Models
Bryantfurnace

926T

Preferred 96 · two-stage · variable-speed · InteliSense

Bryant Preferred 96 two-stage furnace (factory twin of Carrier 59TP6). Two-digit IFC: 31, 32, 33, 34, 41, 42…. Model plug required. InteliSense is remote data to an ecobee-for-Bryant — it is not Evolution ABCD. 925T is the previous Preferred two-stage plate (same 31/32 language).

Not 987M Evolution modulating (ABCD, pressure band). Not 986T / 987T Evolution two-stage (ABCD bus). Not 926S (single-stage Preferred — one PS, no W2). Not 916S Legacy flash-look Comfort 96. A 926T will not become an Evolution furnace by swapping the stat.

AFUE

Up to 96.7% · two-stage condensing

Staging

Two-stage gas · two-speed inducer · dual pressure switches

Blower

Variable / 25-speed ECM · model plug + setup switches

Control

Two-digit Preferred IFC · 24V thermostat · optional InteliSense

Tstat

Conventional 24V W1/W2. InteliSense is dealer data, not ABCD.

Sister SKU

Carrier 59TP6 same IFC · 927T current Preferred two-stage refresh

This board

Preferred two-digit IFC (not Evolution ABCD)

  • Codes are two digits: 11–14, 21–24, 31, 32, 33, 34, 41–45. Same language as Carrier 59TP6.
  • A readout like 3 1.6 is often STAGE + CFM (stage 3 / 1,600 CFM) — not fault 31. Faults flash; run status is steadier. Confirm on THIS Bryant door card.
  • 32 = low-fire PS. 31 on a high-fire call is the active-stage prove. Do not apply 916S ‘one switch’ thinking.
  • InteliSense (when enabled with the matching Bryant/ecobee stat) does not change 31/33/34 meanings.

Last codes store ~48 h or until power is pulled (11 = no history). Use the diagnostic button where equipped. Write the two digits before a power cycle.

Universal swap

No universal

Preferred VS two-stage. Not a 50A55. ICM2807 is HK42FZ017 only — this VS plate is usually not that silk.

Silk: HK42FZ017

White-Rodgers

ICM

  • ICM2807

    Only if the silk is actually HK42FZ017. Do not order 2807 because the cabinet says 926T.

Honeywell

  • 50A55-843 / 50M56U-843 (single-stage PSC).
  • ICM282B (HK42FZ004–016/034 single-stage).
  • Evolution 987M / 986T communicating IFC.

After you pull the dead card

  1. 1Photograph the silk. If it is not HK42FZ017, order the OEM Preferred VS two-stage IFC for 926T / 59TP6.
  2. 2This blower is variable-speed. A PSC heat/cool relay board will not run it.

Field wiring

Written landings for Bryant 926T. Not a factory schematic.

Furnace · two-stage 24V
R / C / W1 / W2 / Y / GGas furnace

Two-stage conventional furnace. W1 low fire, W2 high fire. Outdoor staging is Y or Y1/Y2 — separate from the gas valve.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → R120V / 24V
  2. 2Low. W1 → inducer LOW → LPS → HSI → valve LOWFirst fire
  3. 3High. W2 → inducer HIGH → HPS → valve HIGHSecond solenoid
  4. 4Flame. Rod → IFCµA DC both stages
  5. 5Blow. IFC → heat blowerAfter flame

This indoor

Preferred 96 two-stage. W1/W2. Not 987M ABCD.

24V two-stage heat

Door has W1 and W2. Not Infinity. Not ComfortBridge.

Two-stage thermostat

A single-W stat never proves high fire. That is not a weak inducer.

  • R24V hot24V
  • CCommon24V
  • W1Low-fire heat24V
  • W2High-fire heat24V
  • Y / Y1Cool24V
  • Y2Outdoor high if the condenser is two-stage24V
  • GFan24V

Two-stage IFC

W2 is high fire. Do not tee the pressure-switch hoses because there are two stages.

  • RHot24V
  • CCommon to outdoor24V
  • W1Low fire24V
  • W2High fire24V
  • YCool out24V
  • GBlower / cool tap24V

Landing

  • 24VStat W1IFC W1

    Low fire

  • 24VStat W2IFC W2

    High fire. Missing W2 = stuck on low.

  • 24VStat YIFC Youtdoor Y

    Cool

  • 24VC throughout

    Common

IFC harness — two-stage heat

W1 then W2. Low-fire prove is not high-fire prove.

Transformer + fuse

Same 24V transformer as single-stage. Fuse still kills the whole strip.

  • L1 / N120VLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout. A limit trip is not an E9 / 32 pressure-switch story.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + two pressure switches

W1 = inducer low + LPS. W2 = inducer high + HPS. Separate hoses. Do not tee.

  • IND LO120V low-speed inducerLine
  • IND HI120V high-speed inducerLine
  • LPSLow-fire prove24V
  • HPSHigh-fire prove24V
  • HOSESOne hose per switch. Never tee LPS and HPS24V

HSI + two-stage valve

Igniter 120V. Low solenoid on W1. Second solenoid on W2 after HPS closes.

  • HSI120V igniterLine
  • MV / LO24V low-fire solenoid24V
  • HV / HI24V high-fire solenoid24V
  • FLAMEµA DC on the rod24V

Serial variable-speed ECM

IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.

  • SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
  • CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V

Landing

  • LineW1IFCinducer LOWLPS

    120V inducer, 24V prove

  • LineIFCHSIvalve LOW

    120V igniter, 24V low solenoid

  • 24VW2inducer HIGHHPSvalve HIGH

    Missing W2 = stuck on low

  • 24VFlame rodIFC

    µA DC

  • LineIFCheat blower

    After flame. Motor class on this plate.

Prove it

  • W1 then W2 at the IFC under a 2-heat call.
  • If it never stages, W2 is missing at the board — not a bad gas valve until that is proven.

Do not

  • Do not convert this to Infinity by landing W on a random terminal.
  • Do not apply AMVC / ARVT ComfortBridge menus or a memory card.

926T / 59TP6 / AR9T96 / GR9T96 / S9V2 / EL296E class. Same landing on 80% metal-vent cousins — the vent is not the wire.

Sequence

  1. 1

    W/W1

    Inducer low → low-fire PS (32 family) → HSI → low-fire valve → flame (34 if no prove) → VS blower per model plug.

  2. 2

    W2

    Inducer high → high-fire switch → second solenoid. 23 = a switch that should have opened didn’t.

  3. 3

    Limits

    33 is the open limit/rollout circuit. Three minutes of 33 becomes lockout 13 (3-hour auto reset).

  4. 4

    Ignition fail

    34 repeats, then lockout 14 (3-hour auto reset).

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

11

No stored history

info

Memory empty or power was cycled.

  1. 1 Confirm this is not a fault

    On the Bryant 926T this readout (11) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the Bryant 926T IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: Not a fault. Recreate the call and watch the live code.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch Preferred two-digit IFC (not Evolution ABCD) through one cycle and write the first real fault that replaces this status word.

    Expect: W/W1: Inducer low → low-fire PS (32 family) → HSI → low-fire valve → flame (34 if no prove) → VS blower per model plug.

12

Blower on after power-up

info

Powered up on a W call — 90 s blower.

  1. 1 Confirm this is not a fault

    On the Bryant 926T this readout (12) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the Bryant 926T IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: Normal after a brownout. Repeating 12 + 41 = VS calibration / static.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch Preferred two-digit IFC (not Evolution ABCD) through one cycle and write the first real fault that replaces this status word.

    Expect: W/W1: Inducer low → low-fire PS (32 family) → HSI → low-fire valve → flame (34 if no prove) → VS blower per model plug.

13

Limit lockout

lockout

Limit/rollout stayed open. Auto-reset ~3 h.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Bryant 926T rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Treat as a hardened 33. Filter, static, rise, rollout reset.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Bryant 926T is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

14

Ignition lockout

lockout

Hardened 34. Auto-reset ~3 h.

  1. 1 Watch one full try — do not reset

    Write the Bryant 926T code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, flame sensor, ground. Do not sit on resets.

    Expect: W/W1 → W2 → Limits → Ignition fail

  2. 2 Gas and the valve

    Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.

    Expect: Inlet and manifold on the plate. 24 VAC only during trial.

  3. 3 Flame prove, then the lockout timer

    Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.

    Expect: Flame sense: µA per THIS Bryant door card (typically ≥ 0.5–1.0 µA class).

21

Gas-heat lockout / model plug

lockout

Valve relay fault or missing/wrong model plug.

  1. 1 Read the plug / card on THIS cabinet

    On Bryant 926T the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Model plug seated for THIS 926T cabinet size. A 100 kBtu plug in an 80 kBtu cabinet overfires and limits.

    Expect: Plug / card part matches the rating plate and the replacement control bulletin.

  2. 2 Reseat, then confirm the menu

    Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Miswired valve.

    Expect: IFC recognizes the plug. No size-mismatch code.

  3. 3 Do not run it mismatched

    A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.

    Expect: One clean sequence on the correct identity.

22

Flame with valve off

hazard

Flame sense while GV de-energized.

  1. 1 Shut the gas cock first

    On Bryant 926T the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Leaking valve. Shut the cock.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

23

PS did not open

lockout

A pressure switch is still made when it should be open.

  1. 1 Unplug the switch with the inducer off

    On Bryant 926T this code is the switch made when the inducer is not running. Unplug that switch only. Welded switch, water in hose, inducer still spinning when it should be off.

    Expect: Code changes when the harness is open.

    If fail: Wrong switch, or the IFC input is shorted.

    If pass: Switch/hose path. Go to step 2.

  2. 2 Water in the hose vs a welded switch

    Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off.

    Expect: Hose empty. Switch opens with no draft.

  3. 3 IFC input last

    If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Bryant 926T IFC input is shorted. Do not keep swapping switches.

    Expect: Known-good open switch + open harness = code gone. If not, IFC.

24

Secondary fuse open

warn

24 V fuse on the IFC.

  1. 1 Find the 24 V short before you replace the fuse

    On Bryant 926T an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. Tstat short, HUM/EAC, valve harness. Replace fuse only after the short is gone.

    Expect: Fuse out. 24 V transformer still good. Harness isolated.

  2. 2 Replace the fuse with the harness off

    New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC).

    Expect: Fuse holds with harness off. Dies when the shorted lead lands.

  3. 3 If it blows with the harness off

    Short is on the Bryant 926T IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.

    Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.

31

Pressure / draft / aux did not close

lockout

Inducer running, prove switch open. On two-stage this is often the active-stage PS.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Bryant 926T active code. Write 31. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap, collector, PVC, wind, inducer RPM (42 if the inducer itself is out of band).

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. If open >5 min, many of these IFCs park the inducer 15 min before retry.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

32

Low-fire / low PS

lockout

Low-stage pressure path. Classic attic 926T in wind/ice.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Bryant 926T active code. Write 32. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Low-fire hose only. Intake termination. Attic PVC slope back to the collector.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Do not confuse a live 3 1.6 CFM readout with 32.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

33

Limit or rollout open

warn

The winter callback. Airflow first.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Bryant 926T rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Filter, VS heat CFM (setup switches / model plug), coil, return. Rollout is manual reset — inspect exchanger before you reset.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Bryant 926T is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Three minutes → 13.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

34

Ignition prove fail

lockout

Trial without flame sense. Three strikes → 14.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Bryant 926T during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. HSI glow and 120 VAC, gas cock, manifold, flame rod oxide, IFC ground.

    Expect: Flame sense: µA per THIS Bryant door card (typically ≥ 0.5–1.0 µA class).

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold on the rating plate. Solid burner-box ground.

  3. 3 Prove it is not a switch opening

    Watch the live Bryant 926T display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

41

Blower RPM out of band

lockout

VS motor too slow/fast vs model plug.

  1. 1 Read the plug / card on THIS cabinet

    On Bryant 926T the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Static, wheel, harness, correct model plug, setup SW for AC tons / CF.

    Expect: Plug / card part matches the rating plate and the replacement control bulletin.

  2. 2 Reseat, then confirm the menu

    Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP.

    Expect: IFC recognizes the plug. No size-mismatch code.

  3. 3 Do not run it mismatched

    A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.

    Expect: One clean sequence on the correct identity.

42

Inducer RPM out of band

lockout

Inducer not at commanded speed.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Bryant 926T active code. Write 42. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Condensate in the inducer, bad inducer, vent load. Often pairs with 31/32.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

43

PS tubing / drain

lockout

Blockage or disconnected hose.

  1. 1 Float and the pan

    On Bryant 926T a drain / float code is water until proven otherwise. Pan full? Float stuck? Secondary drain piped? Trace each hose. Attic jobs grow ice in the vent, not just the hose.

    Expect: Pan dry after you clear it. Float moves freely.

  2. 2 Trap and the pump

    Indoor trap primed and flowing. Condensate pump actually pumping, check valve not stuck. On a furnace, a drowned collector will also throw PS codes — clear both.

    Expect: Trap flowing. Pump discharges. No water in the collector.

  3. 3 Then the switch circuit

    If the pan is dry and the code stays, ohm the float / condensate switch and the IFC input. Do not jump a wet-switch input as a repair.

    Expect: Switch closed when dry. Code gone.

44

Blower calibration

warn

CFM learn failed.

  1. 1 Is the wheel free?

    Spin the Bryant 926T blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Filter, 41 also present → motor/static. Wrong A/C or CF switch.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data.

    Expect: Command present. Motor amps in range, not locked.

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.

    Expect: Static on the blower chart. Matching motor / shared-data card.

45

Control lockout

lockout

IFC parked itself. This is Bryant/Carrier 45 — not Rheem 45 (low PS open).

  1. 1 Write the live code and watch one cycle

    On Bryant 926T read Preferred two-digit IFC (not Evolution ABCD) before you pull power. Write 45 exactly. Watch one full sequence and note which step dies. Power reset once after the root code is understood. Repeat 45 = board or persistent input.

    Expect: W/W1: Inducer low → low-fire PS (32 family) → HSI → low-fire valve → flame (34 if no prove) → VS blower per model plug.

  2. 2 Prove the circuit this code names

    Use the Bryant 926T door card and the test points on this plate. Isolate the named switch, sensor, or output with a meter — do not swap the IFC first.

    Expect: A measured open, short, or out-of-range reading — not a guess.

  3. 3 Confirm with a number, then the next part

    If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.

    Expect: Model plug: Must match this 926T cabinet. Missing plug → 21 and garbage CFM.

Workflows

33 / 13 overheating

Most common 926T winter call.

  1. 1 Prove the call and the live code

    Is it 33 (live) or 13 (lockout)? 13 needs the 3-hour wait or a power cycle after the cause is fixed.

    Expect: Write whatever Preferred two-digit IFC (not Evolution ABCD) is showing. Last codes store ~48 h or until power is pulled (11 = no history). Use the diagnostic button where equipped. Write the two digits before a power cycle.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Read heat CFM / setup, not a Goodman 9-speed tap — this motor is VS with a model plug.

    Expect: W2: Inducer high → high-fire switch → second solenoid. 23 = a switch that should have opened didn’t.

  3. 3 Confirm with a number, then the next part

    Model plug present and correct for the cabinet? Wrong plug = 21 and a 33 that never dies. TES vs the 926T / 59TP6 blower chart. Media cabinets and downsized returns are the usual. Rollout portion of the 33 circuit: if the rollout is open, stop and inspect.

    Expect: Model plug: Must match this 926T cabinet. Missing plug → 21 and garbage CFM. · Flame sense: µA per THIS Bryant door card (typically ≥ 0.5–1.0 µA class).

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

32 with 34

Attic 926T, no heat. These are different faults.

  1. 1 Prove the call and the live code

    32 is draft at low fire. 34 is ignition prove. Fix 32 first or you will never get a fair 34 test.

    Expect: Write whatever Preferred two-digit IFC (not Evolution ABCD) is showing. Last codes store ~48 h or until power is pulled (11 = no history). Use the diagnostic button where equipped. Write the two digits before a power cycle.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Trap and PVC slope in the attic.

    Expect: W2: Inducer high → high-fire switch → second solenoid. 23 = a switch that should have opened didn’t.

  3. 3 Confirm with a number, then the next part

    Then HSI and rod. 34 repeating becomes 14. Do not add a hard-start — this is not the outdoor.

    Expect: Model plug: Must match this 926T cabinet. Missing plug → 21 and garbage CFM. · Flame sense: µA per THIS Bryant door card (typically ≥ 0.5–1.0 µA class).

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Which Bryant 96% is this?

Plate is dirty or the last tech said ‘it’s a Bryant 96.’

  1. 1 Prove the call and the live code

    926T / 927T = Preferred two-stage, 24V, model plug, 32 exists. Stay here.

    Expect: Write whatever Preferred two-digit IFC (not Evolution ABCD) is showing. Last codes store ~48 h or until power is pulled (11 = no history). Use the diagnostic button where equipped. Write the two digits before a power cycle.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    926S = Preferred single-stage. One PS. Leave this page.

    Expect: W2: Inducer high → high-fire switch → second solenoid. 23 = a switch that should have opened didn’t.

  3. 3 Confirm with a number, then the next part

    986T / 987T = Evolution two-stage, ABCD wall control. Leave this page. 987M = Evolution modulating. 31 is a band. Leave this page. 916S / 915S = Legacy single-stage Comfort-style. Leave this page.

    Expect: Model plug: Must match this 926T cabinet. Missing plug → 21 and garbage CFM. · Flame sense: µA per THIS Bryant door card (typically ≥ 0.5–1.0 µA class).

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Model plug

Must match this 926T cabinet. Missing plug → 21 and garbage CFM.

Flame sense

µA per THIS Bryant door card (typically ≥ 0.5–1.0 µA class).

Setup SW

AC tons and CF affect 41/44 if someone stacked extra cooling.

Gotchas

  • Carrier 59TP6 is the factory twin — same two-digit card. 987M is not.
  • Bryant 45 is control lockout. Rheem 45 is low-pressure open. Do not mix those.
  • A display of 3 1.6 is often live airflow, not code 31.
  • Replacing the IFC without moving the model plug is how you create a 41/44 ghost.

Related plates

Install this plate

Install 926T as Preferred 24V two-stage VS. Model plug is mandatory. InteliSense is not Evolution ABCD.

Cat IV PVC · two-stage · dual PS · VS ECM + model plug · 24V W1/W2 · optional InteliSense

Model plug & airflow

  • The model plug must match THIS cabinet (80 kBtu plug in a 100 cabinet overfires and 33s). A missing plug is 21.
  • Setup switches set AC tons / comfort profile. This is not a Goodman 9-speed tap card.
  • 927T is the current Preferred two-stage refresh — same 31/32 language. 925T is the previous plate.

Vent & prove

  • PVC 2-pipe / 1-pipe / ventilated combustion air per the 59TP6 / 926T guide. Prime the trap.
  • 32 is low-fire PS. 31 on a high-fire call is the active-stage prove. Do not apply 916S one-switch thinking.
  • A readout like 3 1.6 is often STAGE + CFM, not fault 31. Confirm on this Bryant door card.

Thermostat

  • Conventional 24V W1/W2. InteliSense (Bryant/ecobee) is remote data — it does not turn this into an Evolution furnace.
  • An Evolution ABCD stat will not make a 926T speak 987M language.

First fire

  1. 1Confirm model plug part number against the door card before gas.
  2. 2W1: low inducer, 32-path prove, HSI, low fire, VS heat CFM.
  3. 3W2: high inducer, high-fire switch, second solenoid. 23 = a switch that should have opened didn’t.
  4. 4Rise / static vs the 926T / 59TP6 blower chart. Media cabinets are the usual 33.

Do not on Bryant 926T

  • Do not treat this as 987M / 986T Evolution. No ABCD bus.
  • Do not apply Rheem 45 to a Bryant 45 — 45 here is IFC lockout, not low PS open.
  • Do not steal 916S single-stage setup switches.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • 926T product pageProduct pagePreferred 96 two-stage · InteliSense. Factory twin of Carrier 59TP6.Open manufacturer PDF
  • 59TP6 / 926TB / PG96VTA service & install guideSpec sheetCarrier/Bryant shared guide covering 59TP6, 926TB, PG96VTA — vent, combustion air, and setup.Open manufacturer PDF
  • Bryant document searchLiterature searchEnter the full Bryant plate (926TB60100V21, 987MA…). Owner PDFs are public; many I/Os are dealer-gated.Open manufacturer PDF
  • Bryant document searchLiterature searchSearch Bryant 926T on the maker’s literature page.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Distributor HX claims sheet

    dealerUS

    Furnace heat exchanger claims — serial in/out of range

    Serial 2993A00001 – 1808A99999 (in-range); later serials are standard warranty

    Primary or secondary heat exchanger failure · Distributor claim path

  • CE Canada HX guide

    dealerCanada

    Canada furnace heat exchanger claim options

    2023-02-20

    Heat exchanger failure — Canada · Canada distributor program

  • CE Canada Bryant trade-in 2025–26

    ended seasonCanada

    High-efficiency gas furnace trade-in — Bryant Canada

    2025-04 (ended 2026-04-30)

    Failed 340–355 family secondary within 20 years of install · Trade-in (ended)

  • Residential limited warranty

    warranty sheet

    Carrier / Bryant registered heat-exchanger terms

    Current 59-series / Evolution / Preferred registered warranty · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal