EL195NE
Elite · ultra-low emission · CA / NV
Lennox Elite ultra-low emission (EL195NE and related NV SKUs). Premix / lowest-emission burner. SureLight language can match the Elite 7-seg — the gas train does not. Not a standard EL196E orifice job.
Not EL196E standard Elite. Not SL297NV Signature ULN. Not ML196.
NOx
First-in-class ultra-low emission burner (Lennox NV / NE plates)
AFUE
95–96% class condensing (confirm THIS plate)
This board
SureLight 7-seg IFC (E2xx)
- Idle is a decimal blink at 1 Hz (0.5 s on / 0.5 s off). That is not a fault.
- Faults are E plus three digits. Write the full number. E225 ≠ E223 ≠ E229.
- Pushbutton menu: E = recall last 10 (c twice to clear). F = flame µA. P = program unit size (VS only).
- This chart is the 107045-XX / 103130-XX SureLight family used on EL296V. Confirm any odd extra code on THAT door card before you order a part.
- E105-style RS-bus codes appear only if iComfort is wired. Many EL296V jobs are 24V.
Hold the IFC button to a solid E. Last 10 codes, most recent first. Select c and press again while c flashes to erase. Exit at the triple-bar. 7-seg also repeats the active fault.
Universal swap
Ultra-low emission Elite. No published universal. Not a standard EL196E board swap without the ULN gas train.
Silk: 107045
White-Rodgers
—ICM
—Honeywell
—- EL196E standard IFC assumed. 50A55-843.
After you pull the dead card
- 1OEM ULN Elite IFC. Premix burner stays.
Field wiring
Written landings for Lennox EL195NE. Not a factory schematic.
Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → transformer → R120V in, 24V out
- 2Call. Stat W → IFC W~24 VAC
- 3Draft. IFC → inducer → PS close120V motor, 24V prove
- 4Ignite. IFC → HSI120 VAC
- 5Gas. IFC → valve~24 VAC
- 6Flame. Rod → IFCµA DC
- 7Blow. IFC → heat speedAfter flame prove
This indoor
Elite ULN single-stage. Still one W.
24V single-stage heat
Door card is one-stage. Twin terminal empty unless the job is actually twinned.
Wall thermostat
Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.
- R24V hot from the IFC24V
- CCommon24V
- WHeat24V
- YCool — also starts the outdoor24V
- GFan24V
Furnace IFC
Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.
- RHot to the stat24V
- CCommon — must reach the outdoor24V
- WHeat call24V
- YCool in / cool out24V
- GBlower24V
- TWINEmpty unless twinned24V
Landing
- 24VIFC Rstat R
~24 VAC hot
- 24VIFC Cstat Coutdoor C
Common
- 24VStat WIFC W
Heat. Stays in this cabinet.
- 24VStat YIFC Youtdoor Y
Cool / contactor
- 24VStat GIFC G
Fan. Does not go outdoors.
IFC harness — single-stage heat
After W arrives. This is the gas train, not the thermostat strip.
Transformer + fuse
120V primary. 24V secondary. Dark stat = fuse / door / transformer first.
- L1 / N120V to the IFCLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout in series. Open anywhere kills heat.
- DOORInterlock24V
- LIMITMain limit — rise / no airflow24V
- ROLLOUTManual reset. Do not jumper and leave24V
Inducer + one pressure switch
W → inducer 120V → PS closes → IFC continues. One hose, one switch.
- IND120V from the IFC to the inducerLine
- PS24V prove back to the IFC24V
- HOSESingle hose. Do not add a second because two-stage boards have two.24V
HSI + single valve
Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.
- HSI120V hot-surface igniter — not 24VLine
- VALVE24V to the single solenoid24V
- FLAMEµA DC on the rod. Not a 24V circuit24V
Constant-torque ECM
Tap / profile motor. Not serial VS. Not a PSC cap.
- TAPSHeat / cool / adjust profiles on the IFC24V
- COMMONMotor common back to the IFC24V
Landing
- LineL1IFCinducer
120 VAC after W
- 24VIFCPSIFC
~24 VAC prove. Open PS = no ignition.
- LineIFCHSI
120 VAC during trial
- 24VIFCgas valve
~24 VAC after flame prove starts
- 24VFlame rodIFC
µA DC. Not 24V.
- LineIFCblower
IFC heat speed / tap
Prove it
- 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
- W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.
Do not
- Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
- Do not hunt W2 / E8 / high-fire on a one-stage door.
- TWIN must be empty on a standalone.
9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.
Sequence
- 1
W1
Low inducer → low PS must close. Failure here is E223 / E227 / later E229.
- 2
Trial
HSI (E207 / E290 if the circuit is open) → low-fire valve (E204–E206) → flame (E240 / E270 if no µA).
- 3
W2 / high
High inducer → high PS. E225 if high-fire prove fails. E229 = IFC abandoned low-fire prove and lit on high.
- 4
Limits
E250 = limit string open. Open >3 min or recycle-on-limit becomes E274. E252 = discharge air too high.
- 5
Blower
VS motor talks serial to the IFC. After a board or motor swap, P-menu unit size must match or you get E201 / E202 / E203.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
idle
Decimal blink
Idle / heartbeat. Decimal blinks 1 Hz. Not a fault.
1 Confirm this is not a fault
On the Lennox EL195NE this readout (idle) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the Lennox EL195NE IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: If you expected a code, press E for recall — idle only means nothing is active right now.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch SureLight 7-seg IFC (E2xx) through one cycle and write the first real fault that replaces this status word.
Expect: W1: Low inducer → low PS must close. Failure here is E223 / E227 / later E229.
E
Error recall
Menu: last 10 stored codes.
1 Confirm this is not a fault
On the Lennox EL195NE this readout (E) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the Lennox EL195NE IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: Write them in order before you clear.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch SureLight 7-seg IFC (E2xx) through one cycle and write the first real fault that replaces this status word.
Expect: W1: Low inducer → low PS must close. Failure here is E223 / E227 / later E229.
F
Flame signal
Menu: live flame current in µA on the 7-seg.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL195NE during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Use this on an E240 / E270 call instead of guessing the rod.
Expect: Flame (F menu): µA per EL296 card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Exits on power reset, hold-to-bars, or 10 minutes.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL195NE display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
P
Program unit size
VS only. Stores cabinet / motor capacity in non-volatile memory.
1 Read the plug / card on THIS cabinet
On Lennox EL195NE the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Required after IFC or blower swap. Wrong or blank size → E202 / E203.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Follow the P-menu character for THIS EL296V cabinet, then hold to accept.
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.
Expect: One clean sequence on the correct identity.
E105
RS BUS communication
No other devices on the RS bus, or the bus is too noisy to talk.
1 Data pair, not 24 V
On Lennox EL195NE indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. Only if iComfort is actually wired — i+/i− polarity, one communicating control, indoor/outdoor on the bus.
Expect: Pair continuous, not shorted to chassis, polarity per the diagram.
2 Power both ends, then the outdoor status
Indoor transformer and outdoor control both alive. Read the outdoor LED / 7-seg. Water in the outdoor control is the usual dead-end after a storm. Many EL296V jobs are 24V. E105 on a 24V-only install means data wires landed on the RS terminals. Pull them.
Expect: Both controls powered. Outdoor showing a comm or address state, not a blank board.
3 Address / bias, then the control
Communicating plates need a matching indoor address and sometimes a terminating bias. Swap is last: known-good pair + power both ends + correct address.
Expect: Indoor sees the outdoor. No comm code after a power cycle.
E111
Low line voltage
Line voltage below nameplate. Control waits; resumes ~5 s after voltage recovers.
1 Measure at the IFC under load
On Lennox EL195NE line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. L1 to N at the IFC, not just the disconnect. Brownout, loose lug, undersized circuit.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. Some older EL296UHE cards print E110 as low line and E111 as polarity reversed — confirm THAT door card.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.
Expect: 24 V holds under load. Line stays in window.
E112
Ground not detected
IFC does not see earth ground. Unit shuts down.
1 Hot and neutral at the IFC, not the disconnect
On Lennox EL195NE polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green to cabinet and IFC. Painted screw / missing star washer.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Resumes ~5 s after a real ground is provided.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
E113
High line voltage
Line voltage above nameplate.
1 Measure at the IFC under load
On Lennox EL195NE line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. Measure at the IFC. Boost transformer, generator, or utility high.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. Resumes ~5 s after voltage is in range.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.
Expect: 24 V holds under load. Line stays in window.
E114
Line frequency out of range
No clean 60 Hz. OEM: no 60 Hertz power.
1 Measure at the IFC under load
On Lennox EL195NE line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. Generator / inverter / poorly conditioned backup power is the usual.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. Utility frequency events are rare — confirm you are not on a job-site gen set.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.
Expect: 24 V holds under load. Line stays in window.
E115
Low 24V
Secondary below ~18–30 V class. Control restarts if voltage recovers.
1 Measure at the IFC under load
On Lennox EL195NE line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. 24 VAC at the IFC under load. Extra accessories robbing the transformer.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. Door-switch / shorted valve / undersized VA. Fix the load before you upsize the transformer.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.
Expect: 24 V holds under load. Line stays in window.
E117
Poor ground
Ground is present but dirty. Warning only — clears ~30 s after it recovers.
1 Hot and neutral at the IFC, not the disconnect
On Lennox EL195NE polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Same ground path as E112, just not open. Flame µA and HSI both suffer.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Do not ignore a repeating E117 on an E240 / E270 call.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
E201
Indoor blower communication failure
IFC lost serial talk with the VS indoor blower (including a motor that never powered up).
1 Reseat the serial plug
On Lennox EL195NE this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. Motor harness seated at IFC and module. 120/240 at the motor, not just the IFC.
Expect: Plug fully seated both ends. Correct motor for this cabinet.
2 Power and the data pair at the motor
Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. After a board or motor swap this is usually P-menu / wrong motor — see E202 / E203.
Expect: Line voltage present. Data pair not shorted to chassis.
3 Motor vs IFC serial driver
Known-good motor still throws this code = Lennox EL195NE IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC.
Expect: One clean CFM request after a known-good pair.
E202
Indoor blower HP / unit capacity mismatch
Programmed unit size does not match the motor horsepower the IFC sees.
1 Read the plug / card on THIS cabinet
On Lennox EL195NE the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. P menu: pick the character for THIS cabinet, hold to store, let the IFC reset.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. An EL296E constant-torque motor in this VS cabinet will throw E202 / E310. Use the VS motor.
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.
Expect: One clean sequence on the correct identity.
E203
Appliance capacity not programmed
Unit size code is blank or invalid after a new IFC.
1 Read the plug / card on THIS cabinet
On Lennox EL195NE the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. This is a P-menu job, not a bad motor. Program size, then retest.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Remove the stat from the bus if iComfort is fighting the program cycle.
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.
Expect: One clean sequence on the correct identity.
E204
Gas valve mis-wired
Valve harness does not match what the IFC commanded.
1 Coil ohms and 24 VAC during trial only
On Lennox EL195NE measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Stage 1 / stage 2 leads on the correct valve terminals. Pinched or swapped harness.
Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.
2 Do not energize a leaking valve
If the unexpected-flame code is also in history, shut the cock and replace the valve. Applying 24 V as a ‘test’ and walking away is a gas leak. Clears when the wiring is repaired — do not replace the IFC first.
Expect: No flame with the cock shut and solenoids de-energized.
3 IFC relay vs the valve
Voltage at the harness and a dead coil = valve. No voltage during a known trial = IFC relay or a lockout that never opened the valve (look at the live code).
Expect: Known trial + 24 VAC + good coil = flame. Otherwise IFC.
E205
Gas valve control relay shorted
IFC thinks its valve relay contacts are shorted.
1 Coil ohms and 24 VAC during trial only
On Lennox EL195NE measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Unplug the valve. If E205 stays, the IFC relay is the fault.
Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.
2 Do not energize a leaking valve
If the unexpected-flame code is also in history, shut the cock and replace the valve. Applying 24 V as a ‘test’ and walking away is a gas leak. If it clears, ohm the valve coil and harness for a short to chassis.
Expect: No flame with the cock shut and solenoids de-energized.
3 IFC relay vs the valve
Voltage at the harness and a dead coil = valve. No voltage during a known trial = IFC relay or a lockout that never opened the valve (look at the live code).
Expect: Known trial + 24 VAC + good coil = flame. Otherwise IFC.
E206
Second-stage gas valve relay failure
High-fire solenoid will not drive. OEM: furnace runs first stage only for the rest of the call.
1 Let it cool, then read the drive LED
On Lennox EL195NE overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. W2 present? 24 VAC at stage-2 coil on a high call.
Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.
2 Voltage and compressor windings
Incoming voltage in range (this plate’s line-voltage code). Compressor windings even, no ground. A shorted compressor will kill a new drive. If wiring is good and it never stages, replace the IFC — it is already heating on low.
Expect: Balanced windings. No winding to ground. Line voltage stable under load.
3 Charge and the drive last
A starved or flooded compressor will overcurrent. Confirm SH/SC and charge weight. Only then condemn the inverter.
Expect: Charge on the nameplate. Drive code gone after a cool-down and a clean coil.
E207
HSI sensed open
Hot-surface ignitor circuit measures open.
1 Ohms at the igniter, then at the IFC
On Lennox EL195NE measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Cold ohms at the ignitor, then at the IFC. Replace if open or out of the IOM range.
Expect: HSI: Cold ohms in the IOM range. 120 VAC during trial.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Harness rub-through on the collector is common on these cabinets.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
E223
Low PS failed OPEN
Low-fire pressure switch did not close on the heat call.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL195NE active code. Write E223. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer actually on low? Low-fire hose only, 96% trap, PVC intake/exhaust.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Clean the inducer pressure port — known EL296. Dust packs the port and throws the whole PS family.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E224
Low PS failed CLOSED
Low-fire switch is made when it should be open.
1 Unplug the switch with the inducer off
On Lennox EL195NE this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the low switch. Water in the hose or a welded switch.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Inducer still coasting / hose holding residual draft.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Lennox EL195NE IFC input is shorted. Do not keep swapping switches.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
E225
High PS failed OPEN
IFC commanded high; high-fire switch did not close.
1 Prove the high-fire call
Write the live Lennox EL195NE code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. Does the inducer actually go high?
Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.
If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.
If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’
2 Prove the inducer actually went high
Listen and amp the inducer on low vs high. No speed-up → IFC high output or inducer winding. Speed-up and this code still live → high-fire PS path (hose, switch, vent). High-fire hose not teed to the low switch. Vent capacity on 110/135 kBtu cabinets.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: Measure 120 VAC on the high-speed inducer lead during the high call. 0 V = IFC. Voltage + dead motor = inducer.
3 Isolate the HIGH hose and switch
High-fire hose on the high tap only — a tee with the low switch is the common first-install miss on this dual-switch plate. Blow the hose, confirm it is dry and downhill to the collector. Ohm the high-fire switch: it is NO and must close only on high draft.
Expect: NO switch. Opens with hose off. Closes on high collector draft.
If fail: Welded open, cracked hose, or water in the line. Replace the failed part — do not leave a jumper.
If pass: Switch and hose good → step 4 (vent / condensate / IFC).
4 Vent, condensate, and the IFC input
High fire needs more draft than a low-fire code ever saw. Check PVC size on this cabinet, shared chase, wind, ice, bird screen, and condensate backing into the collector only on high. If the switch closes on known draft and the code stays, the Lennox EL195NE IFC input is the last call.
Expect: Clear vent, dry collector, known-good switch, then IFC.
E226
High PS failed CLOSED
High-fire switch is made when it should be open.
1 Prove the switch is made with inducer not on high
On Lennox EL195NE this code means the high-fire switch is closed when it should be open. Do not treat it as the low-fire stuck-closed code. Write the live display, then unplug the high-fire switch only.
Expect: Code should change when the high-fire harness is open.
If fail: IFC input shorted or you unplugged the wrong switch.
2 Hose water and a welded switch
Water in the high-fire hose holds residual draft and fakes a closed switch. Route downhill to the collector. Ohm the switch with the hose off — a welded high-fire switch stays closed. Unplug the high switch only. Water or a welded disc. W2 shorted so the IFC thinks it should already be in high.
Expect: Hose dry. Switch opens with no draft.
3 Confirm the IFC is not commanding high
W2 shorted to W1, a communicating stat stuck on high, or an IFC that never drops inducer speed will keep this code alive. Measure W2 at the board and watch inducer speed after you open the high-fire harness.
Expect: Inducer on low (or off) with W2 open. High-fire switch ohms open.
E227
Low PS opened during trial or run
Low switch had closed, then opened mid-trial or in run.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL195NE active code. Write E227. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Wind, ice, trap siphon, inducer dropping out after light-off.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Same port-clean as E223 — a half-clogged port will make then drop.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E228
Combustion air inducer calibration failure
IFC could not finish pressure-switch calibration.
1 Is the wheel free?
Spin the Lennox EL195NE blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Vent and both hoses seated. Inducer must be able to sweep both switches.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Fix E223/E225 physics first — calibration will not pass on a clogged port.
Expect: Command present. Motor amps in range, not locked.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
E229
Ignition on high fire
Low-fire switch did not close in time, so the IFC ran the inducer high and lit on high. OEM: no action needed as a separate repair.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL195NE active code. Write E229. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is a low-fire draft problem wearing a high-fire costume. Fix E223 / E227 physics. Do not start on the high-fire manifold screw.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Also fires on high for ~60 s if continuous fan was already on (heat-exchanger warmup) — that one is information only.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E240
Low flame current — run mode
Flame is present but µA is below the run threshold.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL195NE during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. F menu for live µA. Clean the rod — not sandpaper. Neutral-to-ground and E117.
Expect: Flame (F menu): µA per EL296 card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Clears at the end of the heat call. Repeating E240 becomes E270 / E273.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL195NE display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E241
Flame sensed out of sequence — flame still present
Rod sees flame with the valve de-energized. Flame is still there.
1 Shut the gas cock first
On Lennox EL195NE the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. Leaking valve — replace, do not jump.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. If flame dies when you shut the cock, the IFC flame circuit / rod short is next.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
E250
Limit switch circuit open
Primary / rollout / secondary string is open. If it stays open >3 min the IFC goes to a 1-hour soft lockout (E274).
1 Treat this as flame outside the exchanger
Do not reset the Lennox EL195NE rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. VS heat CFM vs the EL296 chart — not a 9-speed tap. Filter, coil, media cabinet. Walk the rollout string if E270 / E274 also store. Manual-reset rollout is a hazard until the cause is gone.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Lennox EL195NE is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
E252
Discharge air too high
Leaving-air temperature above the gas-heat limit (DAT sensor).
1 Airflow before you touch the limit
On Lennox EL195NE a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Rise vs plate. Heat CFM in the IFC, not a guess.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Lennox EL195NE blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Input rate / manifold. Sensor itself only after airflow and fire are right.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold on plate. Limit closed when cool.
E270
Soft lockout — max retries, no flame current
Tried to light, never saw flame current. Soft lockout. Clears on a successful heat call.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL195NE during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Watch a try: inducer, HSI glow, valve click, flame, then F-menu µA. Which step dies?
Expect: Flame (F menu): µA per EL296 card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. This is ignition, not rollout. The older field rumor that E270 ‘is rollout’ is wrong on this SureLight family — rollout lives in the E250 / E274 string.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL195NE display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E271
Soft lockout — last retry failed because PS opened
Retries used up; the last try died when a pressure switch opened.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL195NE active code. Write E271. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Treat as a hardened E223 / E227. Port, trap, PVC, inducer.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Do not replace the ignitor because the stack says 270-family.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E272
Soft lockout — last recycle PS opened
Recycles used up; last recycle failed because a pressure switch opened.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL195NE active code. Write E272. Is the inducer spinning on this call? Silent inducer is not a pressure switch. It ran, then draft dropped. Wind, ice, trap siphon, inducer after light-off.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Same two-hose / port-clean as the E223 cluster.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E273
Soft lockout — last recycle flame failure
Recycles used up; last recycle lost flame signal.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL195NE during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. F-menu µA, rod, ground, manifold after blower-on. Flame that dies when the wheel starts is often draft or a weak rod.
Expect: Flame (F menu): µA per EL296 card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Pairs with E240.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL195NE display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E274
Soft lockout — last recycle limit open or limit >3 min
Recycles used up because the limit string opened, or a limit stayed open longer than 3 minutes.
1 Airflow before you touch the limit
On Lennox EL195NE a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Hardened E250. VS CFM, media cabinet, rise.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Lennox EL195NE blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. If a rollout is open in that string, stop and inspect the exchanger before you up the CFM.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold on plate. Limit closed when cool.
E275
Flame out of sequence lockout
Soft lockout after out-of-sequence flame. Same hazard family as E241.
1 Shut the gas cock first
On Lennox EL195NE the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Valve leak or IFC flame circuit.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. 1-hour-class lockout. Do not keep resetting.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
E290
Ignitor circuit fault
Failed ignitor or triggering circuitry. 1-hour soft lockout until flame proves stable.
1 Ohms at the igniter, then at the IFC
On Lennox EL195NE measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms the HSI. Open / out of IOM range = replace the ignitor.
Expect: HSI: Cold ohms in the IOM range. 120 VAC during trial.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Good ohms + no 120 VAC during trial = IFC / harness.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
E292
Heat airflow restricted below minimum
VS heat CFM is below the minimum the IFC will allow for this firing rate.
1 Is the wheel free?
Spin the Lennox EL195NE blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Filter, coil, wheel, return. Media cabinets on Elite jobs are the usual.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Some communicating SureLight cards print a different sentence next to E292 — confirm THAT door card before you condemn a motor.
Expect: Command present. Motor amps in range, not locked.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
E310
Blower unable to start
Indoor blower did not start — seized bearings / obstructed wheel class.
1 Is the wheel free?
Spin the Lennox EL195NE blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Spin the wheel. Ice, debris, rusted module, unplugged harness.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Door-card note: a few revisions park a DAT-sensor sentence on E310. If the card says sensor, treat it as a sensor. If it says wheel/bearings, treat it as a motor.
Expect: Command present. Motor amps in range, not locked.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
E311
Blower temperature too high
Blower / module overtemp. IFC sheds or parks heat.
1 Airflow before you touch the limit
On Lennox EL195NE a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Static, wheel rub, module fins packed with dust.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Lennox EL195NE blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. After a motor swap, confirm you did not put an EL296E CT motor in this VS plug.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold on plate. Limit closed when cool.
E312
Restricted airflow — cooling / CF
Cooling or continuous-fan CFM is below the setting. Cutback / high-static warning.
1 Airflow before you touch the limit
On Lennox EL195NE a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter and duct. VS motor is already in torque limit (roughly 0–0.8 in. w.c. class).
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Lennox EL195NE blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Not a heat-call code. Do not chase E312 with a pressure switch.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold on plate. Limit closed when cool.
Workflows
EL195NE no light
CA / NV Elite.
1 Prove the call and the live code
ULN / NV plate. Standard Elite LP kit is the wrong carton.
Expect: Write whatever SureLight 7-seg IFC (E2xx) is showing. Hold the IFC button to a solid E. Last 10 codes, most recent first. Select c and press again while c flashes to erase. Exit at the triple-bar. 7-seg also repeats the active fault.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Draft is still 96% trap / PVC if this cabinet is condensing. Confirm vent.
Expect: Trial: HSI (E207 / E290 if the circuit is open) → low-fire valve (E204–E206) → flame (E240 / E270 if no µA).
3 Confirm with a number, then the next part
Do not drill the premix burner.
Expect: E-code: Three digits. E229 ≠ E225. Confirm odd extras on the door card. · Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
E-code
Three digits. E229 ≠ E225. Confirm odd extras on the door card.
Inducer port
Open to the collector, not packed with oxide. Two hoses, never teed.
Flame (F menu)
µA per EL296 card. Rising while running.
HSI
Cold ohms in the IOM range. 120 VAC during trial.
P menu
Unit size stored for this VS cabinet after any IFC or motor swap.
Gotchas
- SL297NV is the Signature communicating ULN. Different board, same burner idea.
Related plates
Install this plate
Install Lennox EL195NE as Elite · ultra-low emission · CA / NV.
Elite · ultra-low emission · CA / NV
This plate — not the sister SKU
- Not EL196E standard Elite. Not SL297NV Signature ULN. Not ML196.
- SL297NV is the Signature communicating ULN. Different board, same burner idea.
IFC on this door
- Idle is a decimal blink at 1 Hz (0.5 s on / 0.5 s off). That is not a fault.
- Faults are E plus three digits. Write the full number. E225 ≠ E223 ≠ E229.
- Pushbutton menu: E = recall last 10 (c twice to clear). F = flame µA. P = program unit size (VS only).
- This chart is the 107045-XX / 103130-XX SureLight family used on EL296V. Confirm any odd extra code on THAT door card before you order a part.
- E105-style RS-bus codes appear only if iComfort is wired. Many EL296V jobs are 24V.
Hardware
- NOx: First-in-class ultra-low emission burner (Lennox NV / NE plates)
- AFUE: 95–96% class condensing (confirm THIS plate)
First fire
- 1ULN / NV plate. Standard Elite LP kit is the wrong carton.
- 2Draft is still 96% trap / PVC if this cabinet is condensing. Confirm vent.
- 3Do not drill the premix burner.
Do not on Lennox EL195NE
- Not EL196E standard Elite. Not SL297NV Signature ULN. Not ML196.
- SL297NV is the Signature communicating ULN. Different board, same burner idea.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Lennox residential furnacesLiterature searchEL296V / ML196E / SLP99V / SL280V listing. Wiring and I/O: LennoxPros.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
warranty sheetLennox furnace warranty
Registered EL / ML / SL / SLP furnace warranty · Dealer claims portal
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal