ARVM97
ComfortBridge · modulating · serial VS · 97%
Current Amana ComfortBridge modulating 97% (ARVM97 / ADVM97). 0–100% valve and variable inducer. Same communicating world as AMVM97 — newer cabinet / card. Do not run AMVC96 two-stage E8/E9 tee tests.
Not AMVM97 only by badge — this is the current ARVM97 plate. Not ARVT96 (two-stage ComfortBridge). Not AR9T96 (9-speed 24V).
AFUE
Up to 97% modulating
Valve
Modulating 0–100%. No W1/W2 solenoids.
Sister SKU
ADVM97 downflow · Goodman GRVM97
This board
ComfortBridge IFC · three 7-segment digits + menu buttons
- Same triple 7-seg and E/b/d language as AMVC96. Status words (idle, Ht, CF) are run states, not faults. Capacity is a percent, not Ht1 vs Ht2 staging.
- E2 / E9 are pressure-band / inducer proves as the variable inducer ramps — not ‘the low PS vs high PS tee’ from a two-stage collector. Do not start teeing hoses or looking for a W2 solenoid.
- Shared-data memory card is required after an IFC swap (d0/d4). Use the AMVM97 card, not an AMVC96 two-stage card.
- Force high fire from the IFC menu / CoolCloud gas-pressure test (GPT), not by jumping W2. There is no second-stage solenoid to energize.
- 24V fallback may accept a W call. The valve still modulates from IFC tables. A W2 wire does not create high fire.
IFC menu fault history (not the AR9T96 2-second hold). Write the exact token. Stored history survives a power cycle; the active display may not.
Universal swap
Current modulating ComfortBridge. No universal.
Silk: ARVM97 · ComfortBridge
White-Rodgers
—ICM
—Honeywell
—- Any 50A55-843 / 50A65-843 / 50M56U-843 / 50M56X-843 / S9200U1000 universal — those are conventional 24V HSI, not this data bus.
- ICM280 / 2811 / 2810 / 282B — wrong IFC family.
- AMVM97 older card. ARVT96 two-stage card.
After you pull the dead card
- 1OEM ARVM97 / ADVM97 modulating IFC. CoolCloud.
Field wiring
Written landings for Amana ARVM97. Not a factory schematic.
AMVM97 / GMVM97 / ARVM97 / DM97MC. Same 1/2 pair as two-stage ComfortBridge. Capacity is 0–100%, not W1/W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
This indoor
Current modulating Amana. Not ARVT96 two-stage.
Communicating modulating
ComfortBridge / ComfortNet indoor with a modulating valve.
Modulating IFC
No W2 high-fire prove. Percent request on the bus.
- 1DataData
- 2DataData
- R24V24V
- CCommon24V
Landing
- DataControlIFC 1/2outdoor 1/2
Data. Fire rate is serial.
IFC harness — modulating
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Variable inducer + pressure band
Inducer ramps to a pressure band. There is no discrete 32 / E9 high-fire switch.
- INDVariable inducer from the IFCLine
- BANDPressure transducer / band — not LPS vs HPS24V
HSI + modulating valve
Capacity is a percent on the bus. There is no W2 solenoid to chase.
- HSI120V igniterLine
- VALVE %Serial / percent valve24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Band, not a single PS
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- CoolCloud / Daikin One shows percent capacity, not Ht1/Ht2.
Do not
- Do not apply AR9T96 / AMVC96 two-stage staging tests.
- Do not land W on a random terminal to force it.
Same published 1/2 pair. The valve is the difference.
Sequence
- 1
Call
Communicating stat requests a percent capacity. This is not a W2 close. On 24V fallback a W call starts heat; the IFC still picks the firing rate from its tables.
- 2
Variable inducer / prove
Inducer ramps to the pressure band for that rate. E2 = will not prove the running band (trap, hose, vent, inducer). E9 = will not make the high-capacity draft band. These are not a low-tee vs high-tee two-stage test.
- 3
HSI / modulating valve
Nitride warm-up, then the modulating valve opens to the requested percent. Open igniter / no-ground → E7. Flame must prove. Failures stack toward E0.
- 4
Blower
Serial ECM CFM follows capacity from the IFC tables. Same b0/b1/d0 motor-and-card rules as AMVC96. No tap plugs.
- 5
Modulate
Valve and inducer track load. Do not expect a discrete low-to-high step. High-fire manifold is a menu/GPT test, not a W2 jump.
- 6
Satisfied
Valve closed, inducer post-purge, blower delay. Unexpected flame → E4.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
idle / Ht / CF
Status, not a fault
Normal run states. idle = standby. Ht = heat running (capacity is a percent, not Ht1/Ht2 stages). CF = continuous fan.
1 Confirm this is not a fault
On the Amana ARVM97 this readout (idle / Ht / CF) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the Amana ARVM97 IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: Do not replace the board because it says Ht or CF.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch ComfortBridge IFC · three 7-segment digits + menu buttons through one cycle and write the first real fault that replaces this status word.
Expect: Call: Communicating stat requests a percent capacity. This is not a W2 close. On 24V fallback a W call starts heat; the IFC still picks the firing rate from its tables.
E0
System / ignition lockout
Failed to sense flame after 3 retries. 1-hour auto reset.
1 Watch one full try — do not reset
Write the Amana ARVM97 code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. Watch one full try: inducer ramp, HSI, valve, flame, µA.
Expect: Call → Variable inducer / prove → HSI / modulating valve → Blower → Modulate → Satisfied
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence. Gas supply. Modulating valve actually opening (not a stuck two-stage solenoid test).
Expect: Inlet and manifold on the plate. 24 VAC only during trial.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets. Rod and ground. Do not sit on hourly resets.
Expect: Flame rod: µA per this IFC sticker at the rate it is firing, not only at high fire.
E2
Pressure-band open / inducer will not prove
Variable inducer is running and the pressure switch / band for that rate never made. Same 96% trap/hose/vent physics as other Amana condensing furnaces — not ‘unplug the low-fire tee.’
1 Prove inducer and the live code
Do not pull power — that clears the Amana ARVM97 active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer actually spinning and ramping? 120 VAC and a speed change.
Expect: Inducer: Variable speed. Must ramp with requested rate. 120 VAC present; speed change on a high-fire menu test.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Trap, collector, and condensate first.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Hose dry, on the correct port, not pinched. Cracked hose fakes an open band.
Expect: Pressure band: Switch(es) prove draft at the running band. Not a two-stage low/high tee.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E3
Open primary / aux / rollout limit
Limit opened. Airflow or overfire. Rollout is still a manual-reset hazard.
1 Treat this as flame outside the exchanger
Do not reset the Amana ARVM97 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. IFC heat CFM, not a tap. Filter, coil, static. Firing rate vs plate — a valve stuck toward 100% will limit.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Amana ARVM97 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Limit ohms after it cools. Recurring rollout → exchanger / burners / flue.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
E4
Flame sensed with no call for heat
Rod sees flame with the modulating valve commanded closed.
1 Shut the gas cock first
On Amana ARVM97 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground or IFC flame circuit.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
E5
Open 24V fuse
Low-voltage fuse open. Operation inhibited except the display.
1 Find the 24 V short before you replace the fuse
On Amana ARVM97 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. 24 V short on the stat harness, humidifier, EAC, or a leftover data pair on R/C.
Expect: Fuse out. 24 V transformer still good. Harness isolated.
2 Replace the fuse with the harness off
New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC). Unplug the harness and replace the fuse. Repeat blow = board or valve harness.
Expect: Fuse holds with harness off. Dies when the shorted lead lands.
3 If it blows with the harness off
Short is on the Amana ARVM97 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.
Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.
E6
Low flame-sense µA
Flame present, signal below threshold. Lazy flame at a low modulating rate is a common miss.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Amana ARVM97 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod, chassis ground.
Expect: Flame rod: µA per this IFC sticker at the rate it is firing, not only at high fire.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Manifold at the rate the IFC is actually firing, not just a ‘high-fire’ number.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Amana ARVM97 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. LP conversion and orifice.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E7
Igniter open / no-ground
Igniter open, unplugged, or ground check failed.
1 Ohms at the igniter, then at the IFC
On Amana ARVM97 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Nitride ohms per sticker. 120 VAC during warm-up.
Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Burner-box ground. Cracked element.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
E9
High-capacity pressure band open
Inducer will not make the high-rate draft band. This is not ‘the high-fire PS tee on a two-stage collector.’ The unit may run at a reduced percent and never reach high fire.
1 Prove the high-fire call
Write the live Amana ARVM97 code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. Force high fire from the IFC / CoolCloud GPT menu — do not jump W2.
Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.
If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.
If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’
2 Prove the inducer actually went high
Listen and amp the inducer on low vs high. No speed-up → IFC high output or inducer winding. Speed-up and this code still live → high-fire PS path (hose, switch, vent). Inducer actually at high speed? Variable inducer that will not climb is E9 with a good switch.
Expect: Inducer: Variable speed. Must ramp with requested rate. 120 VAC present; speed change on a high-fire menu test.
If fail: Measure 120 VAC on the high-speed inducer lead during the high call. 0 V = IFC. Voltage + dead motor = inducer.
3 Isolate the HIGH hose and switch
High-fire hose on the high tap only — a tee with the low switch is the common first-install miss on this dual-switch plate. Blow the hose, confirm it is dry and downhill to the collector. Ohm the high-fire switch: it is NO and must close only on high draft. Vent sized for high fire on this cabinet. Trap that only loads at high rate.
Expect: Pressure band: Switch(es) prove draft at the running band. Not a two-stage low/high tee.
If fail: Welded open, cracked hose, or water in the line. Replace the failed part — do not leave a jumper.
If pass: Switch and hose good → step 4 (vent / condensate / IFC).
4 Vent, condensate, and the IFC input
High fire needs more draft than a low-fire code ever saw. Check PVC size on this cabinet, shared chase, wind, ice, bird screen, and condensate backing into the collector only on high. If the switch closes on known draft and the code stays, the Amana ARVM97 IFC input is the last call.
Expect: Clear vent, dry collector, known-good switch, then IFC.
EA
Reversed polarity / poor ground
L1/N reversed or chassis ground missing. Furnace will not operate.
1 Hot and neutral at the IFC, not the disconnect
On Amana ARVM97 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot and neutral at the IFC.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Burner-box ground screw.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
EE
No 115V to control / internal / door switch
No line voltage, door switch open, or internal control condition. This is power, not a data-pair code.
1 Measure at the IFC under load
On Amana ARVM97 line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. Switch, breaker, door switch. 115 VAC at L1/N.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. If the IFC is alive and the stat is dark, that is the data pair — not EE.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.
Expect: 24 V holds under load. Line stays in window.
b0
ECM blower not running
IFC commanded the serial ECM and does not detect it running.
1 Reseat the serial plug
On Amana ARVM97 this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. 14-pin harness at motor and IFC. No tap plugs.
Expect: Plug fully seated both ends. Correct motor for this cabinet.
2 Power and the data pair at the motor
Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. Do not install an AR9T96 9-speed or an AMVC96 motor of the wrong HP.
Expect: Line voltage present. Data pair not shorted to chassis.
3 Motor vs IFC serial driver
Known-good motor still throws this code = Amana ARVM97 IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC. Wheel free, 120 VAC to the motor.
Expect: One clean CFM request after a known-good pair.
b1
ECM communications lost
IFC cannot talk to the variable-speed blower.
1 Reseat the serial plug
On Amana ARVM97 this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. 14-pin seated, pins straight.
Expect: Plug fully seated both ends. Correct motor for this cabinet.
2 Power and the data pair at the motor
Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. Motor vs IFC: known-good motor still b1 = IFC serial driver.
Expect: Line voltage present. Data pair not shorted to chassis.
3 Motor vs IFC serial driver
Known-good motor still throws this code = Amana ARVM97 IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC.
Expect: One clean CFM request after a known-good pair.
b2 / b3 / b9
Motor HP / limiting / low CFM
b2 = motor HP does not match the shared-data set. b3 = motor folding back on power/speed/temp. b9 = airflow below calculated minimum.
1 Read the plug / card on THIS cabinet
On Amana ARVM97 the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Correct AMVM97 motor and memory card.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Static, filter, coil. CFM follows modulating rate — a brick duct still b9s.
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint. Wrong CoolCloud outdoor type / CFM table.
Expect: One clean sequence on the correct identity.
d0 / d4
Shared data / memory card
d0 = no shared-data set on a replacement IFC. d4 = wrong-model card.
1 Read the plug / card on THIS cabinet
On Amana ARVM97 the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Install the AMVM97 card, not an AMVC96 two-stage card.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. GMVM97 twin card is the usual cross. AVPTC / AR9T96 cards are d4.
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint. Empty tables will not drive the serial ECM or calculate CFM.
Expect: One clean sequence on the correct identity.
Workflows
Modulating vs two-stage ComfortBridge
Amana 97 / 96 mix-up.
1 Prove the call and the live code
Plate ARVM97 / AMVM97 = percent fire, variable inducer. Plate ARVT96 / AMVC96 = Ht1/Ht2, two solenoids.
Expect: Write whatever ComfortBridge IFC · three 7-segment digits + menu buttons is showing. IFC menu fault history (not the AR9T96 2-second hold). Write the exact token. Stored history survives a power cycle; the active display may not.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
No high-fire PS tee on a modulator. Pressure is a band.
Expect: Variable inducer / prove: Inducer ramps to the pressure band for that rate. E2 = will not prove the running band (trap, hose, vent, inducer). E9 = will not make the high-capacity draft band. These are not a low-tee vs high-tee two-stage test.
3 Confirm with a number, then the next part
Memory card must be the modulating set. A two-stage card is d4.
Expect: Data pair: OEM communicating voltage / polarity — never 24 VAC between the data pins. · Modulating valve: Single modulating body. High-fire manifold from IFC/CoolCloud GPT, not a W2 jump. Plate wins.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Data pair
OEM communicating voltage / polarity — never 24 VAC between the data pins.
Modulating valve
Single modulating body. High-fire manifold from IFC/CoolCloud GPT, not a W2 jump. Plate wins.
Inducer
Variable speed. Must ramp with requested rate. 120 VAC present; speed change on a high-fire menu test.
Pressure band
Switch(es) prove draft at the running band. Not a two-stage low/high tee.
Flame rod
µA per this IFC sticker at the rate it is firing, not only at high fire.
Motor harness
14-pin serial ECM. No tap plugs. Correct AMVM97 HP / card.
Memory card
AMVM97 (or GMVM97 twin) after an IFC swap. AMVC96 card is d4.
Gotchas
- AMVM97 is the older modulating plate. Same physics, different shared-data set than ARVM97.
Related plates
Install this plate
Install Amana ARVM97 as ComfortBridge · modulating · serial VS · 97%.
ComfortBridge · modulating · serial VS · 97%
This plate — not the sister SKU
- Not AMVM97 only by badge — this is the current ARVM97 plate. Not ARVT96 (two-stage ComfortBridge). Not AR9T96 (9-speed 24V).
- AMVM97 is the older modulating plate. Same physics, different shared-data set than ARVM97.
IFC on this door
- Same triple 7-seg and E/b/d language as AMVC96. Status words (idle, Ht, CF) are run states, not faults. Capacity is a percent, not Ht1 vs Ht2 staging.
- E2 / E9 are pressure-band / inducer proves as the variable inducer ramps — not ‘the low PS vs high PS tee’ from a two-stage collector. Do not start teeing hoses or looking for a W2 solenoid.
- Shared-data memory card is required after an IFC swap (d0/d4). Use the AMVM97 card, not an AMVC96 two-stage card.
- Force high fire from the IFC menu / CoolCloud gas-pressure test (GPT), not by jumping W2. There is no second-stage solenoid to energize.
- 24V fallback may accept a W call. The valve still modulates from IFC tables. A W2 wire does not create high fire.
Hardware
- AFUE: Up to 97% modulating
- Valve: Modulating 0–100%. No W1/W2 solenoids.
- Sister SKU: ADVM97 downflow · Goodman GRVM97
First fire
- 1Plate ARVM97 / AMVM97 = percent fire, variable inducer. Plate ARVT96 / AMVC96 = Ht1/Ht2, two solenoids.
- 2No high-fire PS tee on a modulator. Pressure is a band.
- 3Memory card must be the modulating set. A two-stage card is d4.
Do not on Amana ARVM97
- Not AMVM97 only by badge — this is the current ARVM97 plate. Not ARVT96 (two-stage ComfortBridge). Not AR9T96 (9-speed 24V).
- AMVM97 is the older modulating plate. Same physics, different shared-data set than ARVM97.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Amana literature libraryLiterature searchGas furnace / air-handler PDFs. Match the plate, not just the Amana badge.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Standard limited warranty
warranty sheetAmana furnace heat-exchanger / unit-replacement terms
Registered residential furnace warranty terms · Limited warranty certificate
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal