Bryant

926S

Furnace · Preferred 96 · single-stage · variable-speed · InteliSense

Bryant Preferred 96 single-stage. VS / 25-speed blower and InteliSense like 926T, but one gas solenoid and one pressure switch. Two-digit IFC. A 32 on this board is not ‘low fire’ — there is no high fire.

Not 926T (two-stage, dual PS, W2). Not 916S Legacy (fixed/18-speed Comfort, no InteliSense VS story). Not 987M / 986T Evolution ABCD.

Walk this in Diagnose

This plate

AFUE
Up to 97% · single-stage condensing
Staging
Single-stage gas valve · one inducer speed · one pressure switch
Blower
Variable / 25-speed ECM · setup, not a 926T two-stage plug map
Control
Two-digit Preferred IFC · 24V · optional InteliSense

This board

Preferred two-digit IFC · single-stage

  • Same 11–14, 21–24, 31, 33, 34, 41, 45 family as other Bryant/Carrier two-digit boards.
  • One draft switch. 31 is that switch. Door-card 32, if printed, is still the only PS — not a 926T low-fire path.
  • No W2 furnace terminal that means high fire. A leftover W2 is unused or an AC stage.

Sequence

  1. W. Inducer → single PS must close (31 if not) → HSI → valve → flame (34) → VS blower.
  2. No W2 path. There is no high-fire prove and no second solenoid.

Faults on this IFC

  • 13 / 33

    Limit / lockout

    warn

    Airflow or rollout. 13 is the hardened 33.

    • VS heat CFM / setup — not a 9-speed tap.
    • Filter, coil, return. Rollout is manual reset.
  • 14 / 34

    Ignition

    lockout

    No flame prove. 14 is the hardened 34.

    • HSI, gas, rod, ground.
  • 24

    Fuse

    warn

    24 V fuse open.

    • Tstat short, HUM/EAC, valve harness.
  • 31

    PS / draft

    lockout

    The only pressure switch did not close.

    • Trap, collector, PVC, wind, inducer. One hose, one switch.
    • Do not hunt a high-fire hose.
  • 41 / 44

    Blower RPM / calibration

    lockout

    VS motor vs setup.

    • Static, filter, correct setup for the coil tons.
  • 45

    Control lockout

    lockout

    IFC parked. Not Rheem 45.

    • Find the root two-digit first.

Workflows

31 on a 926S

Inducer runs, no ignition.

  1. This is single-stage. One PS. Do not pull a 926T dual-hose card.
  2. Trap and PVC first — 96% Preferred still drowns a collector.
  3. Then inducer 120 VAC and the only hose.
  4. If someone landed W2 from an old 926T job, ignore it for furnace staging.

Test points

Pressure switch
One NO switch. Closed only after inducer is up.
Manifold
Single-stage plate value — no low/high pair.

Gotchas

  • Techs treat 926S like 926T and start looking for high-fire. There is none.
  • 916S is the Legacy Comfort cousin — similar 31, different blower setup.

Related plates

  • bryant-926t — Preferred two-stage sibling. Dual PS, W2, model-plug 32.
  • bryant-916s — Legacy 96/97 single-stage. Same one-PS 31 physics, Comfort/Legacy IFC.
  • carrier-59sc5 — Carrier Comfort 96 single-stage parent language.