Two-stage 96–97% condensing furnace with a 9-speed ECM (not a communicating VS motor) and a single 7-segment IFC. SS-AR9T96_AD9T96-R32 / wiring 0140F20004-B: two pressure switches (low + high). Conventional 24V thermostat. E1/E2 vs E8/E9 are not interchangeable with AR9S96 (one PS) or ARVT96 (ComfortBridge).
Not AR9S96 (single-stage, one PS, no E8/E9). Not AR9S80 (80% Cat I metal vent). Not ARVT96 / AMVC96 / AMVM97 (ComfortBridge communicating VS — no 9-speed taps, no 2-second recall hold). AR9T96 will not talk ComfortNet/ComfortBridge and does not use idle/Ht1/CF status words.
High-stage pressure switch is made with the inducer not on high.
This is the second switch — do not confuse with E1.
Welded HPS or water-filled hose.
IFC calling high when it should be low — W2 shorted to W1.
E9
High-fire PS open
lockout
Inducer on high, high-fire switch never closes. Classic ‘runs on low, will not go high.’
Inducer actually changes speed on W2? Listen / amp it.
HPS hose on the high-fire tap, not teed to the low switch.
Vent capacity / wind / shared chase. High fire needs more draft than E2 ever saw.
Condensate backing into the collector only under high fire.
EA
Line polarity / ground
lockout
L1/N reversed or chassis ground missing. HSI and flame sense both suffer.
Hot and neutral at the IFC, not just the disconnect.
Burner box to IFC ground screw.
Twinned jobs — follow the twinning kit, then look at EEJ.
Eb / Ec
Gas valve circuit
lockout
Internal (Eb) or external (Ec) gas-valve electrical fault.
Valve coil ohms, 24 VAC at the harness during trial.
Do not apply 24 V to a leaking valve as a ‘test’ and walk away.
Ed
Open rollout
hazard
Manual-reset rollout opened. Treat as flame outside the exchanger until proven otherwise. Door chart may render this as a distinctive 7-seg character — confirm on the unit sticker.
Reset only after the cause is fixed. Recurring rollout is a CO / fire call.
En
Igniter open
lockout
Igniter circuit measures open.
Ohms at the igniter plug, then at the IFC.
Harness rub-through on the collector.
EEH
Grounding error
lockout
IFC failed its ground check (sister to EA).
Green ground to cabinet and IFC.
Painted screw, missing star washer.
EEJ
Twin error
lockout
Twinning miswire or twin terminal active on a standalone unit.
If not twinned, nothing should be on the TWIN terminal.
Twinned pair must be same family / same IFC revision.
LE1 / UE2
Circulator current
lockout
ECM current too low (LE1) or unexpected (UE2).
Harness seated at motor and IFC. 9-speed ECM is tap-driven — a half-seated plug throws these.
Locked rotor, wet winding, or wrong motor for the cabinet.
Do not put a PSC motor on this IFC.
FE3 / LE4 / SE5 / rE6
A2L mitigation
hazard
Leak / comm / relay alarm from the A2L board when paired with R-32 or R-454B outdoor.
Only valid on A2L pairs. On 410A, this is a miswired mitigation harness.
Leak sensor location, ventilation blower, and OEM mitigation sequence before you condemn the IFC.
Workflows
No heat on W1
Tstat calling heat, indoor is cold, or E0/E2/E7.
Read the 7-seg before you pull power. Write the code.
Door switch in? 120 VAC at L1, 24 VAC across the fuse (E5 if open).
W1 present at the IFC (not just at the stat). R to W ~24 VAC.
Inducer on low? If silent → inducer / IFC output. If running and E2 → trap, hose, LPS, vent.
If E1 with inducer off → unplug LPS. Code change = switch/hose. No change = IFC.
HSI glow? No glow + En/E7 → igniter. Glow but no flame → gas cock, valve 24 VAC, manifold.
Flame then drop → µA on E6, ground, or rollout (Ed). Do not keep cycling.
Runs on low, will not go high
Comfort complaint or long run times. Often E9.
Confirm the thermostat is actually closing W2 (or the IFC staging timer has expired).
Listen for inducer speed-up. No speed-up → W2 / IFC. Speed-up + E9 → high-fire PS path.
HPS hose on the high tap only. A tee with the LPS is a common first-install miss.
Manifold high-fire vs plate. A valve that never opens stage 2 looks like an airflow complaint.
Vent and intake sized for high fire on this cabinet — 2" that passed on low will fail on a 100–120 kBtu high fire.
E3 limit trips
Blower on, burners drop, E3.
This is a 9-speed ECM. Read the heat tap on the IFC / motor harness before you replace a limit.
Total external static vs the AR9T96 blower chart for this cabinet (B/C/D).
Filter, wheel, coil. A new 5" media cabinet the installer added will trip E3 all winter.
Clock the meter / manifold — overfire trips limits with a clean filter.
Secondary / condensate — a drowned coil raises head in the exchanger and trips limit.
Test points
Flame rod
Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.
Manifold low / high
Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
LPS / HPS
Both NO. Closed only when that inducer speed is making the collector setpoint. Two hoses — never tee.
HSI
Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use a 80% Norton chart.
ECM taps
Factory defaults from SS p.8: fan F03, Y1/Y F04, Y2 F05, heat low F01, heat high F02. Rise is cabinet-specific (15–45 on 0303AN through 35–65 on 80–120 kBtu).
Gotchas
Techs treat AR9T96 like AMVC96 or ARVT96 and start looking for ComfortBridge menus. There are none.
E2 vs E9: fixing the trap clears low fire and the callback is ‘still no high fire’ because the HPS hose was never on the high tap.
9-speed ECM on the wrong heat tap is the silent E3 generator. It is not a bad limit. Move F01/F02, not the valve.
Bottom return: SS note — failure to unfold the flanges can cut airflow ~18% and will look like a limit/noise call.
Airflows over 1600 CFM need two-side return or side+bottom, min 20×25 filter (SS p.8).
AD9T96 is the downflow twin — drain and secondary orientation change, codes do not. Downflow LP kit is LPM-33, not LPM-34.
0303AN uses LPM-30 for LP. Every other AR9T96 upflow uses LPM-34. Do not grab the wrong carton.
Goodman GR9T96 is the same IFC and the same chart. Do not pull a GMVC96 / ARVT96 communicating board into this cabinet.
AR9S96 looks like this cabinet. One PS, no E8/E9, heat default F02. Wrong chart if the door is 0140F20003-B.
AR9S80 is the 80% Cat I cousin — 4" metal vent, wiring 0140F20001-B, LPM-31. E2 is a chimney, not a trap.
Related plates
amana-ar9s96 — Single-stage 9-speed sister — one PS, 0140F20003-B, E0–E7 only. Do not look for E8/E9 here.
amana-ar9s80 — 80% single-stage 9-speed — Cat I 4" metal vent, 0140F20001-B, LPM-31. Not this PVC two-stage.
amana-arvt96 — New ComfortBridge two-stage VS R-32 plate. Triple 7-seg + serial ECM. Not this tap IFC.
amana-amvc96 — Older ComfortBridge two-stage VS cousin — triple 7-seg and serial ECM. Do not use that chart on this 9-speed 24V IFC.
amana-am9s96 — Older single-stage 96% flash sibling. One pressure switch, LED 1–9, no E8/E9.
goodman-gr9t96 — Goodman-badge twin. Same IFC and the same E0–E9 chart.