Current Lennox packaged rooftop class (Enlight L*T, Model L L*M). Same rooftop physics as Landmark — new unit controller and menus. Do not walk a Prodigy alarm list on this plate.
Not Landmark LGH / LCH Prodigy. Not a residential SLP99. Not 20 t+ Energence unless the plate says so.
G/E, E/E, HP depending on nomenclature. Read the plate.
This board
Lennox current rooftop unit controller (not Landmark Prodigy)
Alarms and economizer live on the unit display in this cabinet.
If you still see a Prodigy label, you are on an LGH — switch charts.
Sequence
Call. Occupied / G starts the indoor fan. Y1 is cool. W is gas heat. They are different boards in the same box.
Fan. Indoor blower must prove (belt, ECM, or current switch) before some controllers allow heat or cool.
Econo. If OA is below the economizer setpoint, the damper takes the cool call. Compressor stays off. That is not a dead contactor.
Cool. Y1 → unit board → compressor contactor through HPS (and LPS when equipped). OD fan on the same call or on head pressure.
Heat. W → IGC / ignition module: inducer → pressure switch → HSI → valve → flame rod → indoor blower on delay.
Faults on this IFC
Heat
Heat fail
lockout
Heat section did not prove.
Ignition path in the heat section. Unit display names the fail.
Cool
Cool fail
lockout
Mechanical cool did not prove.
Economizer first, then contactor / HPS.
Fan
Blower fail
lockout
Indoor fan did not prove.
Direct-drive ECM vs belt — this generation is often ECM.
HPS
High pressure
lockout
Discharge / liquid opened the high-pressure switch.
OD coil packed. Fan running and correct rotation on 3-phase.
Overcharge or non-condensables. Recirc over a low roof screen.
Indoor airflow so bad the refrigerant has nowhere to go — still an HPS trip.
LPS
Low pressure / freeze
lockout
Suction dropped out the low-pressure switch.
Charge / leak. Filters and indoor coil first — a dirty rooftop ices like a starved piston.
TXV / orifice. Economizer dumping 40 °F OA on the coil can look like a freeze-stat trip.
Do not add gas because suction is low.
Contactor
No start / hum
lockout
Y1 at the board, compressor not running.
24 VAC across the coil. Then dual cap (if this chassis has one) or VFD / two-stage unload.
3-phase: phase loss, reverse rotation. A scroll run backwards is loud and pumps no gas.
Internal overload. Let it cool; find why it overheated.
Fan prove
Indoor fan proving
lockout
Controller did not see blower current / pressure.
Belt off, ECM alarm, or current switch around the wrong lead.
VFD in limp mode on some Trane/VFD cabinets will not make the prove switch.
Do not jumper fan-prove and walk away — heat will fire into a dead blower.
Smoke
Smoke / firestat
hazard
Supply or return smoke detector, or a firestat, has the unit locked out.
Reset only after you know why it tripped. Welding and dirty returns nuisance-trip these.
The unit board sees this as a shutdown, not a refrigerant fault.
Phase
Phase loss / rotation
lockout
Three-phase monitor opened.
Measure all three legs at the disconnect and at the contactor.
Condenser fan and compressor rotation. Swap two legs only after you confirm this unit is 3-phase on the plate.
Econo
Economizer FDD
warn
Start here when the hood is the complaint. Title 24 FDD classes: sensor, not-economizing, false-economizing, damper not modulating, excess OA.
Read the module in THIS hood (JADE W7220 / W7212 / Reliatel / Prodigy / factory FDD). Type the live LCD string — examples: MA SENS ERR, OA SENS ERR, CO2 SENS ERR, ACT ERROR.
Blade vs command first. Then OA / RA / MAT vs a real thermometer. Then Y1 vs compressor.
Do not add refrigerant because mixed air is cold — that is often the damper.
MA ERR
MA SENS ERR (JADE LCD example)
warn
JADE two-line LCD: MA / SENS ERR. Mixed-air sensor failed. This one alarms immediately on power-up — others wait the 60-minute setup window.
Probe mixed air after the damper vs MAT on the module.
Ohm the MA sensor. Open/short or a sensor in the OA stream is this code.
MAT lying high keeps mechanical cool off. MAT lying low drives the damper shut or trips FREEZING.
OA ERR
OA SENS ERR (JADE LCD example)
warn
JADE LCD: OA / SENS ERR (or OA SYLK ERR). Outside-air thermistor failed or lost SYLK. Board thinks the roof is 20 °F or 120 °F.
Probe OA at the hood vs the module. Several degrees off is a sensor, not a damper.
Ohm / SYLK the OA sensor. Cut 2-wire in the hood is weekly.
Sun-soaked hood vs a shaded probe — measure the air the sensor sees.
RA ERR
RA SENS ERR (JADE LCD example)
warn
JADE LCD: RA / SENS ERR. Return-air thermistor failed. Differential / enthalpy changeover compares OA to RA.
Probe RA in the return vs the module.
A missing RA sensor on a differential setup looks like false economizing.
CO2 ERR
CO2 SENS ERR (JADE LCD example)
warn
JADE LCD: CO2 / SENS ERR. DCV sensor failed or the 0–10 V input is floating. Damper holds open; compressor never runs.
Read CO2 in an empty space. 400–800 ppm typical empty retail. 2000 ppm empty is a failed sensor.
0–10 V at the DCV input vs the sensor. If DCV is unused, set the input OFF on JADE.
ACT ERR
ACT ERROR (JADE LCD example)
warn
JADE LCD: ACT ERROR / ACT RANGE. Actuator did not follow command. Feedback pot off the shaft is the weekly.
Command min → 100%. 2–10 V (or 24 V floating) at the actuator vs blade travel.
Linkage on the shaft. Seized blades. A 24 V actuator on a 2–10 V output.
FREEZE
FREEZING (JADE LCD example)
warn
JADE LCD: FREEZING. Mixed air below the low-limit. Damper drives shut; mechanical cool may lock.
MAT vs a real probe. A failed MAT lying low is this, not a frozen DX coil.
Damper stuck open dumping 30 °F OA on the mixed-air sensor — walk ACT ERROR first.
True freeze: indoor airflow and charge after the damper is explained.
Not econ
Not economizing when it should
warn
OA is in the free-cooling window and the damper stayed shut. Title 24 FDD class.
Confirm OA really is below the high-limit / enthalpy changeover on THIS module (not a 55 °F guess).
Y1 present? Some modules will not economize without a cool call.
Min-position only, jammed blades, or a MAT low-limit holding the damper closed.
Mechanical cool running in 50 °F OA is this fault until the damper moves.
False econ
Economizing when it should not
warn
Damper open with OA above changeover. Space hot, high OA bills, or wet coil.
OA vs changeover setpoint. Sensor lying low (see OA T) is the usual.
Min position cranked to 40% on a small store. DCV failed high.
Power-fail default on some actuators is spring-open — they dump OA with 24 V lost.
Excess OA
Excess outdoor air
warn
Damper open past the commanded minimum with no economizer or DCV request.
Commanded position vs blade. Feedback saying 80% when the board asked 15% is actuator/linkage.
Barometric relief / power exhaust stuck open looks like excess OA at the space.
Unoccupied damper should go to the unoccupied minimum, often 0. A 24 V occupancy point stuck high holds min all night.
No mod
Damper not modulating
warn
Damper is two-position (0 or 100) instead of tracking 2–10 V. Title 24 FDD class.
2–10 V at the actuator while OA is in the window. 0 V or 24 V only = module output or a two-position actuator installed by mistake.
JADE set for 2-position vs modulating. Direct-coupled actuator vs a 24 V floating that someone landed on analog.
Stuck at 50% is a failed actuator, not ‘modulating.’
VFD
VFD / indoor-fan drive
lockout
The indoor fan is a drive, not a contactor + cap. Type the keypad string: oC, Uv, ov, GF, oH, PF.
Photograph the drive keypad before you cycle power. Yaskawa/ABB show oC / Uv / ov; EcoBlue / Reliatel may say fan fail instead.
Enable present? Speed reference present? Motor spinning and proving?
Do not throw a dual run cap at a VFD motor.
Enable
VFD enable missing
warn
Drive has line voltage but will not run — the unit board never enabled it.
24 VAC (or the digital enable this drive uses) at the enable terminals while G / occupied / heat / cool is on.
0 V enable with a live G = unit board output or a smoke/firestat shutdown still open.
Some EcoBlue / Reliatel cabinets enable on a board relay, not on G from the stat.
0-10V
VFD speed reference
warn
Drive is enabled but stays at min Hz or 0 because analog / serial speed is missing.
0–10 VDC at the speed-reference pair under a high-fan call. Typical occupied cool is not 10 V — check the unit-board fan table.
0 V with enable = broken analog wire, board analog dead, or the drive is set for a different reference (serial vs 0–10).
10 V at all times = board commanding 100%. High static / oC will follow.
oC
oC / OC — overcurrent
lockout
Keypad example: oC (Yaskawa) or OC. Output current trip. Locked rotor, dirty filters, or FLA set too low.
Spin the wheel by hand (power off). Debris, seized bearing, belt wrapped.
Total external static vs this blower table. A rooftop with 1.4" TES and a 0.8" motor is an oC waiting to happen.
FLA / motor-data parameters vs the motor nameplate. Do not raise FLA to hide a dirty coil.
Ramp-up too fast on a high-inertia wheel — lengthen accel before you change a drive.
Uv
Uv / LU — undervoltage
lockout
Keypad example: Uv (Yaskawa) or LU. DC bus dropped. Incoming power or a missing phase.
Three legs at the drive line terminals, under load. A single-phased 3-phase drive nuisances Uv / oC.
Do not ignore Uv on a 480 V roof with a 208 V drive, or the reverse.
ov
ov / OU — overvoltage
lockout
Keypad example: ov (Yaskawa) or OU. DC bus high. Usually regen on decel, not a new drive.
ov on shutdown = decel too fast; lengthen decel.
Incoming voltage high or a utility swell. Measure line first.
GF
GF — ground fault
hazard
Keypad example: GF. Drive sees current to ground on the motor leads.
Megger the motor with the drive disconnected. A wet rooftop motor after a rain is this code.
Cable from drive to motor — insulation rubbed through the curb or the fan deck.
Do not reset-and-run a GF. That is a grounded winding or a damaged VFD output.
oH
oH — heatsink overtemp
warn
Keypad example: oH. Drive thermal trip.
Drive fan spinning. Heat sink packed with roof lint.
Cabinet door left off in the sun is not always the drive — still clean the sink.
PF
PF — input phase loss
lockout
Keypad example: PF. Missing or imbalanced incoming phase.
L1 L2 L3 at the drive and at the disconnect. Tight lugs.
A rooftop fuse that opened one leg looks like a dead motor until you read PF.
Limp
VFD limp / min Hz — fan prove
warn
Drive is running too slow to close the prove switch, so the unit board reports fan fail. Reliatel example: Fan Fail with the drive still at min Hz.
Min-frequency / limp parameter vs the prove-switch setpoint (often ~0.07" on some Reliatel cabinets).
A dirty filter that drops the motor into current-limit limp will never make prove. Clean first.
Do not jumper the prove switch. Heat will fire into a near-dead blower.
Drain
Condensate / float
warn
Float switch or tripped condensate opened 24V.
Roof drain pan, trap, and the overflow to the roof — not a furnace collector.
A clogged pan on a curb soaks the deck. Fix the drain before the board.
Workflows
No cool, LGT
Space hot. Indoor fan may or may not be running.
This is a packaged rooftop. There is no split outdoor to walk to. Cool, heat, and the economizer share this curb.
Prove 24 VAC Y1 at the unit controller under a cool call. Occupied/G first — a unoccupied shutdown looks like a dead compressor.
Look at the economizer. Damper commanded open on cold OA? Mixed-air sensor lying? Compressor off by design is not a failed contactor.
If the board is actually asking for mechanical cool: 24 VAC at the contactor coil, then cap, then rotation on 3-phase, then HPS/LPS, then pressures.
Roof condenser: cottonwood, cardboard, hail guards packed with lint. High head here is dirt until proven otherwise.
No heat, LGT
Cool works or the space is cold on a W call.
Heat is the IGC / ignition module in the heat section — not the economizer board and not the compressor contactor.
24 VAC W at the IGC. Then inducer. Then the pressure-switch circuit. Then HSI glow. Then 24 VAC at the valve during trial. Then µA.
Count the IGC LED (or the unit-controller heat alarm). The sticker in THIS heat compartment is the book — revisions differ.
Limit / rollout are in series with the valve. High static, dirty filters, and a slipping belt trip limit on a rooftop faster than a basement furnace.
Do not jump a rollout. Find why the heat exchanger spilled.
Economizer, LGT
Building hot with the compressor off, or high OA bills, or mixed air wrong.
Read the module in THIS hood (JADE W7220 / W7212 / Reliatel / Prodigy / factory FDD). Write the live alarm — OA T, MAT, CO2, ACT, not-economizing, excess OA.
Blade vs command. Stuck open = overventilation and no mechanical cool. Stuck closed = no free cooling.
OA, RA, MAT vs a real thermometer. A lying OA sensor is the usual ‘not economizing’ / ‘false economizing.’
CO2 / DCV failed high holds the damper open. Min position is a setup, not 40%.
Title 24 FDD classes: sensor fail, not economizing when it should, economizing when it should not, damper not modulating, excess OA. Walk that list before a compressor.
High static / limit / belt, LGT
Limit trips, noisy cabinet, or poor airflow on a rooftop.
Total external static vs the blower table for THIS tonnage and heat size. Rooftop ductboard and dirty 2" filters are the usual miss.
Belt deflection and sheave alignment on belt units. Direct-drive ECM / VFD: tap / 0–10 V / unit-controller speed, not a dual cap.
Evap coil from the access panel — rooftop coils load with insulation and roof grit.
Heat section: temperature rise vs the rating plate. Overfire and low airflow both trip the same limit.
VFD / indoor fan, LGT
Fan prove, no airflow, drive display in alarm, or EcoBlue / Reliatel limp.
Read the drive keypad (OC, LU, OU, GF, OH) or the unit-board fan alarm before you cycle 24V.
Enable 24 VAC at the drive while G / occupied / a heat or cool call is on. No enable is the unit board, not the motor.
0–10 VDC speed reference under a high-fan call. 0 V with enable = analog wire or board, not a bad VFD.
OC: spin the wheel, measure TES, then FLA vs the motor plate. Do not raise FLA to hide a dirty roof.
Limp / min Hz that will not close the prove switch — clean filters and raise min, do not jumper fan-prove.
Test points
Y1 at controller
~24 VAC on a mechanical-cool call. 0 V if the economizer is satisfying.
Contactor coil
~24 VAC when the board commands the compressor. 0 V with Y1 present = board or lockout.
HPS / LPS
Closed in the run circuit when pressures are legal. Open is a switch or a real pressure problem.
3-phase
All three legs, correct rotation. Nameplate voltage ±10%.
TES / static
External static vs the blower table for this tonnage — rooftops run dirty.
OA / MAT
Module reading vs a real thermometer at the hood and in the mixed-air stream.
Actuator
2–10 V (or 24 V floating) tracks commanded damper. Blade moves with voltage.
VFD enable
~24 VAC (or this drive’s digital enable) while G / occupied / a call is on.
VFD 0–10 V
Analog speed present under a high-fan call. 0 V with enable is a board/wire, not a motor.
IGC W
~24 VAC on a heat call.
Flame rod
µA DC per the IGC sticker in this heat section. Rising while running.
Manifold
Rating plate wins. Roof gas piping often starves high-fire.
Gotchas
Packaged rooftop — one nameplate. Do not pick a split furnace + condenser pair for this call.
Economizer can run the building without the compressor. Look at the damper before you condemn a scroll.
3-phase rotation and a roof full of lint are the first two measurements, not a charge chart.
Type the live string in Diagnose. Examples: IGC 2-flash / 8-flash, JADE MA SENS ERR / ACT ERROR, Reliatel Fan Fail, VFD oC / Uv / GF. The sticker or LCD in THIS cabinet is the book.
Related plates
lennox-lgh — Landmark Prodigy predecessor. Still most of the roofs.