Amana

ARVT96

Furnace · ComfortBridge · two-stage · communicating VS · up to 97.50% AFUE

Current Amana ComfortBridge two-stage 96–97.5% with a serial variable-speed ECM, CoolCloud Bluetooth, and a two-speed inducer / dual PS. SS-ARVT96_ADVT96-R32 (Feb 2025): do not operate above 0.5" w.c. ESP in heating — 0.5–0.8" tables are cooling only. Compatible with any single-stage thermostat. This is not AR9T96 (9-speed taps) and not the older AMVC96 plate (memory card is ARVT96).

Not AR9T96 / GR9T96 (9-speed tap ECM, conventional 24V, single 7-seg E0–E9, 2-second recall hold). Not AR9S96 (single-stage, one PS, no ComfortBridge). Not AMVC96 (older ComfortBridge two-stage — same E/b/d language, different memory card and this SS’s 0.5" heat-ESP hard limit). Not AMVM97 (modulating valve + variable inducer).

Walk this in Diagnose

This plate

Input / AFUE
40–120 kBtu · up to 97.50% AFUE (SS-ARVT96_ADVT96-R32 Feb 2025) · 40 ng/J Low NOx, not SCAQMD after Oct 1 2019
SKUs (upflow)
ARVT960403BN / 0603BN / 0803BN / 0804CN / 1005CN / 1005DN / 1205DN
SKUs (downflow)
ADVT960403BN / 0603BN / 0804CN / 1005CN / 1205DN
Staging
Two-stage gas valve · two-speed inducer · dual pressure switches
Blower
Communicating variable-speed ECM (serial CFM, no tap plugs). Ships high-speed cooling — installer must adjust. ~400 CFM/ton.
Heat ESP
HARD LIMIT 0.5" w.c. in heating (SS p.7). CFM between 0.5" and 0.8" is tabulated for cooling only.
Rec. heat CFM
0403BN 1025 · 0603BN 1200 · 0803BN 1400 · 0804CN 1760 · 1005CN 1770 · 1005DN 2000 · 1205DN 2150 (mid-rise)
Ignition
120 VAC silicon nitride HSI
Vent
Cat IV PVC 2–3" · 2-pipe or 1-pipe · 24" front service
Control
ComfortBridge IFC · UP/MENU/DOWN · CoolCloud Bluetooth · compatible with any single-stage thermostat
Accessories
LPM-34 all SKUs · HASFK-1/2/3 (1005DN TBD) · 72950/72951 · RF000142 · EFR02 · 0170K00000S/00001S · 0270F20723 (upflow) / 0270F20670 (downflow) · CFSB17/21/24 downflow
Sister SKU
ADVT96 downflow. Not AMVC96 (older card). Not AR9T96 taps.

This board

ComfortBridge IFC · three 7-segment digits + UP/MENU/DOWN · CoolCloud

  • Three digits and menu buttons (UP / MENU / DOWN) — not the AR9T96 single 7-seg and not 9-speed taps. Status words (idle, Ht1, Ht2, CF, CL1, CL2) are run states, not faults.
  • SS wiring p.9 is the ComfortBridge menu IFC — no E-code table printed on that sheet. Door card on THIS cabinet wins. ComfortBridge two-stage language on this family is E0–E9 (dual PS), b0–b9 (serial ECM), d0/d4 (memory card).
  • Shared-data memory card is ARVT96. d0 = no card / empty set. d4 = wrong-model card (AMVC96, AMVM97, AR9T96, AVPTC). The replacement board will not drive the serial ECM without the correct ARVT96 card.
  • Compatible with any single-stage thermostat (SS). 24V W/W1 fallback is legal. CFM still comes from IFC tables, not tap plugs. A leftover data pair shorted to R/C will look like a dead bus.
  • CoolCloud Bluetooth is the menu for CFM, outdoor type, and commissioning. Do not look for F01–F09 heat taps — there are none.

Sequence

  1. Call. Communicating stat requests heat capacity, or a single-stage 24V stat closes W. CFM still comes from the IFC tables, not taps.
  2. Prove limits. IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.
  3. Low inducer / LPS. Two-speed inducer starts low. Low-stage PS must close. Already closed with inducer off → E1. Never closes → E2.
  4. HSI / low-fire valve. Silicon nitride warm-up, then first-stage solenoid. Open igniter / no-ground → E7. Flame must prove. Failures stack toward E0.
  5. Blower. Serial ECM ramps to the IFC heat CFM table. SS rec. high-heat CFM is cabinet-specific (1025 on 0403BN through 2150 on 1205DN). Silent motor → b0/b1. Do not hang an AR9T96 9-speed motor on this harness.
  6. High fire. Communicating capacity or W2 / staging timer. Inducer goes high. High-stage PS must close (E9 if open, E8 if already closed). Second-stage solenoid opens.
  7. Satisfied. Valve off, inducer post-purge, blower heat-off delay. Unexpected flame after valve-off → E4.

Faults on this IFC

  • idle / Ht1 / Ht2 / CF / CL1 / CL2

    Status, not a fault

    info

    Normal run states on the triple display. idle = standby. Ht1 / Ht2 = low / high heat. CF = continuous fan. CL1 / CL2 = cooling stage.

    • Do not replace the board because it says Ht1 or CF.
    • Ht1 forever with a high-fire request → staging / E8–E9 path, not a ‘bad Ht1 code.’
  • E0

    System / ignition lockout

    lockout

    Control failed to sense flame after retries and shut off gas.

    • Watch one full try: inducer, HSI glow, valve click, flame, µA.
    • Gas supply and manifold (low then high).
    • Ground and flame-rod cleanliness.
    • Do not sit on hourly resets — find which step dies.
  • E1

    Low-stage PS stuck closed

    lockout

    Low-stage pressure switch is made with the inducer off.

    • Unplug the LPS. If the code changes, the switch is welded or the hose is holding residual draft.
    • Hose routed downhill? Water fakes a closed switch.
    • IFC input shorted — only after the switch ohms open.
  • E2

    Low-stage PS stuck open

    lockout

    Inducer is on low and the low-stage switch will not close.

    • Inducer spinning? 120 VAC at the inducer on a heat call.
    • Collector box, inducer outlet, and condensate trap — this 96% will not make pressure with a full trap.
    • PVC intake/exhaust (bird screen, ice, long run, wind).
    • LPS hose cracked or on the wrong port (low vs high tap).
  • E3

    Open primary / aux / rollout limit

    warn

    A limit opened. Airflow or overfire. On this plate, heat ESP above 0.5" is a documented hard limit.

    • IFC heat CFM vs the SS rec. CFM for this SKU — not a 9-speed tap.
    • Total external static in HEAT. SS p.7: do not operate above 0.5" w.c. ESP in heating. 0.5–0.8" tables are cooling only.
    • Filter, wheel, coil, return size. Bottom-return flanges unfolded (SS: ~18% loss if left folded).
    • Manifold low and high vs rating plate. Recurring rollout → exchanger / burners / flue.
  • E4

    Flame sensed with no call for heat

    hazard

    Rod sees flame with both solenoids de-energized.

    • Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
    • Rod shorted to ground or IFC flame circuit.
  • E5

    Open 24V fuse

    warn

    Low-voltage fuse on the IFC is open.

    • 24 V short on W, Y, G, humidifier, EAC, or a leftover data pair landed on R/C.
    • Unplug the tstat / data harness and replace the fuse.
  • E6

    Low flame-sense µA

    warn

    Flame is present but the micro-amp signal is below the IFC threshold.

    • Clean rod with a non-scratch pad — not sandpaper.
    • Chassis ground to burner box and IFC.
    • Manifold / orifice / LP conversion (this plate is LPM-34 on every SKU).
  • E7

    Igniter open / no-ground

    lockout

    Igniter is open, not connected, or the IFC failed its ground check.

    • Nitride ohms per sticker. 120 VAC during warm-up.
    • Burner-box ground screw and painted-cabinet star washer.
  • E8

    High-stage PS stuck closed

    lockout

    High-stage pressure switch is made with the inducer not on high. Furnace runs low only.

    • This is the second switch — do not confuse with E1.
    • Welded HPS or water-filled hose.
    • IFC calling high when it should be low — W2 shorted to W1 on 24V fallback.
  • E9

    High-stage PS stuck open

    lockout

    Inducer on high, high-stage switch never closes. Classic ‘runs on low, will not go high.’

    • Inducer actually changes speed on a high-fire request? Listen / amp it.
    • HPS hose on the high-fire tap, not teed to the low switch.
    • Vent capacity / wind / shared chase. High fire needs more draft than E2 ever saw.
    • Condensate backing into the collector only under high fire.
  • EA

    Reversed polarity / poor ground

    lockout

    L1/N reversed or chassis ground missing. Furnace will not operate.

    • Hot and neutral at the IFC, not just the disconnect.
    • Burner box to IFC ground screw.
  • EE

    No 115V to control / internal / door switch

    lockout

    No line voltage reaching the IFC, door switch open, or an internal control condition. This is power, not a ComfortBridge data-pair code.

    • Furnace switch, breaker, and blower-door switch fully made.
    • 115 VAC at L1/N on the IFC.
    • If the IFC is alive and the stat is dark, that is the data pair — not EE.
  • b0

    ECM blower not running

    lockout

    IFC commanded the serial ECM and does not detect it running.

    • 14-pin harness seated at motor and IFC. No tap plugs on this motor.
    • 120 VAC to the motor, wheel free, no wet winding.
    • Do not install an AR9T96 9-speed motor as a ‘cheaper ECM’ — it will not talk this serial bus.
  • b1

    ECM communications lost

    lockout

    IFC cannot communicate with the variable-speed blower.

    • Same 14-pin harness — pins bent, corrosion, half-seated.
    • Motor vs IFC: if a known-good motor still b1s, the IFC serial driver is the fault.
  • b2

    Motor HP mismatch vs shared-data set

    lockout

    Connected motor horsepower does not match the value in the furnace shared-data set.

    • Wrong replacement motor for this cabinet size.
    • Wrong memory card after an IFC swap (see d0/d4). An AMVC96 card is the usual miss on this new plate.
  • b3 / b9

    Motor limiting / low indoor airflow

    warn

    b3 = folding back on power/speed/temp. b9 = airflow below calculated minimum.

    • Filter, coil, TES. Heat ESP must stay ≤ 0.5" on this SS — a brick duct is b9 / E3, not a bad motor.
    • IFC heat CFM vs the SS rec. CFM for this SKU (1025–2150).
    • Return undersized or a 5" media cabinet the installer added.
  • b4 / b5 / b7

    Motor trip / locked rotor / failed start

    lockout

    b4 = lost rotor or overload. b5 = locked rotor after start attempts. b7 = failed to start / missing parameters.

    • Wheel rub, debris, seized bearings.
    • Static so high the motor cannot start the wheel — prove TES before a motor.
    • Harness intermittents look like b7. Prove the 14-pin before a motor or IFC.
  • d0 / d4

    Shared data / memory card

    lockout

    d0 = IFC has no shared-data set (replacement board, missing card). d4 = card rejected (wrong model card).

    • After an IFC swap the ARVT96 memory card must be installed and seated.
    • An AMVC96, AMVM97, AVPTC, or AR9T96 card is d4 on this plate. The card is labeled for THIS model, not ‘any ComfortBridge 96%.’
    • Do not run the furnace on empty shared data and guess CFM.

Workflows

Identify ARVT96 vs AMVC96 vs AR9T96

First minute. Badge says Amana 96% and the last tech mixed boards.

  1. Plate ARVT96 / ADVT96 = stay here. ComfortBridge + CoolCloud + two-stage VS. Memory card says ARVT96.
  2. Plate AMVC96 = older ComfortBridge two-stage. Same E/b/d language, different card and no 0.5" heat-ESP callout on that older SS. Use that chart if the plate is AMVC96.
  3. Plate AR9T96 = 9-speed taps, single 7-seg, 2-second recall hold, no menu buttons. Wrong page.
  4. Plate AR9S96 = one PS, E0–E7, heat F02. Wrong page.
  5. Do not drop an AMVC96 memory card into this IFC and expect it to commission. d4.

No heat on ComfortBridge or 24V

Stat calling heat, furnace idle or locked, or the display is dark.

  1. Photograph the triple display and the stat before you pull a wire. Status vs E-code vs b-code vs d0 vs EE.
  2. Communicating or single-stage 24V? SS says any single-stage thermostat is legal. Leftover data wires on R/C still take the bus down.
  3. If communicating: data-pair polarity and splices (never 24 VAC between the data pins).
  4. Door switch / 115 VAC (EE). 24V fuse (E5). W or communicating heat present?
  5. Inducer on low? Silent → inducer / IFC. Running and E2 → trap, hose, LPS, vent. E1 with inducer off → unplug LPS.
  6. HSI glow? No + E7 → igniter/ground. Glow, no flame → gas cock, valve 24 VAC, manifold.
  7. Motor silent + b0/b1 → 14-pin and the ARVT96 card (d0) before a board. Do not hang a 9-speed tap motor here.

E3 / b9 — heat ESP over 0.5"

Limits, low CFM, or a noisy heat call on a new ARVT96.

  1. SS p.7 hard limit: do not operate above 0.5" w.c. ESP in heating. The 0.5–0.8" numbers on the sheet are cooling only.
  2. Measure TES on a high-heat call. Above 0.5" → return/filter/coil/duct, not a ‘bad VS motor.’
  3. Confirm IFC heat CFM against the SS rec. for this SKU (1025 on 0403BN up to 2150 on 1205DN).
  4. Bottom return: unfold the flanges. SS notes ~18% airflow loss if you leave them folded.
  5. Airflows over ~1600 CFM need two-side return or side+bottom, min 20×25 filter (0804C and larger).
  6. Then look at E3 / b3 / b9. A communicating motor will ramp into a brick and then fold back.

E2 / E9 draft (dual PS still exist)

No heat, or runs on low only. Display E2 or E9.

  1. ComfortBridge did not delete the dual pressure switches. E2 is low-fire prove, E9 is high-fire prove — two hoses, two taps, never teed.
  2. Trap and collector first. A drowned 96% looks like E2 overnight and E9 on the first cold morning that actually calls high.
  3. Inducer actually on (E2) or actually on high (E9)? 120 VAC and a speed change.
  4. Hoses: LPS on the low tap, HPS on the high tap. Water fakes E1/E8. Cracked hose fakes E2/E9.
  5. Vent/intake: bird screen, ice, long 2" on a 100–120 kBtu high fire, wind on a sidewall pair.
  6. Then ohm the switch with that inducer speed running. Closed and still E2/E9 = IFC input.

d0 after a board swap

Replacement IFC, display d0 or d4, motor will not run.

  1. A replacement ComfortBridge IFC ships without this furnace’s shared-data set. d0 is expected until the ARVT96 card is in.
  2. Install the ARVT96 memory card. Seat it fully. An AMVC96 ‘96% ComfortBridge’ card is d4 on this plate.
  3. d4 = wrong card. AMVM97, AVPTC, AR9T96, or a generic 96% card will be rejected.
  4. After the card takes, verify CoolCloud outdoor type and heat CFM against the SS rec. for this SKU before you leave.

Test points

Data pair
OEM communicating voltage / polarity — never 24 VAC between the data pins. Single-stage 24V fallback is legal; CFM still from IFC tables.
Motor harness
14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.
Heat ESP
≤ 0.5" w.c. in heating (SS p.7 hard limit). 0.5–0.8" is cooling only.
Heat CFM
SS rec. high-heat: 0403BN 1025 · 0603BN 1200 · 0803BN 1400 · 0804CN 1760 · 1005CN 1770 · 1005DN 2000 · 1205DN 2150.
LPS / HPS
Both NO. Two hoses, two taps, never teed. Closed only when that inducer speed is making the collector setpoint.
Manifold low / high
Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
HSI
Nitride, 120 VAC during warm-up. Cold ohms per sticker.
Memory card
Seated ARVT96 card after any IFC swap. AMVC96 card is d4.

Gotchas

  • Techs treat ARVT96 like AR9T96 and start looking for heat taps. There are none. Triple display + 14-pin serial motor + CoolCloud.
  • Techs treat ARVT96 like AMVC96 and drop in the older memory card. d4, silent blower. The card is labeled ARVT96.
  • 0.5" heat ESP is a hard limit on this SS, not a suggestion. A duct that ‘ran fine’ on a 9-speed AR9T96 can E3/b9 here.
  • Furnaces ship on high-speed cooling. Installer must set CoolCloud / menu CFM. Leaving it on high heat CFM in a tight return is an E3 call.
  • LPM-34 is the LP kit on every ARVT96 / ADVT96 SKU. Not LPM-33 (AR9S96) and not LPM-30 (AR9T96 0303AN).
  • Single-stage thermostat is legal. That does not turn this into a tap furnace. CFM still comes from the IFC tables.
  • Bottom return: unfold the flanges. SS notes ~18% airflow loss — looks like a limit/noise call on a brand-new install.
  • Door card on THIS cabinet wins. The spec-sheet wiring page has the ComfortBridge menu, not a printable E-table.

Related plates

  • amana-amvc96 — Older ComfortBridge two-stage VS cousin. Same E/b/d language — different memory card and no 0.5" heat-ESP hard limit on that plate.
  • amana-ar9t96 — 9-speed tap, conventional 24V, single 7-seg. Do not use that chart on this communicating VS IFC.
  • amana-ar9s96 — Single-stage 9-speed sister — one PS, 0140F20003-B, E0–E7. Not ComfortBridge.
  • amana-amvm97 — Modulating ComfortBridge cousin — 0–100% valve and variable inducer. Do not apply two-stage staging tests.
  • goodman-gmvc96 — Goodman ComfortBridge two-stage twin of AMVC96 — not this newer ARVT96 plate.