Bryant
926S Furnace · Preferred 96 · single-stage · variable-speed · InteliSense
Bryant Preferred 96 single-stage. VS / 25-speed blower and InteliSense like 926T, but one gas solenoid and one pressure switch. Two-digit IFC. A 32 on this board is not ‘low fire’ — there is no high fire.
Not 926T (two-stage, dual PS, W2). Not 916S Legacy (fixed/18-speed Comfort, no InteliSense VS story). Not 987M / 986T Evolution ABCD.
Walk this in Diagnose This plate
AFUE Up to 97% · single-stage condensing
Staging Single-stage gas valve · one inducer speed · one pressure switch
Blower Variable / 25-speed ECM · setup, not a 926T two-stage plug map
Control Two-digit Preferred IFC · 24V · optional InteliSense This board Preferred two-digit IFC · single-stage
Same 11–14, 21–24, 31, 33, 34, 41, 45 family as other Bryant/Carrier two-digit boards. One draft switch. 31 is that switch. Door-card 32, if printed, is still the only PS — not a 926T low-fire path. No W2 furnace terminal that means high fire. A leftover W2 is unused or an AC stage. Sequence W. Inducer → single PS must close (31 if not) → HSI → valve → flame (34) → VS blower. No W2 path. There is no high-fire prove and no second solenoid. Faults on this IFC 13 / 33
Limit / lockout warn Airflow or rollout. 13 is the hardened 33.
VS heat CFM / setup — not a 9-speed tap. Filter, coil, return. Rollout is manual reset. 14 / 34
Ignition lockout No flame prove. 14 is the hardened 34.
24
Fuse warn 24 V fuse open.
Tstat short, HUM/EAC, valve harness. 31
PS / draft lockout The only pressure switch did not close.
Trap, collector, PVC, wind, inducer. One hose, one switch. Do not hunt a high-fire hose. 41 / 44
Blower RPM / calibration lockout VS motor vs setup.
Static, filter, correct setup for the coil tons. 45
Control lockout lockout IFC parked. Not Rheem 45.
Find the root two-digit first. Workflows 31 on a 926S Inducer runs, no ignition.
This is single-stage. One PS. Do not pull a 926T dual-hose card. Trap and PVC first — 96% Preferred still drowns a collector. Then inducer 120 VAC and the only hose. If someone landed W2 from an old 926T job, ignore it for furnace staging. Test points
Pressure switch One NO switch. Closed only after inducer is up.
Manifold Single-stage plate value — no low/high pair. Gotchas Techs treat 926S like 926T and start looking for high-fire. There is none. 916S is the Legacy Comfort cousin — similar 31, different blower setup. Related plates bryant-926t — Preferred two-stage sibling. Dual PS, W2, model-plug 32. bryant-916s — Legacy 96/97 single-stage. Same one-PS 31 physics, Comfort/Legacy IFC. carrier-59sc5 — Carrier Comfort 96 single-stage parent language. Terms Privacy Refund policy FieldBench is an independent reference tool and is not affiliated with, authorized by, or endorsed by Goodman, Amana, Daikin, Carrier, Bryant, or any equipment manufacturer. All product names and model numbers are trademarks of their respective owners, used for identification only.