout

    b4 = lost rotor or overload trip (shuts down and retries). b5 = locked rotor after 10 start attempts. b7 = motor parameters missing or failed to start after 40 attempts.

    • Wheel rub, debris in the housing, seized bearings.
    • Static so high the motor cannot start the wheel.
    • Harness intermittents look like b7. Prove the 14-pin before a motor or IFC.
    • Adjacent b-codes on some door cards are the same family — same harness/static/motor path.
  • b9

    Low indoor airflow

    warn

    Indoor airflow fell below the calculated minimum. Furnace stages down (high to low) and will halt if CFM reaches 0.

    • Filter, coil, closed registers, undersized return.
    • IFC heat/cool CFM setting vs the coil and the outdoor.
    • TES. A communicating motor will ramp into a brick and then b9 / E3.
  • d0 / d4

    Shared data / memory card

    lockout

    d0 = IFC has no shared-data set (replacement board, missing card) and cannot drive the serial ECM or calculate CFM. d4 = card rejected (wrong model card).

    • After an IFC swap the AMVC96 memory card must be installed and seated.
    • A GMVC96 card usually twins; an AMVM97, AVPTC, or AR9T96 card is d4.
    • Do not run the furnace on empty shared data and guess CFM.

Workflows

No heat on ComfortBridge

Communicating stat shows a heat call, furnace idle or locked, or the display is dark.

  1. Photograph the triple display and the stat error before you pull a wire or kill power.
  2. Is the IFC in communicating mode or 24V fallback? That changes every next step. Leftover data wires on a converted job shorted to R/C will take the bus down.
  3. If communicating: data-pair polarity and splices (never 24 VAC between the data pins), one master, and whether the outdoor is crashing the bus.
  4. If 24V fallback: W1 at the IFC (R to W ~24 VAC), then inducer / dual PS / HSI as a two-stage 96%.
  5. Door switch in? 115 VAC at L1 (EE if not). 24 VAC across the fuse (E5 if open).
  6. Inducer on low? Silent → inducer / IFC output. Running and E2 → trap, hose, LPS, vent. E1 with inducer off → unplug LPS.
  7. HSI glow? No glow + E7 → igniter / ground. Glow but no flame → gas cock, valve 24 VAC, manifold. Flame then drop → E6 / E0.
  8. Motor silent with a heat call and b0/b1 → 14-pin harness and static before a board. Do not install an AR9T96 9-speed motor.

b0 / b1 / b-family motor

Display is b0, b1, b2, b3, b4, b5, b7, or b9. Blower silent or folding back.

  1. 14-pin serial harness at the motor and at the IFC. Fully seated, no bent pins, no tap adapters.
  2. This is not an AR9T96 9-speed. A tap-plug ECM will not run and will throw b0/b1/b2. Do not install one as a ‘cheaper ECM.’
  3. Total external static vs the AMVC96 chart for this cabinet. b3/b9 are airflow, not a bad motor.
  4. b2 or d0/d4 after a parts-runner motor or IFC — HP and shared-data card must match this SKU.
  5. Wheel free? Rub, wet winding, or locked rotor is b4/b5. Forty failed starts is b7 — find why it will not spin before you shotgun the IFC.
  6. Replace motor and IFC only after comms, static, and the memory card are proven.

d0 after a board swap

Replacement IFC, display d0 or d4, motor will not run.

  1. A replacement ComfortBridge IFC ships without this furnace’s shared-data set. d0 is expected until the card is in.
  2. Install the correct AMVC96 memory card (Goodman GMVC96 twin card is the usual cross). Seat it fully.
  3. d4 = wrong card. An AMVM97, AVPTC, AR9T96, or generic ‘96%’ card will be rejected.
  4. After the card takes, verify CoolCloud / IFC menu outdoor type and CFM before you leave. Empty tables give you a running furnace that limits or b9s all winter.

E2 / E9 draft (dual PS still exist)

No heat, or runs on low only. Display E2 or E9.

  1. ComfortBridge did not delete the dual pressure switches. E2 is low-fire prove, E9 is high-fire prove — two hoses, two taps, never teed.
  2. Trap and collector first. A drowned 96% looks like E2 overnight and E9 on the first cold morning that actually calls high.
  3. Inducer actually on (E2) or actually on high (E9)? 120 VAC and a speed change. A dead high-speed winding is E9 with a perfect HPS.
  4. Hoses: LPS on the low tap, HPS on the high tap. Water in a hose fakes E1/E8. Cracked hose fakes E2/E9.
  5. Vent/intake: bird screen, ice, long 2" on a 100–120 kBtu high fire, wind on a sidewall pair.
  6. Then ohm the switch with that inducer speed running. If it closes and the IFC still E2/E9s, the IFC input is the fault.

Test points

Data pair
OEM communicating voltage / polarity — never 24 VAC between the data pins.
Motor harness
14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.
Flame rod
µA per this IFC sticker, not the AR9T96 card. Rising while running is the goal.
LPS / HPS
Both NO. Two hoses, two taps, never teed. Closed only when that inducer speed is making the collector setpoint.
Manifold low / high
Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
HSI
Nitride, 120 VAC during warm-up. Cold ohms per sticker.
Memory card
Seated AMVC96 (or GMVC96 twin) card after any IFC swap. d0 empty, d4 wrong card.
24V fuse / door
Fuse intact (E5). Door switch made, 115 VAC at L1 (EE if not).

Gotchas

  • Techs treat AMVC96 like AR9T96 and start counting a single 7-seg or looking for heat taps. There are none. Triple display + 14-pin serial motor.
  • EE on this board is line voltage / door / internal — not a ComfortBridge comm code. A dark stat with a live IFC is a data-pair problem, not EE.
  • E2 vs E9: fixing the trap clears low fire and the callback is ‘still no high fire’ because the HPS hose was never on the high tap. Dual PS still exist.
  • AMVM97 looks identical in the basement and is modulating. W1/W2 staging tests and E8/E9-as-a-tee will lie. Confirm the valve and the data plate.
  • GMVC96 is the Goodman-badge twin. Same IFC, same card family, same chart. GM9S96 / GR9T96 are not.
  • Door cards differ by board generation. A 2014 AMVC96 card is wrong on a later triple-display replacement IFC — read the sticker in THIS blower.
  • 24V fallback does not turn this into a tap furnace. CFM still comes from the IFC tables. Wrong CoolCloud outdoor type / CFM is an E3/b9 generator.

Related plates

  • amana-arvt96 — Newer ComfortBridge two-stage VS R-32 plate. Same E/b/d language — ARVT96 memory card, 0.5" heat-ESP hard limit. Do not drop this AMVC96 card into that cabinet.
  • amana-amvm97 — Modulating cousin — 0–100% valve and variable inducer. Do not apply AMVC96 two-stage staging tests.
  • goodman-gmvc96 — Goodman-badge twin. Same ComfortBridge IFC and the same E/b/d chart.
  • amana-ar9t96 — 9-speed tap, conventional 24V, single 7-seg. Do not use that chart on this communicating VS IFC.
  • amana-avptc — Matching ComfortBridge communicating air handler — electric heat, no gas, no inducer.