Carrier Performance two-stage air conditioner. Y1/Y2, two-stage scroll, InteliSense-capable on late boards. Not Infinity ABCD and not a single-stage 24ACC6.
Not 24VNA6 / 26VNA1 (inverter, no Y2). Not 24ACC6 / 26SCA5 (single-stage, one Y). Not 26TPA8 (R-454B two-stage).
24V Y1/Y2. InteliSense when paired with a participating stat
Refrigerant
R-410A on this generation
Sister
Bryant 148TAN / 187B (Preferred / Evolution two-stage cousins — different bus on 187B)
This board
Two-stage outdoor — Y1/Y2, not Infinity drive
No inverter L-codes. If you see them, you are on 24VNA6.
High stage is Y2 at the outdoor. A single-stage stat never pulls high.
HPS in the coil circuit on typical Performance wiring.
Sequence
Y1. Low-stage compressor. Indoor blower on low/mid cool.
Y2. High-stage. Head and SC should rise.
HPS. Opens the coil. Silence or chatter — not an L-code.
Faults on this IFC
HPS
High pressure switch open
lockout
Outdoor HPS opened — coil circuit is dead. Not an inverter pressure fault and not an L-code.
HPS continuity, reset if manual, wiring in series with the coil.
Outdoor airflow: dirty coil, bent fins, fan not running (see ODF / cap).
Overcharge or non-condensables — confirm indoor metering before you recover (SH vs SC).
Do not treat this as a 25VNA drive trip.
ODF
Outdoor fan fail
warn
Fan not turning. Compressor may still run and then HPS.
Dual-cap FAN section µF vs sticker. A good HERM and a dead FAN is the usual Comfort call.
Fan motor ohms / ground, blade clearance, capacitor wiring (C / FAN / HERM).
Not an inverter fan module — there isn’t one.
Contactor
Contactor / coil
warn
Will not pull, chatters, or is welded.
24 VAC at the coil under a Y call. Low voltage = long stat wire, weak indoor transformer, or a furnace 24 (fuse) problem.
Coil ohms / burned turns. Pitted or welded points — replace, do not file and leave.
Chatter: low 24V, bad coil, weak transformer — not an inverter ramp.
Cap
Dual run capacitor
warn
HERM and/or FAN section out of rating. Single-stage Comfort dies this way all summer.
Both sections vs microfarad rating, not just one.
Bulged can, open bleed, wrong replacement (single vs dual, voltage).
Hard-start add-ons do not fix a dead FAN section.
Charge
Charge (SH piston / SC TXV)
warn
Wrong charge method is as common as wrong charge.
Indoor piston: charge by superheat. Indoor TXV: charge by subcooling.
Do not use Greenspeed weigh-in-only as the only method unless the factory TXV rating plate on THIS outdoor says so. Most 24ACC are piston/TXV conventional.
Line-set length and indoor coil match still matter. Weigh-in after a repair, then finish on SH or SC.
Workflows
24TPA7 stuck on low
Runs but never gets cold enough on a design day.
Y2 at the outdoor under a 2-cool call. Missing Y2 is a stat / indoor IFC / wire issue, not a weak compressor.
Then SC on the TXV indoor. Two-stage charge is not a 24ACC6 single-stage shortcut.
This is not 24VNA6. There is no drive to reset.
Identify 24TPA7 vs 24ACC6 vs 24VNA6
Invoice just says Carrier AC.
One Y / one contactor / dual cap = 24ACC6 Comfort.
Y1 and Y2 / two-stage scroll = 24TPA7 (this plate).
No contactor + ABCD + inverter = 24VNA6.
Test points
Contactor coil
Stable ~24 VAC on Y. Chatter = voltage, coil, or HPS. No ABCD to probe.
Dual cap
HERM and FAN both within ~6% (or OEM) of the stamped µF.
Charge
SH target on piston indoor; SC target on TXV indoor. Weigh-in is a start, not a Greenspeed-only finish.
HPS
Closed at rest. Open under high head = airflow/charge, not an inverter L-code.
Gotchas
InteliSense does not turn this into Infinity ABCD.