Models
Daikinfurnace

DM96VC

Daikin ComfortNet / Daikin One · two-stage · communicating VS · 96%

Daikin-badge ComfortNet / Daikin One 96% two-stage with a communicating variable-speed blower and a triple 7-segment IFC. Same factory family as Amana AMVC96 / Goodman GMVC96. Use the ComfortBridge E / b / d set (E0–EA, b0/b1/b2, d0) — not the AR9T96 E-only 24V card.

Not Amana AR9T96 / Goodman GR9T96 (single 7-seg E0–E9, 9-speed taps, no b/d codes). Not DM97MC (modulating percent capacity, not two-stage). Not a VRV indoor. A Daikin One on a 24V GR9T96 is a mis-pair.

AFUE

Two-stage 96% condensing

Blower

Communicating VS ECM · CFM requested on the serial harness, not taps

Control

ComfortNet / ComfortBridge IFC · triple 7-segment + menu buttons

Bus

ComfortNet / Daikin One data pair. 24V fallback exists on some IFCs

Staging

Two-stage valve · two-speed inducer · dual pressure switches (E1/E2 vs E8/E9)

Sister SKU

Amana AMVC96 / Goodman GMVC96 — same IFC family, Daikin badge

This board

ComfortNet / Daikin One IFC · triple 7-segment

  • Three digits. Status words (idle, Ht1, Ht2, CF, dF) are not faults. Do not replace a board because it says Ht1.
  • Faults are the ComfortBridge set: E0–EA for gas/safety, b0/b1/b2 for the serial blower, d0 for network/shared data. EE is bus or internal depending on board date — believe the Daikin One English plus this door card.
  • This is not AR9T96 E-only. AR9T96 has no b0/b1/b2/d0 and will not talk Daikin One.
  • Learn / menu buttons step CFM, staging, and last faults. A setup screen is not a lockout.

IFC menu fault history (not the AR9T96 2-second hold). Daikin One / ComfortNet thermostat Last Events names the fault in English. Write the exact characters (E2, b1, d0) plus any status word.

Universal swap

No universal

Daikin communicating — same world as ComfortBridge. No WR/ICM/Honeywell universal.

White-Rodgers

ICM

Honeywell

  • Any 50A55-843 / 50A65-843 / 50M56U-843 / 50M56X-843 / S9200U1000 universal — those are conventional 24V HSI, not this data bus.
  • ICM280 / 2811 / 2810 / 282B — wrong IFC family.
  • Amana AR9T96 PCBBF132. AMVC96 card assumed without matching the Daikin memory.

After you pull the dead card

  1. 1OEM Daikin ComfortNet / Daikin One IFC. Pair the communicating control.

Field wiring

Written landings for Daikin DM96VC. Not a factory schematic.

ComfortBridge / ComfortNet furnace
1 / 2 data — or 24VGas furnace

Goodman / Amana / Daikin communicating two-stage. Outdoor on 1 and 2 when the outdoor talks. A 24V GSX16 still wants Y, not data.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC120V
  2. 2Call. Data pair or 24V W → IFCBus or 24V
  3. 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
  4. 4Ignite. IFC → HSI → valve120V igniter
  5. 5Blow. IFC → serial ECMNo tap, no cap

This indoor

ComfortNet 96% two-stage. P1/P2 / 1/2 to DZ or FIT.

Communicating outdoor

GSXC / ASXC / GXV / DZ / FIT on the same bus. CoolCloud or Daikin One at the wall.

CoolCloud / Daikin One

Menus on the indoor. Do not put R/C on 1 and 2.

  • 1DataData
  • 2DataData

ComfortBridge / ComfortNet IFC

Memory card must match THIS cabinet (ARVT96 card is not AMVC96).

  • 1Data to outdoorData
  • 2Data to outdoorData
  • R24V accessories24V
  • CCommon24V

Landing

  • DataIFC 1outdoor 1 · IFC 2outdoor 2

    Data. Polarity matters.

24V outdoor on this IFC

GSX16 / GLXS4B / any contactor outdoor. Land Y. Leave 1/2 empty.

Conventional stat (allowed)

W1/W2/Y/G on the IFC 24V strip. Not on 1/2.

  • RHot24V
  • CCommon24V
  • W1Heat24V
  • YCool24V
  • GFan24V

Landing

  • 24VStat YIFC Youtdoor Y

    ~24 VAC. Data wire is a miswire.

IFC harness — communicating two-stage

Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.

Transformer + fuse

24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.

  • L1 / N120VLine
  • R / C24V strip24V
  • FUSEOn the IFC24V

24V safety chain

Limit / rollout / door still open the heat path. Codes are on THIS IFC language.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + dual PS

Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.

  • IND LO/HITwo-speed inducerLine
  • LPSLow prove24V
  • HPSHigh prove24V

HSI + two-stage valve

Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.

  • HSI120V igniterLine
  • MV / HV24V low / high solenoids24V
  • FLAMEµA DC24V

Serial variable-speed ECM

IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.

  • SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
  • CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V

Landing

  • LineCallIFCinducerprove

    Low then high

  • LineIFCHSIvalve

    120V igniter, 24V or serial valve

  • 24VFlame rodIFC

    µA DC

  • DataIFCserial blower

    No F-taps. No PSC cap.

Prove it

  • Indoor family first. Communicating outdoor = 1/2. Contactor outdoor = Y.
  • Memory card / CoolCloud sees THIS furnace.

Do not

  • Do not drop an ARVT96 card into AMVC96 or the other way around.
  • Do not land 1/2 on a GR9T96.

1 and 2 are the published ComfortBridge / ComfortNet pair.

Sequence

  1. 1

    Call

    Daikin One / ComfortNet requests heat capacity. On 24V fallback, W1/W2 behave like a two-stage furnace but CFM still comes from the IFC tables — no taps.

  2. 2

    Inducer / PS

    Low inducer → low PS (E1 stuck closed, E2 open). High inducer → high PS (E8 stuck closed, E9 open). Same physics as AR9T96, ComfortBridge presentation.

  3. 3

    HSI / valve

    Nitride igniter, two-stage valve, flame rod µA. Failures stack to E0. Open igniter / no-ground is E7. Weak flame is E6.

  4. 4

    Blower

    Serial ECM. b0 = not running, b1 = lost comms, b2 = HP / shared-data mismatch. A tap jumper from a GR9T96 motor will not run this blower.

  5. 5

    Network

    d0 = shared data not on the network (memory card / learn). Outdoor or stat dropping the bus is EE / d-code territory, not a furnace E2.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

idle / Ht1 / Ht2 / CF

Status, not a fault

info

Ready, low heat, high heat, or continuous-fan CFM on the triple display.

  1. 1 Confirm this is not a fault

    On the Daikin DM96VC this readout (idle / Ht1 / Ht2 / CF) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the Daikin DM96VC IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: Do not change the board because it says Ht1 or CF.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch ComfortNet / Daikin One IFC · triple 7-segment through one cycle and write the first real fault that replaces this status word.

    Expect: Call: Daikin One / ComfortNet requests heat capacity. On 24V fallback, W1/W2 behave like a two-stage furnace but CFM still comes from the IFC tables — no taps.

E0

Retry / recycle lockout

lockout

Failed to sense flame after the retry limit (typically three trials). One-hour-class auto retry.

  1. 1 Airflow before you touch the limit

    On Daikin DM96VC a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Watch one full try: inducer, HSI, valve, flame, µA.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Daikin DM96VC blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Gas supply and manifold low then high.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Do not keep resetting — find which step dies.

    Expect: Manifold on plate. Limit closed when cool.

E1

Low-stage PS stuck closed

lockout

Low-fire pressure switch is made with the inducer off.

  1. 1 Unplug the switch with the inducer off

    On Daikin DM96VC this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the LPS. Code change = switch or water-filled hose.

    Expect: Code changes when the harness is open.

    If fail: Wrong switch, or the IFC input is shorted.

    If pass: Switch/hose path. Go to step 2.

  2. 2 Water in the hose vs a welded switch

    Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Do not confuse with AR9T96-only extras (Ed / En / EEJ) — those are the 24V 9-speed card.

    Expect: Hose empty. Switch opens with no draft.

  3. 3 IFC input last

    If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Daikin DM96VC IFC input is shorted. Do not keep swapping switches.

    Expect: Known-good open switch + open harness = code gone. If not, IFC.

E2

Low-stage PS open

lockout

Inducer on low, low-fire switch never closes. Classic 96% trap / PVC.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Daikin DM96VC active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer 120 VAC and spinning.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Collector, trap, PVC intake/exhaust, wind.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. LPS hose on the low tap, not teed to high.

    Expect: LPS / HPS: Two NO switches, two hoses. E1/E2 vs E8/E9.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

E3

Open limit / rollout circuit

warn

Primary, auxiliary, or rollout opened. ComfortNet bundles these on E3 — inspect rollout before you treat it as a dirty filter.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Daikin DM96VC rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Heat CFM in the IFC menu, not a tap. Filter, coil, return, static.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Daikin DM96VC is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Rollout portion: exchanger / burners / flue. Manual reset. Recurring rollout is hazard.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

E4

Flame when no flame should be present

hazard

Rod sees flame with the valve de-energized.

  1. 1 Shut the gas cock first

    On Daikin DM96VC the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. Leaking valve — replace, do not jump.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Flame-sense short or IFC input.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

E5

Open fuse

warn

24 V automotive fuse on the IFC is open.

  1. 1 Find the 24 V short before you replace the fuse

    On Daikin DM96VC an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. Short on W/Y/G, humidifier, EAC, or the valve harness.

    Expect: Fuse out. 24 V transformer still good. Harness isolated.

  2. 2 Replace the fuse with the harness off

    New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC). Unplug the tstat/data harness and replace the fuse. If it blows again the short is on-board or in the cabinet.

    Expect: Fuse holds with harness off. Dies when the shorted lead lands.

  3. 3 If it blows with the harness off

    Short is on the Daikin DM96VC IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.

    Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.

E6

Low flame signal

warn

Flame present, µA below the IFC threshold.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Daikin DM96VC during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod, chassis ground, manifold / LP conversion.

    Expect: Flame rod: µA per this IFC sticker, not the AR9T96 card.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. µA per this door card, not the AR9T96 sticker.

    Expect: Manifold on the rating plate. Solid burner-box ground.

  3. 3 Prove it is not a switch opening

    Watch the live Daikin DM96VC display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

E7

Igniter / no-ground

lockout

Open or cracked HSI, bad igniter connection, or missing equipment ground.

  1. 1 Ohms at the igniter, then at the IFC

    On Daikin DM96VC measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Igniter ohms and 120 VAC during warm-up.

    Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. IFC and burner-box ground.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

E8

High-stage PS stuck closed

lockout

High-fire switch is made with the inducer not on high. Furnace may stay on low.

  1. 1 Unplug the switch with the inducer off

    On Daikin DM96VC this code is the switch made when the inducer is not running. Unplug that switch only. This is the second switch — not E1.

    Expect: Code changes when the harness is open.

    If fail: Wrong switch, or the IFC input is shorted.

    If pass: Switch/hose path. Go to step 2.

  2. 2 Water in the hose vs a welded switch

    Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Welded HPS or water in the high hose.

    Expect: Hose empty. Switch opens with no draft.

  3. 3 IFC input last

    If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Daikin DM96VC IFC input is shorted. Do not keep swapping switches. W2 shorted so the IFC thinks it is already on high.

    Expect: Known-good open switch + open harness = code gone. If not, IFC.

E9

High-stage PS open

lockout

Inducer on high, high-fire switch never closes. Runs on low, will not go high.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Daikin DM96VC active code. Write E9. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer actually changes speed?

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. HPS hose on the high tap only.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Vent capacity / condensate only under high fire.

    Expect: LPS / HPS: Two NO switches, two hoses. E1/E2 vs E8/E9.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

EA

Reversed polarity / ground

lockout

115 V L1/N reversed, 24 V transformer reversed, or poor chassis ground.

  1. 1 Hot and neutral at the IFC, not the disconnect

    On Daikin DM96VC polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC, not just the disconnect.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Burner box ground screw.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

EE

Bus / internal

lockout

ComfortNet / Daikin One data dropped, or (on some dates) no 115 V / internal IFC fault. Stat English tells you which.

  1. 1 Measure at the IFC under load

    On Daikin DM96VC line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. Data pair polarity and splices. This is not 24 V Y.

    Expect: Voltage in the rating-plate window under load.

  2. 2 Drop, breaker, and the whip

    Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. Only one communicating master. Leftover data wires landed on R/C after a 24V conversion.

    Expect: Minimal drop. Tight lugs. Correct breaker size.

  3. 3 Transformer 24 V last

    If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call. Door switch, disconnect, and 115 V at the IFC if the display is dark / EE on power-up.

    Expect: 24 V holds under load. Line stays in window.

b0

Blower motor not running

lockout

IFC commanded the serial ECM and does not see it run.

  1. 1 Reseat the serial plug

    On Daikin DM96VC this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. 14-pin harness seated at motor and IFC.

    Expect: Plug fully seated both ends. Correct motor for this cabinet.

  2. 2 Power and the data pair at the motor

    Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. Wheel rub, open inductor on 3/4–1 HP motors, dead ECM.

    Expect: Line voltage present. Data pair not shorted to chassis.

  3. 3 Motor vs IFC serial driver

    Known-good motor still throws this code = Daikin DM96VC IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC. Do not install a GR9T96 tap motor.

    Expect: One clean CFM request after a known-good pair.

b1

Blower motor communication

lockout

IFC lost serial comms with the circulator.

  1. 1 Reseat the serial plug

    On Daikin DM96VC this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. Harness, motor module, IFC serial output.

    Expect: Plug fully seated both ends. Correct motor for this cabinet.

  2. 2 Power and the data pair at the motor

    Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. Power-cycle once after the harness is proven. Then motor vs board.

    Expect: Line voltage present. Data pair not shorted to chassis.

  3. 3 Motor vs IFC serial driver

    Known-good motor still throws this code = Daikin DM96VC IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC.

    Expect: One clean CFM request after a known-good pair.

b2

Blower HP / shared-data mismatch

lockout

Connected motor horsepower does not match the shared data set.

  1. 1 Read the plug / card on THIS cabinet

    On Daikin DM96VC the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Wrong replacement motor.

    Expect: Plug / card part matches the rating plate and the replacement control bulletin.

  2. 2 Reseat, then confirm the menu

    Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Memory card / shared data for THIS DM96VC cabinet — a card from a different input or an AMVM97 will b2.

    Expect: IFC recognizes the plug. No size-mismatch code.

  3. 3 Do not run it mismatched

    A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.

    Expect: One clean sequence on the correct identity.

d0

Data not yet on network

lockout

Communicating pair is wired and the IFC has no shared data (new board, missing memory card, learn not done).

  1. 1 Read the plug / card on THIS cabinet

    On Daikin DM96VC the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Memory card / ComfortBridge learn for this SKU.

    Expect: Plug / card part matches the rating plate and the replacement control bulletin.

  2. 2 Reseat, then confirm the menu

    Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Outdoor and Daikin One actually on the bus? d0 on a standalone 24V job means someone enabled communicating when the network is empty.

    Expect: IFC recognizes the plug. No size-mismatch code.

  3. 3 Do not run it mismatched

    A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint. Do not confuse with E0 (ignition lockout).

    Expect: One clean sequence on the correct identity.

Workflows

DM96VC vs a 24V Daikin 96%

First minute on site.

  1. 1 Prove the call and the live code

    Triple 7-seg + serial motor + Daikin One / ComfortNet = this page. Use E/b/d, not AR9T96 E-only.

    Expect: Write whatever ComfortNet / Daikin One IFC · triple 7-segment is showing. IFC menu fault history (not the AR9T96 2-second hold). Daikin One / ComfortNet thermostat Last Events names the fault in English. Write the exact characters (E2, b1, d0) plus any status word.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Single 7-seg E0–E9 + tap motor = Amana AR9T96 / Goodman GR9T96 even if the door says Daikin.

    Expect: Inducer / PS: Low inducer → low PS (E1 stuck closed, E2 open). High inducer → high PS (E8 stuck closed, E9 open). Same physics as AR9T96, ComfortBridge presentation.

  3. 3 Confirm with a number, then the next part

    Percent-capacity / modulating valve / AMVM-style cousin = DM97MC. Leave this two-stage page.

    Expect: Data pair: OEM ComfortNet / Daikin One voltage and polarity. Never 24 VAC between the data pins. · Motor harness: Serial ECM, fully seated. No tap plugs. b2 means the shared data / HP does not match.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

No heat on Daikin One

Stat shows a call, furnace idle or E/b/d.

  1. 1 Prove the call and the live code

    Photograph the triple display and the Daikin One event before touching wires.

    Expect: Write whatever ComfortNet / Daikin One IFC · triple 7-segment is showing. IFC menu fault history (not the AR9T96 2-second hold). Daikin One / ComfortNet thermostat Last Events names the fault in English. Write the exact characters (E2, b1, d0) plus any status word.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Communicating or 24V fallback? That changes every next step.

    Expect: Inducer / PS: Low inducer → low PS (E1 stuck closed, E2 open). High inducer → high PS (E8 stuck closed, E9 open). Same physics as AR9T96, ComfortBridge presentation.

  3. 3 Confirm with a number, then the next part

    If communicating: data pair, d0/EE, one master, outdoor crashing the bus. If 24V fallback: W at the IFC, then E2 trap / E7 igniter / E0 retries as a two-stage 96%. Motor silent with b0/b1/b2 → harness, shared data, static — not an AR9T96 tap.

    Expect: Data pair: OEM ComfortNet / Daikin One voltage and polarity. Never 24 VAC between the data pins. · Motor harness: Serial ECM, fully seated. No tap plugs. b2 means the shared data / HP does not match.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

E2 / E9 draft on ComfortNet

Inducer runs, no prove, or low only.

  1. 1 Prove the call and the live code

    E2 is low-fire PS. E9 is high-fire PS. Same hoses as AMVC96, Daikin badge.

    Expect: Write whatever ComfortNet / Daikin One IFC · triple 7-segment is showing. IFC menu fault history (not the AR9T96 2-second hold). Daikin One / ComfortNet thermostat Last Events names the fault in English. Write the exact characters (E2, b1, d0) plus any status word.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Trap and PVC first. Communicating does not fix a drowned collector.

    Expect: Inducer / PS: Low inducer → low PS (E1 stuck closed, E2 open). High inducer → high PS (E8 stuck closed, E9 open). Same physics as AR9T96, ComfortBridge presentation.

  3. 3 Confirm with a number, then the next part

    Never tee the two switches. High-fire-only E9 after an E2 ‘fix’ is the high hose.

    Expect: Data pair: OEM ComfortNet / Daikin One voltage and polarity. Never 24 VAC between the data pins. · Motor harness: Serial ECM, fully seated. No tap plugs. b2 means the shared data / HP does not match.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Data pair

OEM ComfortNet / Daikin One voltage and polarity. Never 24 VAC between the data pins.

Motor harness

Serial ECM, fully seated. No tap plugs. b2 means the shared data / HP does not match.

Flame rod

µA per this IFC sticker, not the AR9T96 card.

LPS / HPS

Two NO switches, two hoses. E1/E2 vs E8/E9.

Gotchas

  • AR9T96 E-only techs miss b0/b1/b2/d0 and replace the gas valve for a motor/network fault.
  • DM97MC looks identical in the basement and is modulating — staging tests will lie.
  • Amana AMVC96 / Goodman GMVC96 are the factory twins. Same E/b/d set.
  • Daikin One on a GR9T96 24V indoor will never learn. That is a mis-pair, not a bad stat.

Related plates

Install this plate

Install DM96VC as Daikin ComfortNet / Daikin One two-stage VS. Same IFC family as AMVC96 / GMVC96.

Cat IV PVC · ComfortNet data pair · serial VS · dual PS E1/E2 vs E8/E9 · 24V fallback on some IFCs

Bus

  • Daikin One / ComfortNet pair. 24V fallback exists on some boards — CFM still from IFC tables.
  • Not a VRV indoor. Not AR9T96 / GR9T96 9-speed.

Vent

  • PVC, primed trap, two PS hoses. Communicating does not remove E8/E9 high-fire prove.

First fire

  1. 1Seat the shared-data card. Pair Daikin One if used. W1/Ht1 then W2/Ht2.

Do not on Daikin DM96VC

  • Do not apply DM97MC percent-fire setup.
  • Do not land this data pair on a GR9T96.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    warranty sheet

    Daikin furnace warranty

    Registered ComfortNet / Daikin One furnace warranty · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal