York

YXT

AC · Affinity · two-stage mid

York Affinity YXT two-stage air conditioner. Mid-tier Affinity — two-stage scroll, not the YXV inverter and not the LX YC2F.

Not YXV inverter. Not YC2F LX two-stage. Not YC2E single-stage.

Walk this in Diagnose

This plate

Stages
Two-stage · Y1/Y2 or Affinity communicating per vintage
Control
Read the outdoor diagram — some YXT talk Hx / Affinity, some land 24V

This board

Affinity two-stage outdoor

  • Not the YXV inverter drive.
  • If the indoor is a communicating Affinity furnace, confirm this outdoor actually talks. Many land Y1/Y2.

Sequence

  1. Low. Low-stage scroll.
  2. High. High-stage. Head and SC should rise.

Faults on this IFC

  • HPS

    High pressure switch open

    lockout

    Outdoor HPS opened — coil circuit is dead. Not an inverter pressure fault and not an L-code.

    • HPS continuity, reset if manual, wiring in series with the coil.
    • Outdoor airflow: dirty coil, bent fins, fan not running (see ODF / cap).
    • Overcharge or non-condensables — confirm indoor metering before you recover (SH vs SC).
    • Do not treat this as a 25VNA drive trip.
  • ODF

    Outdoor fan fail

    warn

    Fan not turning. Compressor may still run and then HPS.

    • Dual-cap FAN section µF vs sticker. A good HERM and a dead FAN is the usual Comfort call.
    • Fan motor ohms / ground, blade clearance, capacitor wiring (C / FAN / HERM).
    • Not an inverter fan module — there isn’t one.
  • Contactor

    Contactor / coil

    warn

    Will not pull, chatters, or is welded.

    • 24 VAC at the coil under a Y call. Low voltage = long stat wire, weak indoor transformer, or a furnace 24 (fuse) problem.
    • Coil ohms / burned turns. Pitted or welded points — replace, do not file and leave.
    • Chatter: low 24V, bad coil, weak transformer — not an inverter ramp.
  • Cap

    Dual run capacitor

    warn

    HERM and/or FAN section out of rating. Single-stage Comfort dies this way all summer.

    • Both sections vs microfarad rating, not just one.
    • Bulged can, open bleed, wrong replacement (single vs dual, voltage).
    • Hard-start add-ons do not fix a dead FAN section.
  • Charge

    Charge (SH piston / SC TXV)

    warn

    Wrong charge method is as common as wrong charge.

    • Indoor piston: charge by superheat. Indoor TXV: charge by subcooling.
    • Do not use Greenspeed weigh-in-only as the only method unless the factory TXV rating plate on THIS outdoor says so. Most 24ACC are piston/TXV conventional.
    • Line-set length and indoor coil match still matter. Weigh-in after a repair, then finish on SH or SC.

Workflows

Identify YXT vs YC2F vs YXV

Invoice just says York two-stage or Affinity.

  1. YXV = inverter, no discrete high stage, weigh-in.
  2. YXT = Affinity two-stage (this plate).
  3. YC2F = LX two-stage, typically straight 24V Y1/Y2.

Test points

Contactor coil
Stable ~24 VAC on Y. Chatter = voltage, coil, or HPS. No ABCD to probe.
Dual cap
HERM and FAN both within ~6% (or OEM) of the stamped µF.
Charge
SH target on piston indoor; SC target on TXV indoor. Weigh-in is a start, not a Greenspeed-only finish.
HPS
Closed at rest. Open under high head = airflow/charge, not an inverter L-code.

Gotchas

  • Affinity on the badge is not automatically the inverter.