Daikin
DX13SA
AC · Single-stage · contactor + dual cap · R-410A
Daikin single-stage R-410A condensing unit (DX13SA / DX14SN). Contactor + dual cap. Not the current DC5SE R-32 box and not the FIT inverter.
Not DC5SE (R-32). Not DC9VS FIT. Not DX16TC two-stage.
Walk this in DiagnoseThis plate
- Refrigerant
- R-410A
- Stages
- Single-stage · one Y
This board
Contactor + fan · R-410A
- No outdoor 7-seg.
- Plate R-410A. DC5SE is R-32.
Sequence
- Y. 24 VAC at the contactor coil → compressor and outdoor fan. Indoor blower on the cool tap / G.
Faults on this IFC
No Y
Outdoor silent
warnNo 24 VAC at the contactor or the coil is open.
- Y and C at the outdoor. Indoor IFC / stat actually closing Y.
- Contactor coil ohms. Do not confuse a furnace lockout with a dead outdoor.
Hum / no start
Cap / start
lockoutCompressor hums, outdoor fan may run.
- Dual cap (fan and herm). Replace on values, not just a bulge.
- Hard-start only after the cap and windings are proven.
HPS
High pressure
lockoutOutdoor airflow, overcharge, or restriction.
- Fan running? Coil dirty? SC vs nameplate on a TXV coil.
LPS / freeze
Low pressure
lockoutCharge, indoor airflow, metering.
- Do not add gas on a frozen coil. Indoor filter/coil first.
Workflows
No cool, DX13SA
Indoor running, outdoor dead.
- 24 VAC at the contactor.
- Dual cap, then 410A SH or SC.
- DC5SE on the plate = other refrigerant.
Test points
- Charge
- Nameplate + line-set. SH on piston, SC on TXV.
- Cap
- Dual can. Fan and herm both in spec.
Gotchas
- DC5SE is the current R-32 single. Same cap story, wrong cylinder.