Electrical · 14 min
Enable 24V, then 0–10 V, then the drive code. OC is static or a seized wheel. Do not jumper fan-prove. Do not throw a dual cap at a VFD motor.
VFD DC bus holds a charge after disconnect. Wait the drive’s posted time before you open it.
Lock the roof disconnect. 3-phase at the drive is line voltage.
Do not megger a motor with the VFD still connected — you will take out the output transistors.
Do not jumper fan-prove. Heat will fire into a near-dead blower.
Tools: True RMS meter (VAC and VDC) · Manometer for total external static · The drive keypad in this cabinet (EcoBlue / Reliatel / Yaskawa / ABB / aftermarket) · Megohmmeter if the drive shows ground fault
OC, LU, OU, GF, OH, or a unit-board fan alarm (Reliatel fan fail, EcoBlue fan). Power-cycle wipes it. Confirm L1/L2/L3 at the drive under load.
Expect: Live code written. Three legs present if this drive is 3-phase.
If not: No display and no line = disconnect / fuses, not a motor.
24 VAC (or this drive’s digital enable) while G / occupied / a heat or cool call is on. Then 0–10 VDC at the analog pair under a high-fan call. 0 V enable is the unit board. 0 V analog with enable is a wire or a dead analog output.
Expect: Enable present. Analog not stuck at 0. Occupied cool is often not 10 V — use this fan table.
If not: Fix the board / harness before you change a drive.
Power off, spin the wheel. TES vs this blower table. FLA / motor-data on the drive vs the motor nameplate. A rooftop at 1.4" with a 0.8" motor is OC waiting to happen. Do not raise FLA to hide a dirty coil.
Expect: Wheel free. Static legal. FLA matches the motor plate.
If not: Clean filters/coil and fix duct static before you condemn the drive.
Some Reliatel / VFD cabinets drop into limp (~min Hz). That CFM will not close a 0.07" prove switch, and the board reports fan fail. Clean first, then min-frequency. Never leave a jumper on prove.
Expect: Prove switch closes at a real occupied CFM.
If not: Load the rooftop plate in Diagnose — YSC fan-fail is not a 48FC EcoBlue menu.
Disconnect U/V/W from the drive. Megger the motor. Wet rooftop motors after rain and cables rubbed through the curb are this code. Reset-and-run a GF and you buy a drive.
Expect: Insulation in spec. Cable undamaged.
If not: Replace the motor or the cable. Do not keep resetting GF.