Heat pump · Bosch IDS 2.0 · inverter ducted split · BOVA outdoor + BVA/BAA AHU
Bosch IDS 2.0 / BOVA 2.0 inverter outdoor paired with a BVA / BAA air handler. The indoor–outdoor pair is communicating. The wall thermostat on many jobs is conventional 24 V at the AHU. Charge is weigh-in / the Bosch chart — not piston superheat. Do not apply Daikin U4 or Carrier 31 to this system.
Not Daikin DZ20VC (U4/L5). Not Mitsubishi MXZ. Not a 24V piston 14-SEER with a contactor-only outdoor. Not Climate 5000 ductless (different code set).
BOVA20 / BOVB inverter HP · R-410A · 2–5 ton class
Indoor
BVA / BAA air handler · electric-heat kits with their own limits
Pair wiring
Communicating cable indoor–outdoor. 24V stat typically at the AHU (Y/B/G/W/C)
Charge
Weigh-in + Bosch IDS chart. Not a piston SH target
Example SKU
BVA-36N1 indoor · BOVA20 outdoor
This board
BOVA outdoor inverter PCB + BVA indoor board
Faults show on the outdoor display (C3, E4, E5, E6, E7, E9, H0, H8, P0, P1, P2, P3, P4, ATL, and inverter L-family). Read the IDS sticker in THIS outdoor.
Indoor–outdoor comm is the dedicated pair between BVA and BOVA. The wall stat is 24 V at the AHU on most residential jobs. Techs mix these two cables constantly.
Do not translate these as Daikin U4 or Carrier 31. Bosch letters are Bosch.
Electric-heat limits live on the AHU heat kit (mechanical limits / sequencers), not as a Daikin E3.
Sequence
Stat call. 24 V at the AHU (Y cool, B/O reversing, G fan, W strips). The AHU then talks to the outdoor on the comm cable. No Y at the outdoor like a contactor unit.
Outdoor start. Inverter ramps after the comm handshake. H0 / E9 / blank display with a good 24 V stat is almost always the indoor–outdoor cable, not the stat.
Heat pump heat. B (or O, per Bosch diagram) must be correct or you get ATL / no HP heat and the strips take over.
Defrost. Outdoor coil sensors (T3/T4) and the IDS defrost routine. Failed sensors are E4 / C3, not a furnace rollout.
Faults on this IFC
ATL
Ambient temperature limited
warn
Outdoor T4 outside the allowed window (cool: T4 ≥125°F or <15°F; heat: T4 ≥86°F or <−4°F on IDS 2.0), or the reversing-valve call is wrong so the outdoor thinks it is in the wrong mode.
Idle ≥5 min, compare T4 on the board to real outdoor temp (10K sensor, ~10 kΩ at 77°F).
Heat call must energize B per the Bosch diagram. Y-only in heat, or B stuck on in cool, produces ATL.
18–28 VAC B–C at the outdoor during a heat call.
C3 / C4
Condenser coil sensor seating
warn
T3 reads implausible vs T4 (T3 < T4 − 3°F for 10 min).
T3 on the outdoor coil U-bend per the diagram, not hanging in air.
T3/T4 10K ohms. 18 SEER has one T3; some 15/20 SEER have T3 and T3L.
E4
Temperature sensor fault
lockout
T3, T3L, T4, T5, or TF out of range.
Identify which sensor the display names.
T3/T4/T3L: 10K. T5/TF: 5K class — use the IDS ohm chart. Open/shorted harness vs failed bulb.
E5
High / low voltage protection
lockout
Line voltage out of band (IDS: operate ~180–270 V; typical run ≥210 V).
L1–L2 at the outdoor. A just-pulled disconnect can E5 on the inrush — wait and recheck.
This is line voltage, not a 24 V stat brownout. Still verify 18–28 VAC Y–C at the AHU so you do not chase the drive for a dead transformer.
E6
Outdoor DC fan motor
lockout
Outdoor fan failed or the board is not driving it.
Blade free? Ice/wind lock?
Motor vs board: resistance and drive voltage per the 5-wire or 3-wire diagram on THIS BOVA.
A dead outdoor fan becomes P1/P0 next.
E7
Discharge sensor seating
warn
T5 not tracking (T5 < T3 − 5°F in cool, or similar band in heat, for 10 min) — plug not on the discharge or a real high-discharge event.
T5 fully on the discharge tube. 5K sensor.
If T5 is seated and hot, that is charge / restriction / P4 territory — do not just reseat forever.
E9
EEPROM fault
lockout
Outdoor control EEPROM / memory chip.
L1–L2 in range. If E9 remains, the outdoor board — not a Daikin indoor IFC.
Do not ‘reprogram’ this like ComfortBridge shared data.
H0
Comm / main control chip
lockout
Communication fault in the main control / EEPROM seating. Field: indoor–outdoor handshake and the outdoor board itself.
Dedicated comm cable BVA↔BOVA landed on the comm terminals — not the 24 V stat cable.
EEPROM chip fully seated / not backwards on boards that have a plug-in chip.
L1–L2 in range. H0 that survives a good comm cable and good power is the outdoor board.
H8
Pressure transducer
lockout
Suction PT failed or disagrees with gauges.
PT wiring. Idle PT vs manifold (±50 psi class on IDS).
Supply ~5 VDC on the transducer reference. Bad PT vs bad board.
P0
High outdoor coil temp
lockout
T3 outdoor-coil overtemp.
Outdoor coil and inverter heat sink clean. Fan running (see E6).
T3/TF readings in the parameter list.
P1
High pressure switch
lockout
HPS opened (airflow, overcharge, restriction, or failed switch).
Outdoor fan and coil. Indoor filter/coil.
HPS (2 yellow leads on IDS) ohms closed when idle and cool.
Charge is weigh-in / Bosch subcooling chart — not piston SH.
P2
Low pressure / heating discharge SH
lockout
Low-pressure protection in cool, or high discharge superheat protection in heat (IDS: <44 psi for 5 min cool; high discharge SH band in heat).
Service valves open. Indoor blower on a cool call; outdoor fan on a heat call.
Weigh-in. Restriction / TXV / drier. Then the PT (H8) before you add gas.
P3
Compressor overcurrent
lockout
Inverter current out of band (tonnage-specific trip on the IDS card).
Valves open, coils clean, outdoor fan running, outdoor <125°F.
Overcharge and a locked compressor both P3 — weigh-in and windings before you order a drive.
P4
High compressor discharge temp
lockout
T5 overtemp (IDS trips in steps up to a 230°F-class shutdown).
Weigh-in / Bosch chart (undercharge is the usual P4).