58SU0
Ultra-low NOx · 80% · Cat I · CA
Carrier Comfort / Infinity 80% ultra-low NOx (58SU0 Comfort, 58CU0 Infinity-family). Premix burner, metal vent. 31 is chimney draft. Not 58STA standard Comfort 80.
Not 58STA. Not 59CU5 96% ULN. Not 58SP1 Low-NOx (40 ng/J class, not SCAQMD ULN).
NOx
SCAQMD / SJV ultra-low NOx
AFUE
80% · Cat I metal
This board
Two-digit or vintage LED-status IFC (Comfort 80)
- Current boards use Carrier two-digit: 11–14, 21–24, 31, 33, 34.
- Older Comfort 80 IFCs use an amber LED status chart on the door. Do not import two-digit meanings onto a 1–6 flash board without that sticker, and do not import an old flash chart onto a two-digit display.
- 31 = metal-vent draft / inducer / common vent. NEVER a PVC condensate trap.
- No 32 low-fire code on single-stage STA. If you are looking at 32, you are on a two-stage board (58CTA / 59TP6 / 59TN6) or the wrong card.
Two-digit: last codes ~48 h or until power is pulled (11 = no history). LED vintage: flashes until power is pulled — write the count against THIS door card.
Universal swap
80% ULN premix. Not a 50A55 80% drop-in.
White-Rodgers
—ICM
—Honeywell
—- 50A55-843 ‘because 80%’. 58STA standard Comfort board.
After you pull the dead card
- 1OEM ULN 80% IFC. Metal vent.
Field wiring
Written landings for Carrier 58SU0. Not a factory schematic.
Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → transformer → R120V in, 24V out
- 2Call. Stat W → IFC W~24 VAC
- 3Draft. IFC → inducer → PS close120V motor, 24V prove
- 4Ignite. IFC → HSI120 VAC
- 5Gas. IFC → valve~24 VAC
- 6Flame. Rod → IFCµA DC
- 7Blow. IFC → heat speedAfter flame prove
This indoor
Comfort 80 ULN. Same 24V strip.
24V single-stage heat
Door card is one-stage. Twin terminal empty unless the job is actually twinned.
Wall thermostat
Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.
- R24V hot from the IFC24V
- CCommon24V
- WHeat24V
- YCool — also starts the outdoor24V
- GFan24V
Furnace IFC
Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.
- RHot to the stat24V
- CCommon — must reach the outdoor24V
- WHeat call24V
- YCool in / cool out24V
- GBlower24V
- TWINEmpty unless twinned24V
Landing
- 24VIFC Rstat R
~24 VAC hot
- 24VIFC Cstat Coutdoor C
Common
- 24VStat WIFC W
Heat. Stays in this cabinet.
- 24VStat YIFC Youtdoor Y
Cool / contactor
- 24VStat GIFC G
Fan. Does not go outdoors.
IFC harness — single-stage heat
After W arrives. This is the gas train, not the thermostat strip.
Transformer + fuse
120V primary. 24V secondary. Dark stat = fuse / door / transformer first.
- L1 / N120V to the IFCLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout in series. Open anywhere kills heat.
- DOORInterlock24V
- LIMITMain limit — rise / no airflow24V
- ROLLOUTManual reset. Do not jumper and leave24V
Inducer + one pressure switch
W → inducer 120V → PS closes → IFC continues. One hose, one switch.
- IND120V from the IFC to the inducerLine
- PS24V prove back to the IFC24V
- HOSESingle hose. Do not add a second because two-stage boards have two.24V
HSI + single valve
Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.
- HSI120V hot-surface igniter — not 24VLine
- VALVE24V to the single solenoid24V
- FLAMEµA DC on the rod. Not a 24V circuit24V
PSC blower + run cap
Heat / cool / park taps on the motor. The cap is on this blower — not the outdoor dual can.
- HEATHeat speed tap24V
- COOLCool speed tap24V
- PARKUnused leads parked24V
- CAPRun capacitor on the blowerCap
Landing
- LineL1IFCinducer
120 VAC after W
- 24VIFCPSIFC
~24 VAC prove. Open PS = no ignition.
- LineIFCHSI
120 VAC during trial
- 24VIFCgas valve
~24 VAC after flame prove starts
- 24VFlame rodIFC
µA DC. Not 24V.
- LineIFCblower
120V tap + cap
Prove it
- 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
- W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.
Do not
- Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
- Do not hunt W2 / E8 / high-fire on a one-stage door.
- TWIN must be empty on a standalone.
9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.
Sequence
- 1
W
Inducer → metal-vent draft switch must close (31 if not) → HSI → single-stage valve → flame (34 if no prove) → heat-speed blower.
- 2
No PVC
Category I. There is no collector and no trap to dump. 31 lives in the chimney, cap, liner, common vent, and inducer wheel.
- 3
58CTA cousin
Two-stage 80% adds W2 and a high-fire path. Still metal vent. Still not a 96% trap. Do not use that high-fire path on an STA.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
11
No stored history
Memory empty or power was cycled (two-digit boards).
1 Confirm this is not a fault
On the Carrier 58SU0 this readout (11) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the Carrier 58SU0 IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: Not a fault. Recreate the W call.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch Two-digit or vintage LED-status IFC (Comfort 80) through one cycle and write the first real fault that replaces this status word.
Expect: W: Inducer → metal-vent draft switch must close (31 if not) → HSI → single-stage valve → flame (34 if no prove) → heat-speed blower.
12
Blower on after power-up
Powered up on a W call.
1 Confirm this is not a fault
On the Carrier 58SU0 this readout (12) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the Carrier 58SU0 IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: Normal after a brownout on two-digit IFCs.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch Two-digit or vintage LED-status IFC (Comfort 80) through one cycle and write the first real fault that replaces this status word.
Expect: W: Inducer → metal-vent draft switch must close (31 if not) → HSI → single-stage valve → flame (34 if no prove) → heat-speed blower.
13
Limit lockout
Hardened 33. Limit/rollout stayed open.
1 Treat this as flame outside the exchanger
Do not reset the Carrier 58SU0 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Filter, heat speed, dirty A-coil, rollout reset.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Carrier 58SU0 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
14
Ignition lockout
Hardened 34.
1 Watch one full try — do not reset
Write the Carrier 58SU0 code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, rod, ground. Do not sit on resets.
Expect: W → No PVC → 58CTA cousin
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.
Expect: Inlet and manifold on the plate. 24 VAC only during trial.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.
Expect: Stable µA after light-off. No new PS/limit code.
21
Gas-heat lockout / model plug
Valve relay fault, or missing/wrong model plug on boards that use one.
1 Read the plug / card on THIS cabinet
On Carrier 58SU0 the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Most Comfort 80 STA boards are not TP6-style plug cabinets — check the door before you hunt a plug.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Valve harness and 24 VAC during trial.
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.
Expect: One clean sequence on the correct identity.
22
Flame with valve off
Flame sense while GV de-energized.
1 Shut the gas cock first
On Carrier 58SU0 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Leaking valve. Shut the cock.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
23
PS did not open
Draft switch still made when it should be open.
1 Unplug the switch with the inducer off
On Carrier 58SU0 this code is the switch made when the inducer is not running. Unplug that switch only. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Carrier 58SU0 IFC input is shorted. Do not keep swapping switches. Welded switch, residual chimney draft, inducer still spinning.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
24
Secondary fuse open
24 V fuse on the IFC.
1 Find the 24 V short before you replace the fuse
On Carrier 58SU0 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. Tstat short, HUM/EAC, valve harness. Replace fuse only after the short is gone.
Expect: Fuse out. 24 V transformer still good. Harness isolated.
2 Replace the fuse with the harness off
New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC).
Expect: Fuse holds with harness off. Dies when the shorted lead lands.
3 If it blows with the harness off
Short is on the Carrier 58SU0 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.
Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.
31
Metal-vent draft / inducer
Category I draft will not prove. NEVER a PVC condensate trap.
1 Prove inducer and the live code
Do not pull power — that clears the Carrier 58SU0 active code. Write 31. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Chimney liner, cap, masonry debris, wind.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
33
Limit or rollout open
Airflow or flame-containment. Dirty A-coil on an 80% is the winter/summer crossover call.
1 Treat this as flame outside the exchanger
Do not reset the Carrier 58SU0 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Filter, blower speed, A-coil on top of the furnace — 80% coils load up and limit. Rise vs plate. Rollout: exchanger / burners / flue. Manual reset.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Carrier 58SU0 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Held open → 13.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
34
Ignition prove fail
Trial without flame sense. Repeats → 14.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Carrier 58SU0 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. HSI, gas cock, manifold, rod, ground.
Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Fix 31 metal-vent draft before a fair 34 test.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Carrier 58SU0 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
Workflows
58SU0 no heat
CA 80% ULN.
1 Prove the call and the live code
ULN gas train. Do not use a 58STA LP kit.
Expect: Write whatever Two-digit or vintage LED-status IFC (Comfort 80) is showing. Two-digit: last codes ~48 h or until power is pulled (11 = no history). LED vintage: flashes until power is pulled — write the count against THIS door card.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
31 is metal-vent draft. No trap.
Expect: No PVC: Category I. There is no collector and no trap to dump. 31 lives in the chimney, cap, liner, common vent, and inducer wheel.
3 Confirm with a number, then the next part
58CU0 = Infinity UI. 58SU0 = Comfort 24V.
Expect: Vent: Cat I. Spillage at the draft hood / inducer inlet is a fail. No PVC trap exists. · Draft switch: Open with inducer off; closes on W. 31 = never closed. 23 = never reopened.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Vent
Cat I. Spillage at the draft hood / inducer inlet is a fail. No PVC trap exists.
Draft switch
Open with inducer off; closes on W. 31 = never closed. 23 = never reopened.
Heat speed
Tap / PSC / CT vs rise. Not Infinity CFM and not TP6 model plug.
Gotchas
- 58SP1 is Performance Low-NOx, not this ULN premix.
Related plates
Install this plate
Install Carrier 58SU0 as Ultra-low NOx · 80% · Cat I · CA.
Ultra-low NOx · 80% · Cat I · CA
This plate — not the sister SKU
- Not 58STA. Not 59CU5 96% ULN. Not 58SP1 Low-NOx (40 ng/J class, not SCAQMD ULN).
- 58SP1 is Performance Low-NOx, not this ULN premix.
IFC on this door
- Current boards use Carrier two-digit: 11–14, 21–24, 31, 33, 34.
- Older Comfort 80 IFCs use an amber LED status chart on the door. Do not import two-digit meanings onto a 1–6 flash board without that sticker, and do not import an old flash chart onto a two-digit display.
- 31 = metal-vent draft / inducer / common vent. NEVER a PVC condensate trap.
- No 32 low-fire code on single-stage STA. If you are looking at 32, you are on a two-stage board (58CTA / 59TP6 / 59TN6) or the wrong card.
Hardware
- NOx: SCAQMD / SJV ultra-low NOx
- AFUE: 80% · Cat I metal
First fire
- 1ULN gas train. Do not use a 58STA LP kit.
- 231 is metal-vent draft. No trap.
- 358CU0 = Infinity UI. 58SU0 = Comfort 24V.
Do not on Carrier 58SU0
- Not 58STA. Not 59CU5 96% ULN. Not 58SP1 Low-NOx (40 ng/J class, not SCAQMD ULN).
- 58SP1 is Performance Low-NOx, not this ULN premix.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Carrier residential furnacesLiterature searchProduct pages carry current literature. I/O booklets are typically HVACpartners / dealer.Open manufacturer PDF
- Carrier HVAC resourcesLiterature searchOwner-facing literature hub. Do not invent a 59-series I/O URL.Open manufacturer PDF
- Carrier residential furnacesLiterature searchSearch Carrier 58SU0 on the maker’s literature page.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
warranty sheetCarrier / Bryant registered heat-exchanger terms
Current 59-series / Evolution / Preferred registered warranty · Limited warranty certificate
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal