Furnace · Comfort 80 · single-stage · Category I metal vent
Carrier Comfort 80% single-stage Category I metal-vent furnace. 58STA / 58STX are the single-stage Comfort 80. 58CTA is the two-stage 80% cousin (same vent physics, extra solenoid / high-fire path). Older and current boards speak two-digit codes or a vintage LED-status chart — 31 is always metal-vent draft / inducer / common vent, never a PVC condensate trap.
Not 58CVA / 58MVC Infinity 80 (ABCD communicating two-stage). Not 59SC5 Comfort 96 (PVC trap — a 31 there is a collector, not a chimney). 58CTA is the two-stage 80% cousin: same 31 metal-vent meaning, but it has W2 / high fire this single-stage STA does not.
Current boards use Carrier two-digit: 11–14, 21–24, 31, 33, 34.
Older Comfort 80 IFCs use an amber LED status chart on the door. Do not import two-digit meanings onto a 1–6 flash board without that sticker, and do not import an old flash chart onto a two-digit display.
31 = metal-vent draft / inducer / common vent. NEVER a PVC condensate trap.
No 32 low-fire code on single-stage STA. If you are looking at 32, you are on a two-stage board (58CTA / 59TP6 / 59TN6) or the wrong card.
Sequence
W. Inducer → metal-vent draft switch must close (31 if not) → HSI → single-stage valve → flame (34 if no prove) → heat-speed blower.
No PVC. Category I. There is no collector and no trap to dump. 31 lives in the chimney, cap, liner, common vent, and inducer wheel.
58CTA cousin. Two-stage 80% adds W2 and a high-fire path. Still metal vent. Still not a 96% trap. Do not use that high-fire path on an STA.
Faults on this IFC
11
No stored history
info
Memory empty or power was cycled (two-digit boards).
Not a fault. Recreate the W call.
12
Blower on after power-up
info
Powered up on a W call.
Normal after a brownout on two-digit IFCs.
13
Limit lockout
lockout
Hardened 33. Limit/rollout stayed open.
Filter, heat speed, dirty A-coil, rollout reset.
14
Ignition lockout
lockout
Hardened 34.
HSI, gas, rod, ground. Do not sit on resets.
21
Gas-heat lockout / model plug
lockout
Valve relay fault, or missing/wrong model plug on boards that use one.
Most Comfort 80 STA boards are not TP6-style plug cabinets — check the door before you hunt a plug.
Valve harness and 24 VAC during trial.
22
Flame with valve off
hazard
Flame sense while GV de-energized.
Leaking valve. Shut the cock.
23
PS did not open
lockout
Draft switch still made when it should be open.
Welded switch, residual chimney draft, inducer still spinning.
24
Secondary fuse open
warn
24 V fuse on the IFC.
Tstat short, HUM/EAC, valve harness. Replace fuse only after the short is gone.
31
Metal-vent draft / inducer
lockout
Category I draft will not prove. NEVER a PVC condensate trap.
Chimney liner, cap, masonry debris, wind.
Common-vented water heater — venting tables, not a 96% collector.
Inducer wheel packed or cracked, vent connector disconnected.
PS hose to the inducer housing only. There is no secondary drain to pull.
33
Limit or rollout open
warn
Airflow or flame-containment. Dirty A-coil on an 80% is the winter/summer crossover call.
Filter, blower speed, A-coil on top of the furnace — 80% coils load up and limit.