Models
Amanafurnace

AR9T80

Two-stage · 9-speed ECM · 80% Cat I

Amana two-stage 80% 9-speed. Twin of Goodman GR9T80. E1/E2 vs E8/E9 on a metal vent. Not AR9T96 (96% PVC) and not AR9S80 (single-stage one PS, 0140F20001-B).

Not AR9T96 / AD9T96 (96% two-stage 9-speed). Not AR9S80 (single-stage 80% 9-speed). Not ARVT80 (ComfortBridge).

AFUE

80% two-stage · Cat I metal

Sister SKU

AD9T80 downflow · Goodman GR9T80

This board

Self-diagnostic IFC · single 7-segment (read Seg3→Seg2→Seg1 left to right)

  • Codes sit on the IFC in the blower compartment. door card is wiring 0140F20004-B. Do not kill power — that clears the active code.
  • Read left to right (Seg3→Seg2→Seg1). Idle / no fault is a quiet or dashed display; faults prefix E, EE, L, U, F, S, r.
  • E1/E2 are the LOW-FIRE pressure switch. E8/E9 are the HIGH-FIRE pressure switch. AR9S96 has only one PS and no E8/E9 — leave that page.
  • A2L pair codes (FE3, LE4, SE5, rE6) only apply when this furnace is tied to an R-32 / A2L outdoor. Ignore them on R-410A pairs.

In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.

Universal swap

Read the silk

Amana two-stage 80% 9-speed. PCBBF132 → 50M56-743 if that is the silk.

Silk: PCBBF132 · PCBBF132S

White-Rodgers

ICM

Honeywell

  • 50A55-843. AR9T96 96% door assumed without reading silk.

After you pull the dead card

  1. 1Kill power. Photograph the silk-screen part number on the dead board before you pull it.
  2. 2Match staging (1 vs 2 vs modulating), igniter (carbide / nitride / spark), and motor (PSC / ECMx / 9-speed tap / serial VS).
  3. 3Set heat-off delay and any 80+/90+ jumper to the door card. Prove one full try and flame µA before you leave.

Field wiring

Written landings for Amana AR9T80. Not a factory schematic.

Furnace · two-stage 24V
R / C / W1 / W2 / Y / GGas furnace

Two-stage conventional furnace. W1 low fire, W2 high fire. Outdoor staging is Y or Y1/Y2 — separate from the gas valve.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → R120V / 24V
  2. 2Low. W1 → inducer LOW → LPS → HSI → valve LOWFirst fire
  3. 3High. W2 → inducer HIGH → HPS → valve HIGHSecond solenoid
  4. 4Flame. Rod → IFCµA DC both stages
  5. 5Blow. IFC → heat blowerAfter flame

This indoor

80% two-stage 9-speed. Same W1/W2. Metal vent.

24V two-stage heat

Door has W1 and W2. Not Infinity. Not ComfortBridge.

Two-stage thermostat

A single-W stat never proves high fire. That is not a weak inducer.

  • R24V hot24V
  • CCommon24V
  • W1Low-fire heat24V
  • W2High-fire heat24V
  • Y / Y1Cool24V
  • Y2Outdoor high if the condenser is two-stage24V
  • GFan24V

Two-stage IFC

W2 is high fire. Do not tee the pressure-switch hoses because there are two stages.

  • RHot24V
  • CCommon to outdoor24V
  • W1Low fire24V
  • W2High fire24V
  • YCool out24V
  • GBlower / cool tap24V

Landing

  • 24VStat W1IFC W1

    Low fire

  • 24VStat W2IFC W2

    High fire. Missing W2 = stuck on low.

  • 24VStat YIFC Youtdoor Y

    Cool

  • 24VC throughout

    Common

IFC harness — two-stage heat

W1 then W2. Low-fire prove is not high-fire prove.

Transformer + fuse

Same 24V transformer as single-stage. Fuse still kills the whole strip.

  • L1 / N120VLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout. A limit trip is not an E9 / 32 pressure-switch story.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + two pressure switches

W1 = inducer low + LPS. W2 = inducer high + HPS. Separate hoses. Do not tee.

  • IND LO120V low-speed inducerLine
  • IND HI120V high-speed inducerLine
  • LPSLow-fire prove24V
  • HPSHigh-fire prove24V
  • HOSESOne hose per switch. Never tee LPS and HPS24V

HSI + two-stage valve

Igniter 120V. Low solenoid on W1. Second solenoid on W2 after HPS closes.

  • HSI120V igniterLine
  • MV / LO24V low-fire solenoid24V
  • HV / HI24V high-fire solenoid24V
  • FLAMEµA DC on the rod24V

9-speed tap ECM

F01–F09 on the harness. Heat tap and cool tap are separate. Not a 14-pin serial motor and not a run cap.

  • F01–F09Speed taps on the IFC / harness24V
  • HEATDefault often F02 — F01 is an E3 generator on many 9-speed doors24V
  • COOL / Y / GCool tap. Wrong tap freezes the coil and looks like LPS outdoors.24V

Landing

  • LineW1IFCinducer LOWLPS

    120V inducer, 24V prove

  • LineIFCHSIvalve LOW

    120V igniter, 24V low solenoid

  • 24VW2inducer HIGHHPSvalve HIGH

    Missing W2 = stuck on low

  • 24VFlame rodIFC

    µA DC

  • LineIFCheat blower

    After flame. Motor class on this plate.

Prove it

  • W1 then W2 at the IFC under a 2-heat call.
  • If it never stages, W2 is missing at the board — not a bad gas valve until that is proven.

Do not

  • Do not convert this to Infinity by landing W on a random terminal.
  • Do not apply AMVC / ARVT ComfortBridge menus or a memory card.

926T / 59TP6 / AR9T96 / GR9T96 / S9V2 / EL296E class. Same landing on 80% metal-vent cousins — the vent is not the wire.

Sequence

  1. 1

    W1

    IFC proves limits/rollout closed, starts inducer on low speed.

  2. 2

    Prove low PS

    Low-fire pressure switch must close. If it is already closed with inducer off → E1. If it never closes → E2.

  3. 3

    HSI warm

    Silicon nitride igniter ~17–27 s (OEM). Open igniter → En / E7.

  4. 4

    Low-fire valve

    First-stage solenoid opens. Flame must prove at the rod. Failures stack toward E0 lockout.

  5. 5

    Blower delay

    Heat-on delay, then ECM on the selected heat tap (not a communicating CFM request).

  6. 6

    W2 / high fire

    Inducer goes high. High-fire PS must close (E9 if open, E8 if it was already closed). Second-stage solenoid opens.

  7. 7

    Satisfied

    Valve off, inducer post-purge, blower heat-off delay. Unexpected flame after valve-off → E4.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

E0

Retry / recycle lockout

lockout

Too many failed ignition attempts or flame losses on this call.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Amana AR9T80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Watch one full try: inducer, HSI glow, valve click, flame, µA.

    Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Gas supply and manifold (low then high).

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

  3. 3 Prove it is not a switch opening

    Watch the live Amana AR9T80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Ground and flame-rod cleanliness.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

E1

Low-fire PS stuck closed

lockout

Low-stage pressure switch is made with the inducer off.

  1. 1 Unplug the switch with the inducer off

    On Amana AR9T80 this code is the switch made when the inducer is not running. Unplug that switch only. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: Code changes when the harness is open.

    If fail: Wrong switch, or the IFC input is shorted.

    If pass: Switch/hose path. Go to step 2.

  2. 2 Water in the hose vs a welded switch

    Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Hose empty. Switch opens with no draft.

  3. 3 IFC input last

    If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Amana AR9T80 IFC input is shorted. Do not keep swapping switches. Unplug the LPS. If code changes, switch is welded or hose is holding residual draft.

    Expect: Known-good open switch + open harness = code gone. If not, IFC.

E2

Low-fire PS open

lockout

Inducer is on low and the low-fire switch will not close.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Amana AR9T80 active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Inducer spinning? 120 VAC at inducer on a W1 call.

    Expect: LPS / HPS: Both NO. Closed only when that inducer speed is making the collector setpoint. Two hoses — never tee.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

E3

Open high limit

warn

Primary limit opened. Airflow or overfire — not a charge problem.

  1. 1 Airflow before you touch the limit

    On Amana AR9T80 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, blower wheel, A-coil, heat-speed tap (9-speed: wrong tap is the #1 callback).

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Amana AR9T80 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Static vs blower chart for this cabinet size.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Manifold pressure on low and high vs rating plate.

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

E4

Flame when valve should be off

hazard

Rod sees flame with both solenoids de-energized.

  1. 1 Shut the gas cock first

    On Amana AR9T80 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground or IFC flame circuit.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

E5

Open fuse

warn

3 A (typical) automotive fuse on the IFC is open.

  1. 1 Find the 24 V short before you replace the fuse

    On Amana AR9T80 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. 24 V short on W, Y, G, humidifier, or EAC.

    Expect: Fuse out. 24 V transformer still good. Harness isolated.

  2. 2 Replace the fuse with the harness off

    New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC). Unplug tstat harness and replace fuse. If it blows again the short is on the board or gas valve harness.

    Expect: Fuse holds with harness off. Dies when the shorted lead lands.

  3. 3 If it blows with the harness off

    Short is on the Amana AR9T80 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.

    Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.

E6

Low flame signal

warn

Flame is present but µA is below the IFC threshold.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Amana AR9T80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod with a non-scratch pad — not sandpaper.

    Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Chassis ground to burner box and IFC.

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

  3. 3 Prove it is not a switch opening

    Watch the live Amana AR9T80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Manifold pressure / orifice / LP conversion.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

E7

Igniter relay fault

lockout

IFC did not see the igniter circuit behave as commanded.

  1. 1 Ohms at the igniter, then at the IFC

    On Amana AR9T80 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Igniter ohms cold (OEM — typically 30–115 Ω class, confirm sticker).

    Expect: HSI: Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use a 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. 120 VAC to igniter during warm-up.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter. Cracked nitride element.

    Expect: One clean light after a known-good igniter and a proven ground.

E8

High-fire PS stuck closed

lockout

High-stage pressure switch is made with the inducer not on high.

  1. 1 Prove the switch is made with inducer not on high

    On Amana AR9T80 this code means the high-fire switch is closed when it should be open. Do not treat it as the low-fire stuck-closed code. Write the live display, then unplug the high-fire switch only.

    Expect: Code should change when the high-fire harness is open.

    If fail: IFC input shorted or you unplugged the wrong switch.

  2. 2 Hose water and a welded switch

    Water in the high-fire hose holds residual draft and fakes a closed switch. Route downhill to the collector. Ohm the switch with the hose off — a welded high-fire switch stays closed. This is Category I metal vent. There is no 96% collector or PVC trap to prime. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Hose dry. Switch opens with no draft.

  3. 3 Confirm the IFC is not commanding high

    W2 shorted to W1, a communicating stat stuck on high, or an IFC that never drops inducer speed will keep this code alive. Measure W2 at the board and watch inducer speed after you open the high-fire harness. This is the second switch — do not confuse with E1.

    Expect: Inducer on low (or off) with W2 open. High-fire switch ohms open.

E9

High-fire PS open

lockout

Inducer on high, high-fire switch never closes. Classic ‘runs on low, will not go high.’

  1. 1 Prove the high-fire call

    Write the live Amana AR9T80 code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.

    If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.

    If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’

  2. 2 Prove the inducer actually went high

    Listen and amp the inducer on low vs high. No speed-up → IFC high output or inducer winding. Speed-up and this code still live → high-fire PS path (hose, switch, vent). Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: LPS / HPS: Both NO. Closed only when that inducer speed is making the collector setpoint. Two hoses — never tee.

    If fail: Measure 120 VAC on the high-speed inducer lead during the high call. 0 V = IFC. Voltage + dead motor = inducer.

  3. 3 Isolate the HIGH hose and switch

    High-fire hose on the high tap only — a tee with the low switch is the common first-install miss on this dual-switch plate. Blow the hose, confirm it is dry and downhill to the collector. Ohm the high-fire switch: it is NO and must close only on high draft. Inducer actually changes speed on W2? Listen / amp it.

    Expect: LPS / HPS: Both NO. Closed only when that inducer speed is making the collector setpoint. Two hoses — never tee.

    If fail: Welded open, cracked hose, or water in the line. Replace the failed part — do not leave a jumper.

    If pass: Switch and hose good → step 4 (vent / condensate / IFC).

  4. 4 Vent, condensate, and the IFC input

    High fire needs more draft than a low-fire code ever saw. Check PVC size on this cabinet, shared chase, wind, ice, bird screen, and condensate backing into the collector only on high. If the switch closes on known draft and the code stays, the Amana AR9T80 IFC input is the last call.

    Expect: Clear vent, dry collector, known-good switch, then IFC.

EA

Line polarity / ground

lockout

L1/N reversed or chassis ground missing. HSI and flame sense both suffer.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Amana AR9T80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Hot and neutral at the IFC, not just the disconnect.

    Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Burner box to IFC ground screw.

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

  3. 3 Prove it is not a switch opening

    Watch the live Amana AR9T80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Twinned jobs — follow the twinning kit, then look at EEJ.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

Eb / Ec

Gas valve circuit

lockout

Internal (Eb) or external (Ec) gas-valve electrical fault.

  1. 1 Coil ohms and 24 VAC during trial only

    On Amana AR9T80 measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Valve coil ohms, 24 VAC at the harness during trial.

    Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.

  2. 2 Do not energize a leaking valve

    If the unexpected-flame code is also in history, shut the cock and replace the valve. Applying 24 V as a ‘test’ and walking away is a gas leak. Do not apply 24 V to a leaking valve as a ‘test’ and walk away.

    Expect: No flame with the cock shut and solenoids de-energized.

  3. 3 IFC relay vs the valve

    Voltage at the harness and a dead coil = valve. No voltage during a known trial = IFC relay or a lockout that never opened the valve (look at the live code).

    Expect: Known trial + 24 VAC + good coil = flame. Otherwise IFC.

Ed

Open rollout

hazard

Manual-reset rollout opened. Treat as flame outside the exchanger until proven otherwise. Door chart may render this as a distinctive 7-seg character — confirm on the unit sticker.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Amana AR9T80 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Primary exchanger cracks, burner alignment, crossover. Blocked secondary / condensate / flue.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Amana AR9T80 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Reset only after the cause is fixed. Recurring rollout is a CO / fire call.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

En

Igniter open

lockout

Igniter circuit measures open.

  1. 1 Ohms at the igniter, then at the IFC

    On Amana AR9T80 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the igniter plug, then at the IFC.

    Expect: HSI: Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use a 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Harness rub-through on the collector.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

EEH

Grounding error

lockout

IFC failed its ground check (sister to EA).

  1. 1 Hot and neutral at the IFC, not the disconnect

    On Amana AR9T80 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green ground to cabinet and IFC.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Painted screw, missing star washer.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

EEJ

Twin error

lockout

Twinning miswire or twin terminal active on a standalone unit.

  1. 1 Is this cabinet actually twinned?

    On a standalone Amana AR9T80, nothing belongs on the TWIN terminal. A leftover jumper throws this. If not twinned, nothing should be on the TWIN terminal.

    Expect: TWIN empty on a single cabinet.

  2. 2 Twinned pair must be the same IFC family

    Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin. Twinned pair must be same family / same IFC revision.

    Expect: Same model family, same IFC, kit installed per the twinning sheet.

  3. 3 Phasing and 24 V

    Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.

    Expect: In-phase 24 V. Continuous twin lead.

LE1 / UE2

Circulator current

lockout

ECM current too low (LE1) or unexpected (UE2).

  1. 1 Is the wheel free?

    Spin the Amana AR9T80 blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: ECM taps: Factory defaults from SS p.8: fan F03, Y1/Y F04, Y2 F05, heat low F01, heat high F02. Rise is cabinet-specific (15–45 on 0303AN through 35–65 on 80–120 kBtu).

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call. Harness seated at motor and IFC. 9-speed ECM is tap-driven — a half-seated plug throws these.

    Expect: Static on the blower chart. Matching motor / shared-data card.

FE3 / LE4 / SE5 / rE6

A2L mitigation

hazard

Leak / comm / relay alarm from the A2L board when paired with R-32 or R-454B outdoor.

  1. 1 Confirm this pair is actually A2L

    On Amana AR9T80 FE3 / LE4 / SE5 / rE6-class codes are only valid when this furnace is tied to an R-32 or R-454B outdoor. On R-410A this is a miswired mitigation harness — not a leaking indoor coil.

    Expect: Outdoor refrigerant from the outdoor nameplate, not from memory.

    If fail: Remove / correct the mitigation harness. Do not condemn the IFC.

  2. 2 Sensor location and the mitigation blower

    If it is a real A2L pair, follow the OEM mitigation sequence: sensor location, ventilation blower, relay. This is Category I metal vent. There is no 96% collector or PVC trap to prime. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Sensor seated where the I/O shows. Mitigation blower runs on a test.

  3. 3 Do not bypass mitigation

    Never jump an A2L alarm to get heat. Find the leak or the failed sensor. Recurring mitigation with a clean sensor is a refrigerant leak until proven otherwise.

    Expect: Alarm clears only after the leak/sensor is fixed.

Workflows

AR9T80 vs AR9T96 vs AR9S80

Amana 9-speed 80/96 mix-up.

  1. 1 Prove the call and the live code

    Two hoses + PVC = AR9T96. Two hoses + metal vent = AR9T80. One hose + metal = AR9S80.

    Expect: Write whatever Self-diagnostic IFC · single 7-segment (read Seg3→Seg2→Seg1 left to right) is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Door 0140F20004-B is the 96% two-stage card. Do not hang it in this 80% cabinet.

    Expect: Prove low PS: Low-fire pressure switch must close. If it is already closed with inducer off → E1. If it never closes → E2.

  3. 3 Confirm with a number, then the next part

    Door 0140F20004-B is the 96% two-stage card. Do not hang it in this 80% cabinet.

    Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal. · Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Flame rod

Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.

Manifold low / high

Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

LPS / HPS

Both NO. Closed only when that inducer speed is making the collector setpoint. Two hoses — never tee.

HSI

Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use a 80% Norton chart.

ECM taps

Factory defaults from SS p.8: fan F03, Y1/Y F04, Y2 F05, heat low F01, heat high F02. Rise is cabinet-specific (15–45 on 0303AN through 35–65 on 80–120 kBtu).

Gotchas

  • AR9S80 is the single-stage 80% 9-speed already in the bench. This plate adds the two-stage 80%.

Related plates

Install this plate

Install Amana AR9T80 as Two-stage · 9-speed ECM · 80% Cat I.

Two-stage · 9-speed ECM · 80% Cat I

This plate — not the sister SKU

  • Not AR9T96 / AD9T96 (96% two-stage 9-speed). Not AR9S80 (single-stage 80% 9-speed). Not ARVT80 (ComfortBridge).
  • AR9S80 is the single-stage 80% 9-speed already in the bench. This plate adds the two-stage 80%.

IFC on this door

  • Codes sit on the IFC in the blower compartment. door card is wiring 0140F20004-B. Do not kill power — that clears the active code.
  • Read left to right (Seg3→Seg2→Seg1). Idle / no fault is a quiet or dashed display; faults prefix E, EE, L, U, F, S, r.
  • E1/E2 are the LOW-FIRE pressure switch. E8/E9 are the HIGH-FIRE pressure switch. AR9S96 has only one PS and no E8/E9 — leave that page.
  • A2L pair codes (FE3, LE4, SE5, rE6) only apply when this furnace is tied to an R-32 / A2L outdoor. Ignore them on R-410A pairs.

Hardware

  • AFUE: 80% two-stage · Cat I metal
  • Sister SKU: AD9T80 downflow · Goodman GR9T80

First fire

  1. 1Two hoses + PVC = AR9T96. Two hoses + metal vent = AR9T80. One hose + metal = AR9S80.
  2. 2Door 0140F20004-B is the 96% two-stage card. Do not hang it in this 80% cabinet.

Do not on Amana AR9T80

  • Not AR9T96 / AD9T96 (96% two-stage 9-speed). Not AR9S80 (single-stage 80% 9-speed). Not ARVT80 (ComfortBridge).
  • AR9S80 is the single-stage 80% 9-speed already in the bench. This plate adds the two-stage 80%.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • Amana literature libraryLiterature searchGas furnace / air-handler PDFs. Match the plate, not just the Amana badge.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Standard limited warranty

    warranty sheet

    Amana furnace heat-exchanger / unit-replacement terms

    Registered residential furnace warranty terms · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal