Models
Lennoxfurnace

SL297NV

Signature · ultra-low emission · VS · communicating

Lennox Signature SL297NV variable-speed ultra-low emission. iComfort bus. Premix burner. Not SLP99V modulating and not EL296V 24V Elite.

Not SLP99V modulating iComfort. Not EL296V. Not EL195NE Elite ULN.

NOx

Signature ultra-low emission VS

Bus

iComfort communicating

This board

iComfort IFC

  • Stat event list is primary. It names the E-code in English. Write the E-number anyway.
  • E105 = RS bus. Native here — not the ‘someone landed data wires’ story from EL296V.
  • E2xx pressure / limit / flame codes still mean the same physics as the EL296 SureLight table. The stat just names them.
  • Capacity on the display is a percent, not stage 1 / stage 2. Do not land a non-communicating stat on i+/i−.

iComfort dealer control / last faults. Board E-menu if the stat is dead.

Universal swap

No universal

iComfort ULN. No universal.

White-Rodgers

ICM

Honeywell

  • Any 50A55-843 / 50A65-843 / 50M56U-843 / 50M56X-843 / S9200U1000 universal — those are conventional 24V HSI, not this data bus.
  • ICM280 / 2811 / 2810 / 282B — wrong IFC family.
  • EL296V SureLight. SLP99V modulating card.

After you pull the dead card

  1. 1OEM Signature ULN IFC. Pair iComfort.

Field wiring

Written landings for Lennox SL297NV. Not a factory schematic.

iComfort furnace
I+ / I−Gas furnace

SLP99V / SL297NV / EL296V communicating. iComfort S30/S40 on I+ and I−. Many EL296V jobs are still 24V — use that landing if RS wires are empty.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC120V
  2. 2Call. Data pair or 24V W → IFCBus or 24V
  3. 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
  4. 4Ignite. IFC → HSI → valve120V igniter
  5. 5Blow. IFC → serial ECMNo tap, no cap

This indoor

Signature ULN VS. I+/I−.

iComfort communicating

S30/S40 and a communicating outdoor, or communicating indoor-only.

iComfort S30 / S40

R, C, I+, I−.

  • R24V hot24V
  • CCommon24V
  • I+DataData
  • I−DataData

iComfort IFC

E105 on a 24V-only job means data wires landed on RS terminals. Pull them.

  • I+DataData
  • I−DataData
  • R24V24V
  • CCommon24V
  • W124V heat if used24V

Landing

  • DataStat I+/I−IFC I+/I−outdoor

    iComfort data

  • 24VR and C at the stat

    ~24 VAC

EL296V as 24V

No iComfort outdoor. Conventional W1/W2/Y. Leave I+ / I− empty.

Two-stage 24V stat

Normal W1/W2/Y/G. RS / I+ unused.

  • RHot24V
  • CCommon24V
  • W1Low fire24V
  • W2High fire24V
  • YCool24V
  • GFan24V

Landing

  • 24VStat W1/W2IFC W1/W2

    Two-stage heat

  • 24VStat YIFC Youtdoor Y

    Cool

IFC harness — communicating two-stage

Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.

Transformer + fuse

24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.

  • L1 / N120VLine
  • R / C24V strip24V
  • FUSEOn the IFC24V

24V safety chain

Limit / rollout / door still open the heat path. Codes are on THIS IFC language.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + dual PS

Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.

  • IND LO/HITwo-speed inducerLine
  • LPSLow prove24V
  • HPSHigh prove24V

HSI + two-stage valve

Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.

  • HSI120V igniterLine
  • MV / HV24V low / high solenoids24V
  • FLAMEµA DC24V

Serial variable-speed ECM

IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.

  • SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
  • CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V

Landing

  • LineCallIFCinducerprove

    Low then high

  • LineIFCHSIvalve

    120V igniter, 24V or serial valve

  • 24VFlame rodIFC

    µA DC

  • DataIFCserial blower

    No F-taps. No PSC cap.

Prove it

  • If the stat is S30, I+/I− must be landed and the furnace must be on the equipment list.
  • E105 with a 24V stat = data wires on the RS terminals.

Do not

  • Do not land Y on I+.
  • ML196 / EL196E / EL296E are 24V unless the silk actually has iComfort.

I+ / I− are the published iComfort terminals.

Sequence

  1. 1

    Call

    Stat requests %. Valve and inducer modulate. Blower CFM follows. There is no W1/W2 prove pair like EL296V.

  2. 2

    Prove

    Inducer must hit the pressure band for that firing rate. E223-family on the stat is a band miss, not ‘swap the low PS and leave.’

  3. 3

    Ignition

    Still HSI + flame rod. E207 / E240 / E270 still mean ignitor / µA / retries.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

E105

RS communication

lockout

Device off the iComfort bus. Native, expected, first-class on SLP99.

  1. 1 Data pair, not 24 V

    On Lennox SL297NV indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. i+/i− polarity, one communicating control, indoor and outdoor on the bus. Data, not 24 VAC.

    Expect: Pair continuous, not shorted to chassis, polarity per the diagram.

  2. 2 Power both ends, then the outdoor status

    Indoor transformer and outdoor control both alive. Read the outdoor LED / 7-seg. Water in the outdoor control is the usual dead-end after a storm. Do not convert to 24V. Isolating devices one at a time finds the bad node.

    Expect: Both controls powered. Outdoor showing a comm or address state, not a blank board.

  3. 3 Address / bias, then the control

    Communicating plates need a matching indoor address and sometimes a terminating bias. Swap is last: known-good pair + power both ends + correct address.

    Expect: Indoor sees the outdoor. No comm code after a power cycle.

E201

Indoor blower communication

lockout

Serial blower dropped off the IFC.

  1. 1 Reseat the serial plug

    On Lennox SL297NV this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. Harness, motor power, then motor. This is a communicating VS — same family as EL296V E201, native here.

    Expect: Plug fully seated both ends. Correct motor for this cabinet.

  2. 2 Power and the data pair at the motor

    Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor.

    Expect: Line voltage present. Data pair not shorted to chassis.

  3. 3 Motor vs IFC serial driver

    Known-good motor still throws this code = Lennox SL297NV IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC.

    Expect: One clean CFM request after a known-good pair.

E223 / E225

Pressure / inducer band

lockout

Modulating prove failed at that rate. Stat may say low/high PS even though the hardware is a band, not two EL296 discs.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Lennox SL297NV active code. Write E223 / E225. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Vent, trap, inducer, hose. 96% PVC physics.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Do not treat it as a two-stage W1/W2 swap.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

E240 / E270

Flame current / retry lockout

lockout

Weak µA or max retries with no flame current.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Lennox SL297NV during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Watch a try. Rod, HSI, gas. Same SureLight ignition as EL296V.

    Expect: Flame: µA per SLP99 card — same F-menu idea if the board exposes it.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold on the rating plate. Solid burner-box ground.

  3. 3 Prove it is not a switch opening

    Watch the live Lennox SL297NV display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

E250

Limit switch circuit open

warn

Limit / rollout string. Stat names it in English.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Lennox SL297NV rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Heat CFM follows %. Filter, coil, rise. Rollout is still manual reset.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Lennox SL297NV is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

E207 / E290

HSI / ignitor circuit

lockout

Ignitor open or trigger fault.

  1. 1 Ohms at the igniter, then at the IFC

    On Lennox SL297NV measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms and 120 VAC during trial. Confirm on the SLP99 door card.

    Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

Workflows

SL297NV vs SLP99V

Signature communicating.

  1. 1 Prove the call and the live code

    SLP99V = modulating percent. SL297NV = two-stage / VS ULN.

    Expect: Write whatever iComfort IFC is showing. iComfort dealer control / last faults. Board E-menu if the stat is dead.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    iComfort pair first. Then the ULN gas train — not an EL296 orifice.

    Expect: Prove: Inducer must hit the pressure band for that firing rate. E223-family on the stat is a band miss, not ‘swap the low PS and leave.’

  3. 3 Confirm with a number, then the next part

    iComfort pair first. Then the ULN gas train — not an EL296 orifice.

    Expect: i+ / i−: Data, not 24 VAC. One communicating control. · Capacity: Percent on the stat / IFC. Not W1/W2.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

i+ / i−

Data, not 24 VAC. One communicating control.

Capacity

Percent on the stat / IFC. Not W1/W2.

Flame

µA per SLP99 card — same F-menu idea if the board exposes it.

Gotchas

  • SL280NV is the 80% Signature ULN cousin — metal vent if the plate says 80%.

Related plates

Install this plate

Install Lennox SL297NV as Signature · ultra-low emission · VS · communicating.

Signature · ultra-low emission · VS · communicating

This plate — not the sister SKU

  • Not SLP99V modulating iComfort. Not EL296V. Not EL195NE Elite ULN.
  • SL280NV is the 80% Signature ULN cousin — metal vent if the plate says 80%.

IFC on this door

  • Stat event list is primary. It names the E-code in English. Write the E-number anyway.
  • E105 = RS bus. Native here — not the ‘someone landed data wires’ story from EL296V.
  • E2xx pressure / limit / flame codes still mean the same physics as the EL296 SureLight table. The stat just names them.
  • Capacity on the display is a percent, not stage 1 / stage 2. Do not land a non-communicating stat on i+/i−.

Hardware

  • NOx: Signature ultra-low emission VS
  • Bus: iComfort communicating

First fire

  1. 1SLP99V = modulating percent. SL297NV = two-stage / VS ULN.
  2. 2iComfort pair first. Then the ULN gas train — not an EL296 orifice.

Do not on Lennox SL297NV

  • Not SLP99V modulating iComfort. Not EL296V. Not EL195NE Elite ULN.
  • SL280NV is the 80% Signature ULN cousin — metal vent if the plate says 80%.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • Lennox residential furnacesLiterature searchEL296V / ML196E / SLP99V / SL280V listing. Wiring and I/O: LennoxPros.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    warranty sheet

    Lennox furnace warranty

    Registered EL / ML / SL / SLP furnace warranty · Dealer claims portal

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal