Lennox Elite ultra-low emission (EL195NE and related NV SKUs). Premix / lowest-emission burner. SureLight language can match the Elite 7-seg — the gas train does not. Not a standard EL196E orifice job.
Not EL196E standard Elite. Not SL297NV Signature ULN. Not ML196.
Clean the inducer pressure port — known EL296. Dust packs the port and throws the whole PS family.
E224
Low PS failed CLOSED
lockout
Low-fire switch is made when it should be open.
Unplug the low switch. Water in the hose or a welded switch.
Inducer still coasting / hose holding residual draft.
E225
High PS failed OPEN
lockout
IFC commanded high; high-fire switch did not close.
Does the inducer actually go high?
High-fire hose not teed to the low switch. Vent capacity on 110/135 kBtu cabinets.
E226
High PS failed CLOSED
lockout
High-fire switch is made when it should be open.
Unplug the high switch only. Water or a welded disc.
W2 shorted so the IFC thinks it should already be in high.
E227
Low PS opened during trial or run
lockout
Low switch had closed, then opened mid-trial or in run.
Wind, ice, trap siphon, inducer dropping out after light-off.
Same port-clean as E223 — a half-clogged port will make then drop.
E228
Combustion air inducer calibration failure
lockout
IFC could not finish pressure-switch calibration.
Vent and both hoses seated. Inducer must be able to sweep both switches.
Fix E223/E225 physics first — calibration will not pass on a clogged port.
E229
Ignition on high fire
info
Low-fire switch did not close in time, so the IFC ran the inducer high and lit on high. OEM: no action needed as a separate repair.
This is a low-fire draft problem wearing a high-fire costume. Fix E223 / E227 physics. Do not start on the high-fire manifold screw.
Also fires on high for ~60 s if continuous fan was already on (heat-exchanger warmup) — that one is information only.
E240
Low flame current — run mode
warn
Flame is present but µA is below the run threshold.
F menu for live µA. Clean the rod — not sandpaper. Neutral-to-ground and E117.
Clears at the end of the heat call. Repeating E240 becomes E270 / E273.
E241
Flame sensed out of sequence — flame still present
hazard
Rod sees flame with the valve de-energized. Flame is still there.
Shut the gas cock. Leaking valve — replace, do not jump.
If flame dies when you shut the cock, the IFC flame circuit / rod short is next.
E250
Limit switch circuit open
warn
Primary / rollout / secondary string is open. If it stays open >3 min the IFC goes to a 1-hour soft lockout (E274).
VS heat CFM vs the EL296 chart — not a 9-speed tap. Filter, coil, media cabinet.
Walk the rollout string if E270 / E274 also store. Manual-reset rollout is a hazard until the cause is gone.
E252
Discharge air too high
warn
Leaving-air temperature above the gas-heat limit (DAT sensor).
Rise vs plate. Heat CFM in the IFC, not a guess.
Input rate / manifold. Sensor itself only after airflow and fire are right.
E270
Soft lockout — max retries, no flame current
lockout
Tried to light, never saw flame current. Soft lockout. Clears on a successful heat call.
Watch a try: inducer, HSI glow, valve click, flame, then F-menu µA. Which step dies?
This is ignition, not rollout. The older field rumor that E270 ‘is rollout’ is wrong on this SureLight family — rollout lives in the E250 / E274 string.
E271
Soft lockout — last retry failed because PS opened
lockout
Retries used up; the last try died when a pressure switch opened.
Treat as a hardened E223 / E227. Port, trap, PVC, inducer.
Do not replace the ignitor because the stack says 270-family.
E272
Soft lockout — last recycle PS opened
lockout
Recycles used up; last recycle failed because a pressure switch opened.
It ran, then draft dropped. Wind, ice, trap siphon, inducer after light-off.
Same two-hose / port-clean as the E223 cluster.
E273
Soft lockout — last recycle flame failure
lockout
Recycles used up; last recycle lost flame signal.
F-menu µA, rod, ground, manifold after blower-on. Flame that dies when the wheel starts is often draft or a weak rod.
Pairs with E240.
E274
Soft lockout — last recycle limit open or limit >3 min
lockout
Recycles used up because the limit string opened, or a limit stayed open longer than 3 minutes.
Hardened E250. VS CFM, media cabinet, rise.
If a rollout is open in that string, stop and inspect the exchanger before you up the CFM.
E275
Flame out of sequence lockout
hazard
Soft lockout after out-of-sequence flame. Same hazard family as E241.
Shut the cock. Valve leak or IFC flame circuit.
1-hour-class lockout. Do not keep resetting.
E290
Ignitor circuit fault
lockout
Failed ignitor or triggering circuitry. 1-hour soft lockout until flame proves stable.
Ohms the HSI. Open / out of IOM range = replace the ignitor.
Good ohms + no 120 VAC during trial = IFC / harness.
E292
Heat airflow restricted below minimum
warn
VS heat CFM is below the minimum the IFC will allow for this firing rate.
Filter, coil, wheel, return. Media cabinets on Elite jobs are the usual.
Some communicating SureLight cards print a different sentence next to E292 — confirm THAT door card before you condemn a motor.
E310
Blower unable to start
lockout
Indoor blower did not start — seized bearings / obstructed wheel class.
Spin the wheel. Ice, debris, rusted module, unplugged harness.
Door-card note: a few revisions park a DAT-sensor sentence on E310. If the card says sensor, treat it as a sensor. If it says wheel/bearings, treat it as a motor.
E311
Blower temperature too high
warn
Blower / module overtemp. IFC sheds or parks heat.
Static, wheel rub, module fins packed with dust.
After a motor swap, confirm you did not put an EL296E CT motor in this VS plug.
E312
Restricted airflow — cooling / CF
warn
Cooling or continuous-fan CFM is below the setting. Cutback / high-static warning.
Filter and duct. VS motor is already in torque limit (roughly 0–0.8 in. w.c. class).
Not a heat-call code. Do not chase E312 with a pressure switch.
Workflows
EL195NE no light
CA / NV Elite.
ULN / NV plate. Standard Elite LP kit is the wrong carton.
Draft is still 96% trap / PVC if this cabinet is condensing. Confirm vent.
Do not drill the premix burner.
Test points
E-code
Three digits. E229 ≠ E225. Confirm odd extras on the door card.
Inducer port
Open to the collector, not packed with oxide. Two hoses, never teed.
Flame (F menu)
µA per EL296 card. Rising while running.
HSI
Cold ohms in the IOM range. 120 VAC during trial.
P menu
Unit size stored for this VS cabinet after any IFC or motor swap.
Gotchas
SL297NV is the Signature communicating ULN. Different board, same burner idea.