Bryant

135SAN

AC · Legacy / Comfort · single-stage contactor

Bryant Legacy / older Comfort single-stage condensing unit (135SAN / 134SAN / 114C / 113A / 126BNA). Contactor + dual cap. Same physics as Carrier 24ACC6. Still everywhere.

Not 146SAN Preferred InteliSense. Not 148TAN two-stage. Not 191VAN inverter.

Walk this in Diagnose

This plate

Stages
Single-stage · one Y
Control
24V Y/C to the contactor
Sister
Carrier 24ACC6 / 24ABB3 / 24SCA5

This board

Contactor + fan — no outdoor PCB to interrogate

  • No L-codes. Indoor 31 is the furnace.
  • Dual-cap FAN and HERM both matter.

Sequence

  1. Y. Indoor stat Y → 24 VAC across outdoor C and contactor coil. Contactor pulls in → compressor + outdoor fan on the dual cap.
  2. HPS. High-pressure switch opening drops the coil. Contactor drops. No inverter alarm, just silence or chatter.
  3. Charge. Piston indoor: set by superheat. TXV indoor: set by subcooling. Rating-plate weigh-in is a starting point, not the Greenspeed-only method.

Faults on this IFC

  • HPS

    High pressure switch open

    lockout

    Outdoor HPS opened — coil circuit is dead. Not an inverter pressure fault and not an L-code.

    • HPS continuity, reset if manual, wiring in series with the coil.
    • Outdoor airflow: dirty coil, bent fins, fan not running (see ODF / cap).
    • Overcharge or non-condensables — confirm indoor metering before you recover (SH vs SC).
    • Do not treat this as a 25VNA drive trip.
  • ODF

    Outdoor fan fail

    warn

    Fan not turning. Compressor may still run and then HPS.

    • Dual-cap FAN section µF vs sticker. A good HERM and a dead FAN is the usual Comfort call.
    • Fan motor ohms / ground, blade clearance, capacitor wiring (C / FAN / HERM).
    • Not an inverter fan module — there isn’t one.
  • Contactor

    Contactor / coil

    warn

    Will not pull, chatters, or is welded.

    • 24 VAC at the coil under a Y call. Low voltage = long stat wire, weak indoor transformer, or a furnace 24 (fuse) problem.
    • Coil ohms / burned turns. Pitted or welded points — replace, do not file and leave.
    • Chatter: low 24V, bad coil, weak transformer — not an inverter ramp.
  • Cap

    Dual run capacitor

    warn

    HERM and/or FAN section out of rating. Single-stage Comfort dies this way all summer.

    • Both sections vs microfarad rating, not just one.
    • Bulged can, open bleed, wrong replacement (single vs dual, voltage).
    • Hard-start add-ons do not fix a dead FAN section.
  • Charge

    Charge (SH piston / SC TXV)

    warn

    Wrong charge method is as common as wrong charge.

    • Indoor piston: charge by superheat. Indoor TXV: charge by subcooling.
    • Do not use Greenspeed weigh-in-only as the only method unless the factory TXV rating plate on THIS outdoor says so. Most 24ACC are piston/TXV conventional.
    • Line-set length and indoor coil match still matter. Weigh-in after a repair, then finish on SH or SC.

Workflows

No cool, 135SAN / 114C

Indoor running, outdoor dead.

  1. 24 VAC at the contactor coil.
  2. Dual cap, then 410A SH (piston) or SC (TXV).
  3. This is not 191VAN. There is no drive.

Test points

Contactor coil
Stable ~24 VAC on Y. Chatter = voltage, coil, or HPS. No ABCD to probe.
Dual cap
HERM and FAN both within ~6% (or OEM) of the stamped µF.
Charge
SH target on piston indoor; SC target on TXV indoor. Weigh-in is a start, not a Greenspeed-only finish.
HPS
Closed at rest. Open under high head = airflow/charge, not an inverter L-code.

Gotchas

  • 114C / 113A / 126BNA search here. Preferred 146SAN is the newer single-stage.

Related plates