Goodman
GLXS4B AC · R-32 single-stage · contactor + dual cap
Current Goodman R-32 single-stage condensing unit (GLXS4B / GLXS4M / GLXS5B / GLXS3B). Contactor + dual cap, same physics as GSX16 — different refrigerant. A2L. Charge and recovery are R-32, not a 410A GSX16 top-off.
Not GSX16 / GSX14 (R-410A). Not GLXT7C (R-32 two-stage). Not GXV9S inverter. Not GSZC / GSZ heat pump.
Walk this in Diagnose This plate
Refrigerant R-32 (A2L). Recover / weigh on an R-32 machine. Do not mix 410A.
Stages Single-stage scroll · one contactor
Metering Indoor TXV / piston per the R-32 coil match — not a leftover 410A piston
Pair 24V Y from any conventional furnace / AHU
Sister SKU GLXS4M multi-family 1.5–3 t · GLXS5B 16.5 · GLXS3B 15 · Amana ALXS4B This board Contactor + fan — R-32 nameplate, no communicating outdoor PCB
No 7-seg on this outdoor. Indoor E2 is the furnace. HPS / LPS (when equipped) open the contactor coil. Rating plate says R-32. A 410A gauge set and a GSX16 charge chart are the wrong book. Sequence Y. 24 VAC at the contactor coil → compressor and outdoor fan. Indoor blower on the cool tap / G. Faults on this IFC No Y
Outdoor silent warn No 24 VAC at the contactor or the coil is open.
Y and C at the outdoor. Indoor IFC / stat actually closing Y. Contactor coil ohms. Do not confuse a furnace lockout with a dead outdoor. Hum / no start
Cap / start lockout Compressor hums, outdoor fan may run.
Dual cap (fan and herm). Replace on values, not just a bulge. Hard-start only after the cap and windings are proven. HPS
High pressure lockout Outdoor airflow, overcharge, or restriction.
Fan running? Coil dirty? SC vs nameplate on a TXV coil. LPS / freeze
Low pressure lockout Charge, indoor airflow, metering.
Do not add gas on a frozen coil. Indoor filter/coil first. Workflows No cool, GLXS4B Indoor running, outdoor dead, plate says R-32.
This is 24V Y. There is no ComfortBridge outdoor and no inverter to reset. 24 VAC across the contactor coil. Then dual cap, then R-32 pressures. Charge: piston = SH, TXV = SC, on the R-32 chart for THIS outdoor — not GSX16 410A targets. Leak repair: recover R-32, repair, pressure-test, weigh-in + line-set. Do not top off 410A into this cabinet. Test points
Charge Nameplate + line-set. SH on piston, SC on TXV.
Cap Dual can. Fan and herm both in spec. Gotchas Techs treat every Goodman box as 410A GSX16. Read the plate. R-32 machines and cylinders only. GLXT7C is the two-stage R-32 cousin — Y1/Y2, not this single contactor. Amana ALXS4B is the badge twin. Same R-32 story. Terms Privacy Refund policy FieldBench is an independent reference tool and is not affiliated with, authorized by, or endorsed by Goodman, Amana, Daikin, Carrier, Bryant, or any equipment manufacturer. All product names and model numbers are trademarks of their respective owners, used for identification only.