Modulating ComfortBridge 97% furnace. Badge twin of Amana AMVM97. Same E / b / d display language as GMVC96, but the gas valve is modulating (percent capacity), not two discrete stages. Do not apply Ht1/Ht2 staging tests.
Not GMVC96 (two-stage ComfortBridge — Ht1/Ht2, two solenoids). Not GR9T96 (9-speed 24V). Not GMEC96 (CT two-stage). The cabinet and triple 7-seg look like a GMVC96 until you see the modulating valve and the percent request.
ComfortBridge communicating preferred · 24V fallback is a coarse heat call, not true modulation
Sister SKU
GCVM97 · Amana AMVM97 same IFC family
This board
ComfortBridge IFC · modulating · three 7-segment digits
Status words (idle, Ht, CF, CL1) are not faults. Ht here is a heat-run status, not GMVC96 Ht1/Ht2 staging.
Same E / b / d alphabet as GMVC96. Meanings below are rewritten for a modulating prove — do not import two-stage solenoid steps.
Shared-data card holds this cabinet’s modulating tables. A GMVC96 two-stage card will not satisfy this IFC (d4).
Learn / menu buttons step CFM, heat setup, and last faults. A setup screen is not a lockout.
Sequence
Call. Communicating thermostat requests a firing rate (percent), not W1 then W2. On 24V fallback the IFC runs a coarse heat routine — you lose true modulation.
Low-rate prove. Inducer comes up to the minimum rate. The low-rate pressure path must close before any fire (E1 if already closed at idle, E2 if it never closes). This is not ‘stage 1 of 2.’
HSI / modulate. Nitride warm-up, then the modulating valve opens to light-off rate and ramps toward the request. Failures stack to E0. Weak µA at low percent is E6 — common on this valve.
High-rate prove. As capacity climbs, the high-rate pressure path must close (E9 if it never does, E8 if it was already closed at a low rate). The inducer is tracking the valve, not jumping a discrete high tap.
Blower. Serial ECM CFM tracks the firing rate from the IFC tables. No heat taps. A GR9T96 9-speed or GMEC CT motor will not run here.
Satisfied. Valve toward closed, post-purge. Unexpected flame with the modulator shut → E4.
Faults on this IFC
idle / Ht / CF / CL1
Status, not a fault
info
Normal run states. idle = standby. Ht = heat running (a rate, not Ht1 vs Ht2). CF = continuous fan. CL1 = low cool.
Do not replace the board because it says idle or Ht.
A communicating request sitting at idle is bus / fallback, not a bad modulator.
There is no Ht2 to wait for. If capacity will not climb, look at high-rate prove (E8/E9) and the valve, not a W2 wire.
E0
Retry lockout
lockout
Light-off or flame-loss retries exceeded at the commanded rate. Three-try-class lockout on this IFC family.
Watch light-off at the minimum rate, not a two-stage ‘high fire trial.’
Manifold at light-off vs the modulating plate. A valve that never leaves closed looks like E0 forever.
Rod, ground, HSI. Do not keep resetting.
E1
Low-rate PS stuck closed
lockout
Low-rate pressure switch is made with the inducer at idle. Same letter as GMVC96 E1 — prove is at minimum rate, not ‘low fire stage 1.’
Unplug the low-rate switch. Code change = welded switch or water in the hose.
Inducer must be off / idle for this code to be honest. A modulator that never shuts the inducer down is a different problem.
E2
Low-rate PS open
lockout
Inducer at minimum rate, low-rate switch will not close. No light-off until this proves.
Inducer spinning at the light-off rate? 120 VAC / commanded speed.
Trap, collector, PVC. A drowned 97% secondary will not prove at any percent.
Hose on the low-rate tap. Communicating CFM does not create draft.
E3
Limit / rollout
warn
Limit or rollout string opened while modulating. VS blower should have been tracking rate — if the limit still opens, static, overfire at high percent, or rollout.
IFC heat CFM vs TES. Filter, coil, return.
Which switch is open? Limit = airflow / high-percent overfire. Rollout = exchanger / burners — hazard, manual reset.
Clock input at the rate it tripped. A stuck-high modulator overfires like a two-stage valve welded on high.
E4
Unexpected flame
hazard
Rod sees flame with the modulating valve commanded shut.
Shut the gas cock. If flame stays, leaking modulator — replace, do not drive it as a test.
Rod shorted to ground or IFC flame circuit.
E5
Open fuse
warn
IFC automotive fuse is open.
24 V short on leftover W/Y/G, humidifier, EAC, or data pair landed on 24V.
Unplug harnesses and replace fuse. Repeat blow = board or valve harness.
E6
Low flame signal
warn
Flame present but µA is below threshold. Common at low modulating percent — the rod sees a small flame.
Clean rod, burner-box ground. µA should rise as rate climbs; flat µA at every percent is rod/ground, not the valve.
Light-off rate too lean (valve / orifice / LP). Do not crank a two-stage manifold chart onto this modulator.
Confirm flame at minimum percent before you condemn the IFC.
E7
Igniter / ground
lockout
Igniter circuit or flame-sense ground failed the command.
Igniter ohms and 120 VAC during warm-up. Cracked nitride.
Ground screw at the burner box. E7 is HSI/ground — b0 is the blower.
E8
High-rate PS stuck closed
lockout
High-rate pressure switch is made while the inducer is still at a low rate. Not ‘high-fire solenoid stuck.’
Second switch. Water in the hose or a welded high-rate PS.
Inducer actually at low rate? If the inducer is already high with a low request, the IFC/valve ramp is the fault, not E8 physics.
E9
High-rate PS open
lockout
Capacity is climbing, inducer is up, high-rate switch never closes. Comfort complaint: ‘it never goes above 40%.’
Does the inducer actually accelerate with the percent request? No → IFC / inducer. Yes + E9 → high-rate hose / switch / vent.
High-rate hose on its own tap. A tee with the low-rate switch is a first-install miss.
Vent that proved at light-off can still fail at 80–100% on a 100–120 kBtu cabinet.
EA
Line polarity / ground
lockout
L1/N reversed or chassis ground missing. Modulation and flame sense both suffer.
Hot and neutral at the IFC.
Burner box to IFC ground screw.
b0
ECM not running
lockout
IFC commanded the serial blower and it did not run. Same motor family as GMVC96 — still not a tap motor.
14-pin seated at motor and IFC.
Line voltage, wheel free. A 9-speed or CT motor in this cabinet will sit on b0 forever.
b1
ECM comms lost
lockout
Serial link to the indoor blower dropped. Motor serial — not the ComfortBridge thermostat pair.
14-pin continuity and rub-through at the blower deck.
Reseat motor module and IFC before replacing both.
b2
HP mismatch vs shared data
lockout
Motor horsepower does not match the modulating cabinet’s memory card.
Motor HP stamp vs this GMVM97 size and the card on the IFC.
A GMVC96 two-stage motor/card mix throws b2/d4 even when the wheel would spin.
d0
No shared data / missing memory card
lockout
IFC cannot read the furnace identity card. Classic after an IFC swap when the card stayed on the old board.
Move the card from the failed IFC onto the replacement. That card is the modulating cabinet.
A blank board with no card will not run. Do not borrow a GMVC96 two-stage card to ‘get heat.’
d4
Invalid memory card
lockout
Card present but wrong family or unreadable. A two-stage GMVC96 card is invalid on a GMVM97.
OEM card for this exact GMVM97 / GCVM97 size.
Reseat. d4 after a ‘universal ComfortBridge’ card is the card, not the valve.
Workflows
Confirm it is modulating, not GMVC96
First minute. Triple 7-seg in a Goodman 97% cabinet.
Data plate: GMVM97 / GCVM97. Valve is a modulator (percent), not two solenoids.
Communicating request is a rate. There is no W2 high-fire click to wait for.
If the plate says GMVC96, use that chart — two-stage ComfortBridge, different valve, different shared-data card.
24V fallback on this IFC is heat-on, not true modulation. A job ‘converted’ off a communicating stat will never stage like the selling sheet.
No heat / will not modulate up
Idle with a call, E0/E2 at light-off, or stuck at low percent with E9.
Photograph the triple display and the stat rate request.
Communicating or 24V fallback? Fallback will not climb through a percent curve.
E2 at light-off: trap, low-rate PS, inducer at minimum rate. Same 96/97% collector drowning as any condensing Goodman.
Lights and sits at low percent + E9: high-rate PS path and inducer acceleration, not a W2 wire.
E6 at low percent: rod/ground first, then light-off rate. Do not apply a two-stage manifold spec.
d0/d4 after a board swap: the modulating card must travel with the cabinet.
Test points
Valve
Modulating operator. Percent fire per communicating request — not two discrete solenoids.
Data pair
ComfortBridge voltage / polarity. Never 24 VAC on the data pins.
Shared-data card
GMVM97 family card. A GMVC96 two-stage card is d4.
Motor harness
14-pin serial ECM. No taps. No CT profile plug.
Flame rod
µA at minimum percent and again at high percent. Must exist at both ends of the curve.
Gotchas
Amana AMVM97 is the badge twin. Same chart.
GMVC96 looks identical until you read the plate and the valve. Two-stage staging tests will lie on this furnace.
24V W on a modulating ComfortBridge IFC is a fallback heat call. Homeowners who ‘put a regular stat on it’ lose the product.
Do not import GR9T96 E8/E9 hose stories onto the wrong motor — the draft physics rhyme, the blower and valve do not.
Related plates
amana-amvm97 — Amana badge twin — same modulating ComfortBridge IFC and valve family.
goodman-gmvc96 — Two-stage ComfortBridge cousin. Same E/b/d alphabet, discrete Ht1/Ht2, different card and valve.