Amana
ASX16
AC · Single-stage outdoor AC · contactor + dual cap
Amana single-stage R-410A condensing unit. Contactor + dual cap. Same story as Goodman GSX16. Not ASXC18 and not the current ALXS4B R-32 box.
Not ASXC18. Not ALXS4B (R-32). Not ASZ14 heat pump.
Walk this in DiagnoseThis plate
- Stages
- Single-stage scroll · contactor
- Refrigerant
- R-410A
- Pair
- 24V Y
- Sister SKU
- Goodman GSX16
This board
Contactor + fan — no outdoor PCB to interrogate
- No 7-seg. Indoor E2 is the furnace.
- Dual-cap FAN and HERM both matter.
Sequence
- Y. 24 VAC at the contactor coil → compressor and outdoor fan. Indoor blower on the cool tap / G.
Faults on this IFC
No Y
Outdoor silent
warnNo 24 VAC at the contactor or the coil is open.
- Y and C at the outdoor. Indoor IFC / stat actually closing Y.
- Contactor coil ohms. Do not confuse a furnace lockout with a dead outdoor.
Hum / no start
Cap / start
lockoutCompressor hums, outdoor fan may run.
- Dual cap (fan and herm). Replace on values, not just a bulge.
- Hard-start only after the cap and windings are proven.
HPS
High pressure
lockoutOutdoor airflow, overcharge, or restriction.
- Fan running? Coil dirty? SC vs nameplate on a TXV coil.
LPS / freeze
Low pressure
lockoutCharge, indoor airflow, metering.
- Do not add gas on a frozen coil. Indoor filter/coil first.
Workflows
No cool, ASX16
Indoor running, outdoor dead.
- 24 VAC at the contactor coil.
- Dual cap, then 410A SH (piston) or SC (TXV).
- Do not apply ALXS4B R-32 targets.
Test points
- Charge
- Nameplate + line-set. SH on piston, SC on TXV.
- Cap
- Dual can. Fan and herm both in spec.
Gotchas
- ALXS4B is the current R-32 replacement shape — different refrigerant.
- Goodman GSX16 is the twin.