Models
Amanafurnace

AR9S80

Single-stage · 9-speed ECM · 80% AFUE · Cat I metal vent

Single-stage 80% multi-position furnace with a 9-speed ECM and one pressure switch. SS-AR9S80_AD9S80-R32 / wiring 0140F20001-B: 4" Category I metal vent (not PVC), durable hot-surface igniter, LPM-31 LP kit with LP switch, HANG20 high-altitude. E2 is chimney / B-vent / inducer — not a 96% trap.

Not AR9S96 (96% Cat IV PVC, silicon nitride language, LPM-33, E2 is a collector/trap). Not AR9T96 (two-stage condensing, dual PS, E8/E9). Not ARVT96 / AMVC96 (ComfortBridge). Not GMS80 (LED 1–9 flash, PSC/ECM 80% — different card). Do not cut PVC or prime a trap that is not on this cabinet.

Input / AFUE

40–120 kBtu · 80% AFUE (SS-AR9S80_AD9S80-R32 Aug 2024) · not SCAQMD/SJV · reduce input 4% per 1000' above 4500'

SKUs (upflow)

AR9S800403A / 0603A / 0603B / 0604B / 0803B / 0804B / 0804C / 0805C / 1005C / 1205D

SKUs (downflow)

AD9S800403A / 0603A / 0804B / 0805C / 1005C

Staging

Single-stage gas valve · single-speed inducer · one pressure switch (0140F20001-B)

Blower

9-speed ECM taps F01–F09. Heat default F02. Cool default F04. F01 not recommended for heating.

2-stage outdoor taps

*R9S800805C* Y2=F08 Y1=F02 · *R9S801205D* Y2=F06 Y1=F05 · *D9S800805C* Y2=F08 Y1=F02 (SS p.8 / p.10)

Heat exch.

Stainless dual-diameter tubular · foil-faced insulated HX section

Ignition

Durable hot-surface igniter (SS language — not silicon-nitride) · 115 VAC 60 Hz

Vent

Cat I 4" metal · single-wall connector 6" clearance / B-vent 1" · masonry MVK-01 (most upflow) / MVK-02 (120k only)

Clearances

Sides 1" · rear 0" · front 3" (24" service recommended) · top 1"

Tstat

Conventional 24V · W Y G R C — leftover W2 is unused

Accessories

LPM-31 LP with LP switch (not LPM-33/34) · HANG20 high-altitude NG (not HASFK) · AFE18-60A dual fuel · SBT14/17/21 downflow sub-bases (not CFSB)

Sister SKU

AD9S80 downflow. Not AR9S96 PVC. Not GMS80 flash.

This board

Self-diagnostic IFC · single 7-segment · wiring 0140F20001-B

  • door card is wiring 0140F20001-B. Read left to right. Do not kill power — that clears the active code.
  • Codes are E0–E7, EA, Eb, Ec, Ed, En, plus TWIN, LE1, EEH, and A2L pair tokens. One pressure switch only — E1 stuck closed, E2 open.
  • E2 is Category I draft: chimney, B-vent, 4" metal, inducer, common-vent. It is not a 96% trap / PVC / collector story.
  • A2L pair codes only apply when this furnace is tied to an R-32 / A2L outdoor. Ignore them on R-410A pairs.

In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.

Universal swap

Read the silk

Same 9-speed tap story as AR9S96, metal vent. Universals that assume a PSC 80% will not run this motor.

Silk: 0140F20001-B · PCBBF136 · PCBBF140

White-Rodgers

ICM

  • ICM2810

    Only if the silk is PCBBF136 or PCBBF140. This 80% door is 0140F20001-B — photograph it.

Honeywell

  • 50A55-843 ‘80% universal’ or S9200U1000 — those cartons are PSC carbide, not this 9-speed tap IFC.
  • A 96% PCBBF132 (AR9T96) — dual PS and PVC logic do not belong on a Cat I chimney.
  • ICM2811 unless the silk is PCBBF110/112/123.

After you pull the dead card

  1. 1Kill power. Photograph the silk-screen part number on the dead board before you pull it.
  2. 2Match staging (1 vs 2 vs modulating), igniter (carbide / nitride / spark), and motor (PSC / ECMx / 9-speed tap / serial VS).
  3. 3Set heat-off delay and any 80+/90+ jumper to the door card. Prove one full try and flame µA before you leave.
  4. 4E2 on this plate is chimney / B-vent / inducer, not a trap. After a board swap, prove draft on 4" metal, not PVC.

Field wiring

Written landings for Amana AR9S80. Not a factory schematic.

Furnace · single-stage 24V
R / C / W / Y / GGas furnace

Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → transformer → R120V in, 24V out
  2. 2Call. Stat W → IFC W~24 VAC
  3. 3Draft. IFC → inducer → PS close120V motor, 24V prove
  4. 4Ignite. IFC → HSI120 VAC
  5. 5Gas. IFC → valve~24 VAC
  6. 6Flame. Rod → IFCµA DC
  7. 7Blow. IFC → heat speedAfter flame prove

This indoor

80% 9-speed. Same 24V landing as AR9S96. E2 is a chimney.

24V single-stage heat

Door card is one-stage. Twin terminal empty unless the job is actually twinned.

Wall thermostat

Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.

  • R24V hot from the IFC24V
  • CCommon24V
  • WHeat24V
  • YCool — also starts the outdoor24V
  • GFan24V

Furnace IFC

Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.

  • RHot to the stat24V
  • CCommon — must reach the outdoor24V
  • WHeat call24V
  • YCool in / cool out24V
  • GBlower24V
  • TWINEmpty unless twinned24V

Landing

  • 24VIFC Rstat R

    ~24 VAC hot

  • 24VIFC Cstat Coutdoor C

    Common

  • 24VStat WIFC W

    Heat. Stays in this cabinet.

  • 24VStat YIFC Youtdoor Y

    Cool / contactor

  • 24VStat GIFC G

    Fan. Does not go outdoors.

IFC harness — single-stage heat

After W arrives. This is the gas train, not the thermostat strip.

Transformer + fuse

120V primary. 24V secondary. Dark stat = fuse / door / transformer first.

  • L1 / N120V to the IFCLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout in series. Open anywhere kills heat.

  • DOORInterlock24V
  • LIMITMain limit — rise / no airflow24V
  • ROLLOUTManual reset. Do not jumper and leave24V

Inducer + one pressure switch

W → inducer 120V → PS closes → IFC continues. One hose, one switch.

  • IND120V from the IFC to the inducerLine
  • PS24V prove back to the IFC24V
  • HOSESingle hose. Do not add a second because two-stage boards have two.24V

HSI + single valve

Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.

  • HSI120V hot-surface igniter — not 24VLine
  • VALVE24V to the single solenoid24V
  • FLAMEµA DC on the rod. Not a 24V circuit24V

9-speed tap ECM

F01–F09 on the harness. Heat tap and cool tap are separate. Not a 14-pin serial motor and not a run cap.

  • F01–F09Speed taps on the IFC / harness24V
  • HEATDefault often F02 — F01 is an E3 generator on many 9-speed doors24V
  • COOL / Y / GCool tap. Wrong tap freezes the coil and looks like LPS outdoors.24V

Landing

  • LineL1IFCinducer

    120 VAC after W

  • 24VIFCPSIFC

    ~24 VAC prove. Open PS = no ignition.

  • LineIFCHSI

    120 VAC during trial

  • 24VIFCgas valve

    ~24 VAC after flame prove starts

  • 24VFlame rodIFC

    µA DC. Not 24V.

  • LineIFCblower

    IFC heat speed / tap

Prove it

  • 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
  • W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.

Do not

  • Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
  • Do not hunt W2 / E8 / high-fire on a one-stage door.
  • TWIN must be empty on a standalone.

9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.

Sequence

  1. 1

    W

    IFC proves limits/rollout closed, starts the single-speed inducer.

  2. 2

    Prove PS

    The only pressure switch must close against the metal vent. Already closed with inducer off → E1. Never closes → E2 (chimney / B-vent / 4" / inducer).

  3. 3

    HSI / valve

    Hot-surface igniter warm-up, then the single solenoid. Open igniter → En / E7. Failures stack toward E0.

  4. 4

    Blower

    Heat-on delay, then the 9-speed ECM on the selected heat tap (factory F02). F01 is not recommended for heating.

  5. 5

    Satisfied

    Valve off, inducer post-purge, blower heat-off delay. Unexpected flame → E4.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

E0

Retry / recycle lockout

lockout

Too many failed ignition attempts or flame losses on this call.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Amana AR9S80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Watch one full try: inducer, HSI glow, valve click, flame, µA.

    Expect: Flame rod: µA per this door card. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Gas supply and manifold vs this 80% plate.

    Expect: Manifold: Single-stage plate value. Reduce input 4% per 1000' above 4500'.

  3. 3 Prove it is not a switch opening

    Watch the live Amana AR9S80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Ground and flame-rod cleanliness.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

E1

PS stuck closed

lockout

The only pressure switch is made with the inducer off.

  1. 1 Unplug the switch with the inducer off

    On Amana AR9S80 this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the only PS. Code change = welded switch or residual draft in the hose.

    Expect: Code changes when the harness is open.

    If fail: Wrong switch, or the IFC input is shorted.

    If pass: Switch/hose path. Go to step 2.

  2. 2 Water in the hose vs a welded switch

    Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Hose holding chimney draft with inducer off — wind on a tall stack can fake E1.

    Expect: Hose empty. Switch opens with no draft.

  3. 3 IFC input last

    If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Amana AR9S80 IFC input is shorted. Do not keep swapping switches. IFC input shorted — only after the switch ohms open.

    Expect: Known-good open switch + open harness = code gone. If not, IFC.

E2

PS open — metal-vent draft

lockout

Inducer is on and the only switch will not close. This is a chimney / B-vent / 4" metal / inducer call — not a drowned 96% trap.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Amana AR9S80 active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer 120 VAC and spinning. A dead inducer is E2 with a perfect switch.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Chimney, B-vent, common vent, cap, liner, and 4" connector. Single-wall connector needs 6" to combustibles.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Cold chimney that will not establish draft on a first morning call. Spillage at the draft hood / collector.

    Expect: Pressure switch: One NO switch. Closed only with inducer up against the metal vent. Not a 96% collector tap.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

E3

Open high limit

warn

Primary limit opened. Airflow or overfire.

  1. 1 Airflow before you touch the limit

    On Amana AR9S80 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Heat tap first. Factory default F02. F01 is not recommended for heating.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Amana AR9S80 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Filter, wheel, coil sitting on an 80%. A new media cabinet will trip E3 all winter.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). TES vs the AR9S80 blower chart for this cabinet. Rise ranges are 20–50 up to 40–70 on 1205D.

    Expect: Manifold: Single-stage plate value. Reduce input 4% per 1000' above 4500'.

E4

Flame when valve should be off

hazard

Rod sees flame with the solenoid de-energized.

  1. 1 Shut the gas cock first

    On Amana AR9S80 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground or IFC flame circuit.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

E5

Open fuse

warn

24 V fuse on the IFC is open.

  1. 1 Find the 24 V short before you replace the fuse

    On Amana AR9S80 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. Short on W, Y, G, humidifier, EAC.

    Expect: Fuse out. 24 V transformer still good. Harness isolated.

  2. 2 Replace the fuse with the harness off

    New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC). Unplug the tstat harness and replace the fuse.

    Expect: Fuse holds with harness off. Dies when the shorted lead lands.

  3. 3 If it blows with the harness off

    Short is on the Amana AR9S80 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.

    Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.

E6

Low flame signal

warn

Flame present, µA below threshold.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Amana AR9S80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod with a non-scratch pad.

    Expect: Flame rod: µA per this door card. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Chassis ground, manifold, LP conversion (this plate uses LPM-31 with an LP switch — not LPM-33).

    Expect: Manifold: Single-stage plate value. Reduce input 4% per 1000' above 4500'.

  3. 3 Prove it is not a switch opening

    Watch the live Amana AR9S80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

E7

Igniter relay fault

lockout

IFC did not see the igniter circuit behave as commanded.

  1. 1 Ohms at the igniter, then at the IFC

    On Amana AR9S80 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Hot-surface igniter ohms cold per this sticker — not an AR9S96 nitride chart.

    Expect: HSI: Hot-surface igniter per SS — not the AR9S96 nitride sticker. 120 VAC during warm-up.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. 120 VAC during warm-up. Cracked element.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

EA

Line polarity / ground

lockout

L1/N reversed or chassis ground missing.

  1. 1 Hot and neutral at the IFC, not the disconnect

    On Amana AR9S80 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot and neutral at the IFC. Burner-box ground screw.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

Eb / Ec

Gas valve circuit

lockout

Internal (Eb) or external (Ec) gas-valve electrical fault.

  1. 1 Coil ohms and 24 VAC during trial only

    On Amana AR9S80 measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Valve coil ohms, 24 VAC at the harness during trial.

    Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.

  2. 2 Do not energize a leaking valve

    If the unexpected-flame code is also in history, shut the cock and replace the valve. Applying 24 V as a ‘test’ and walking away is a gas leak.

    Expect: No flame with the cock shut and solenoids de-energized.

  3. 3 IFC relay vs the valve

    Voltage at the harness and a dead coil = valve. No voltage during a known trial = IFC relay or a lockout that never opened the valve (look at the live code).

    Expect: Known trial + 24 VAC + good coil = flame. Otherwise IFC.

Ed

Open rollout

hazard

Manual-reset rollout. Treat as flame outside the exchanger until proven otherwise.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Amana AR9S80 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Primary exchanger, burner alignment, crossover, blocked flue / chimney. Reset only after the cause is fixed.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Amana AR9S80 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

En

Igniter open

lockout

Igniter circuit measures open.

  1. 1 Ohms at the igniter, then at the IFC

    On Amana AR9S80 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the igniter plug, then at the IFC.

    Expect: HSI: Hot-surface igniter per SS — not the AR9S96 nitride sticker. 120 VAC during warm-up.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Harness rub-through.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

EEH

Grounding error

lockout

IFC failed its ground check (sister to EA).

  1. 1 Hot and neutral at the IFC, not the disconnect

    On Amana AR9S80 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green ground to cabinet and IFC. Painted screw, missing star washer.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

TWIN

Twin error

lockout

Twinning miswire or twin terminal active on a standalone unit. Door card lists TWIN on 0140F20001-B.

  1. 1 Is this cabinet actually twinned?

    On a standalone Amana AR9S80, nothing belongs on the TWIN terminal. A leftover jumper throws this. If not twinned, nothing should be on the TWIN terminal.

    Expect: TWIN empty on a single cabinet.

  2. 2 Twinned pair must be the same IFC family

    Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin. Twinned pair must be same family / same IFC revision.

    Expect: Same model family, same IFC, kit installed per the twinning sheet.

  3. 3 Phasing and 24 V

    Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.

    Expect: In-phase 24 V. Continuous twin lead.

LE1

Low circulator current

lockout

9-speed ECM current too low.

  1. 1 Is the wheel free?

    Spin the Amana AR9S80 blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Harness seated at motor and IFC. A half-seated tap plug throws this.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Locked rotor, wet winding, or a PSC motor someone hung on this IFC.

    Expect: ECM taps: Heat default F02. Cool default F04. Two-stage outdoor: 0805C Y2=F08 / Y1=F02; 1205D Y2=F06 / Y1=F05.

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.

    Expect: Static on the blower chart. Matching motor / shared-data card.

FE3 / LE4 / SE5 / rE6

A2L mitigation

hazard

Leak / comm / relay alarm from the A2L board when paired with an R-32 / A2L outdoor.

  1. 1 Confirm this pair is actually A2L

    On Amana AR9S80 FE3 / LE4 / SE5 / rE6-class codes are only valid when this furnace is tied to an R-32 or R-454B outdoor. On R-410A this is a miswired mitigation harness — not a leaking indoor coil.

    Expect: Outdoor refrigerant from the outdoor nameplate, not from memory.

    If fail: Remove / correct the mitigation harness. Do not condemn the IFC.

  2. 2 Sensor location and the mitigation blower

    If it is a real A2L pair, follow the OEM mitigation sequence: sensor location, ventilation blower, relay. Only valid on A2L pairs. On 410A this is a miswired mitigation harness.

    Expect: Sensor seated where the I/O shows. Mitigation blower runs on a test.

  3. 3 Do not bypass mitigation

    Never jump an A2L alarm to get heat. Find the leak or the failed sensor. Recurring mitigation with a clean sensor is a refrigerant leak until proven otherwise.

    Expect: Alarm clears only after the leak/sensor is fixed.

Workflows

No heat — E2 is a chimney

Tstat calling W, indoor cold, or E0/E2/E7 on an 80%.

  1. 1 Prove the call and the live code

    Confirm the plate is AR9S80 / AD9S80 and the vent is 4" metal. If you see PVC, you are on AR9S96 — leave this page.

    Expect: Write whatever Self-diagnostic IFC · single 7-segment · wiring 0140F20001-B is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Read the 7-seg (0140F20001-B) before you pull power. Write the code.

    Expect: Prove PS: The only pressure switch must close against the metal vent. Already closed with inducer off → E1. Never closes → E2 (chimney / B-vent / 4" / inducer).

  3. 3 Confirm with a number, then the next part

    Door switch, 120 VAC at L1, 24 VAC across the fuse (E5). W at the IFC. Cap a leftover W2 — this valve is single-stage. E2: inducer spinning? Then chimney / B-vent / 4" connector / common vent / cap / liner. Do not open a condensate trap that is not here.

    Expect: Pressure switch: One NO switch. Closed only with inducer up against the metal vent. Not a 96% collector tap. · Manifold: Single-stage plate value. Reduce input 4% per 1000' above 4500'.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

E3 limit trips (80%)

Heat works, then drops, E3.

  1. 1 Prove the call and the live code

    Heat tap first. Factory F02. F01 is not recommended for heating on this SS.

    Expect: Write whatever Self-diagnostic IFC · single 7-segment · wiring 0140F20001-B is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Filter and the A-coil sitting on an 80%. A 5" media cabinet is the usual callback.

    Expect: Prove PS: The only pressure switch must close against the metal vent. Already closed with inducer off → E1. Never closes → E2 (chimney / B-vent / 4" / inducer).

  3. 3 Confirm with a number, then the next part

    TES vs the AR9S80 chart. 1205D rise is 40–70 — do not use a 96% rise table. Clock the meter. Overfire on an 80% trips limits with a clean filter.

    Expect: Pressure switch: One NO switch. Closed only with inducer up against the metal vent. Not a 96% collector tap. · Manifold: Single-stage plate value. Reduce input 4% per 1000' above 4500'.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

80% metal or 96% PVC?

First minute. Someone already cut PVC or is looking for a trap.

  1. 1 Prove the call and the live code

    Plate AR9S80 / AD9S80 = stay here. 4" Category I metal. Clearances: sides 1", front 3", vent 6" SW / 1" B.

    Expect: Write whatever Self-diagnostic IFC · single 7-segment · wiring 0140F20001-B is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Plate AR9S96 / AD9S96 = Cat IV PVC, trap, collector. Use that chart. E2 there is not a chimney.

    Expect: Prove PS: The only pressure switch must close against the metal vent. Already closed with inducer off → E1. Never closes → E2 (chimney / B-vent / 4" / inducer).

  3. 3 Confirm with a number, then the next part

    LP kit on this cabinet is LPM-31 (with LP switch). LPM-33/34 belong on the 96% plates. High altitude is HANG20, not HASFK. Masonry vent is MVK-01 (or MVK-02 on 120k upflow only). Downflow sub-base is SBT14 / SBT17 / SBT21 — not the CFSB17/21/24 used on the 96% downflows.

    Expect: Pressure switch: One NO switch. Closed only with inducer up against the metal vent. Not a 96% collector tap. · Manifold: Single-stage plate value. Reduce input 4% per 1000' above 4500'.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Pressure switch

One NO switch. Closed only with inducer up against the metal vent. Not a 96% collector tap.

Manifold

Single-stage plate value. Reduce input 4% per 1000' above 4500'.

Flame rod

µA per this door card. Rising while running is the goal.

HSI

Hot-surface igniter per SS — not the AR9S96 nitride sticker. 120 VAC during warm-up.

ECM taps

Heat default F02. Cool default F04. Two-stage outdoor: 0805C Y2=F08 / Y1=F02; 1205D Y2=F06 / Y1=F05.

Vent

4" Category I metal. Single-wall connector 6" to combustibles. B-vent 1".

Gotchas

  • Techs treat every Amana 9-speed E2 as a 96% trap. On this plate that wastes the call — there is no collector to drown.
  • Do not cut PVC onto an AR9S80. Category I metal only.
  • LPM-31 (with LP switch) is the only LP kit on this SS. LPM-33 is AR9S96. LPM-34 is AR9T96 / ARVT96.
  • HANG20 is the high-altitude kit, not HASFK. Grabbing the 96% HASFK carton is a parts-runner miss.
  • Downflow sub-base is SBT, not CFSB. CFSB17/21/24 are the condensing downflow bases.
  • Looks like AR9S96 in the basement until you look at the flue. 4" metal = this page. PVC = the other page.
  • GMS80 / GMES80 flash 1–9 is a different 80% card. Do not count flashes on this 7-seg.

Related plates

Install this plate

Install AR9S80 as a Category I 80% metal-vent 9-speed — not a 96% PVC furnace.

Cat I 4" metal vent · 24V W · 9-speed tap ECM · one pressure switch · wiring 0140F20001-B · LPM-31

Cabinet & air

  • Read the full plate (AR9S800403A vs 1205D). Rise on 1205D is 40–70 — do not use a 96% rise table.
  • AR9S80 upflow / horizontal. AD9S80 downflow uses SBT14 / SBT17 / SBT21 sub-bases — not the CFSB17/21/24 condensing bases.
  • 9-speed taps F01–F09. Heat default F02. Cool default F04. F01 not recommended for heating.
  • Two-stage outdoor tap recs from SS: *R9S800805C* Y2=F08 Y1=F02; *R9S801205D* Y2=F06 Y1=F05; *D9S800805C* Y2=F08 Y1=F02.

Vent — Category I metal only

  • 4" Category I metal vent. Single-wall connector 6" to combustibles. B-vent 1". Front 3" (24" service recommended), sides 1", rear 0", top 1".
  • Masonry: MVK-01 on most upflow, MVK-02 on the 120k upflow only. Not a 96% concentric PVC kit.
  • E2 is chimney / B-vent / 4" / inducer / common-vent. There is no condensate trap to prime and no PVC to slope.
  • Reduce input 4% per 1000' above 4500'. High-altitude kit is HANG20, not HASFK.
  • Not SCAQMD / SJV. Do not cut PVC onto this flue.

Gas, electrical, thermostat

  • Single-stage 24V stat on W. Cap a leftover W2.
  • LP kit is LPM-31 with an LP switch. Not LPM-33 (AR9S96) and not LPM-34 (AR9T96 / ARVT96).
  • Igniter is the SS ‘durable hot-surface’ — not the silicon-nitride language on the 96% plates. Use this sticker for ohms.
  • Door card is 0140F20001-B. One PS. TWIN terminal empty unless the job is actually twinned.

First fire

  1. 1Confirm 4" metal vent, draft, and clearances (SW 6" / B 1") before you gas it.
  2. 2W: inducer, metal-vent PS close, HSI, valve, flame, heat tap F02.
  3. 3Rise vs the AR9S80 chart for this cabinet — not an AR9S96 PVC table.
  4. 4If E2 on first fire, look at the chimney / B-vent / 4" connector. Do not open a trap that is not here.

Do not on Amana AR9S80

  • Do not install PVC / concentric 72950/72951 / a condensate trap. This is Category I metal.
  • Do not use the AR9S96 E2-as-trap lecture or the AR9T96 E8/E9 chart.
  • Do not grab LPM-33, LPM-34, HASFK, or a CFSB sub-base. This plate is LPM-31, HANG20, SBT.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • Amana literature libraryLiterature searchGas furnace / air-handler PDFs. Match the plate, not just the Amana badge.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Standard limited warranty

    warranty sheet

    Amana furnace heat-exchanger / unit-replacement terms

    Registered residential furnace warranty terms · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal