Goodman
GLXT7C
AC · R-32 two-stage scroll · 17 SEER2 class
Current Goodman R-32 two-stage condensing unit. Y1/Y2 or communicating indoor depending on vintage. Not the R-410A GSXC18 and not the GXV9S inverter.
Not GSXC18 (R-410A two-stage / ComfortBridge). Not GLXS4B (R-32 single-stage, one contactor). Not GXV9S / GSXV9 inverter.
Walk this in DiagnoseThis plate
- Refrigerant
- R-32 (A2L)
- Stages
- Two-stage scroll · Y1 low / Y2 high
- Metering
- TXV indoor required for rating
- Pair
- 24V Y1/Y2 or communicating indoor per the outdoor diagram
- Sister SKU
- Amana ALXT7C
This board
Two-stage outdoor control · R-32
- Codes are on the outdoor board. Indoor E-codes are the furnace.
- Low vs high is Y1/Y2 or the communicating request — confirm which this vintage actually landed.
- R-32 nameplate. Do not apply a GSXC18 410A SC target.
Sequence
- Y1 / low. Outdoor starts low capacity. Indoor blower on low/mid Cool tap (24V) or communicating CFM (ComfortBridge indoor).
- Y2 / high. Second stage. Head and subcooling should rise into the OEM SC window.
- Communicating pair. GMVC96 / AVPTC indoor requests capacity on the data pair. No conventional Y needed. A 24V GR9T96 on that same pair is a miswire.
Faults on this IFC
HPS
High pressure
lockoutOutdoor airflow, overcharge, or restriction opened the high-pressure switch.
- Outdoor fan running? Coil dirty, recirc, bent fins.
- Subcooling vs indoor TXV sheet. Liquid-line drier / restriction.
- Do not keep resetting HPS into a locked fan.
LPS
Low pressure / freeze
lockoutSuction dropped out — charge, indoor airflow, or TXV.
- Indoor filter, blower, coil freeze. Do not add gas on a frozen coil.
- TXV / restriction. Weigh-out if the history is a leak.
- Low ambient and wind can nuisance-trip LPS on a light load — still prove charge.
Comm
Indoor/outdoor data
lockoutComfortBridge data pair only. Invalid as a diagnosis on a 24V Y1/Y2 hookup.
- Data pair polarity and splices. This is not 24V Y.
- Indoor IFC family must be GMVC / AVPTC communicating. GR9T96 / GMEC96 / GMSS96 cannot be the ComfortBridge indoor.
- One master on the bus. Outdoor board power before you condemn the indoor IFC.
Workflows
No cool or stuck on low, GLXT7C
Runs on Y1 only, or silent.
- Prove Y1 and Y2 at the outdoor under a high-stage call. A leftover single-stage stat will never pull high.
- R-32 pressures and SC on the TXV indoor. Not a GSX16 piston SH chart.
- If the indoor is ComfortBridge, confirm this outdoor actually talks. Many GLXT land 24V only.
Test points
- Charge
- Nameplate + line-set adders. SC per indoor TXV sheet.
- Y1 / Y2
- 24V pair: both present on high stage. Communicating pair: data, not 24 VAC.
- Outdoor board
- LED/display before the disconnect. Codes die when you pull power.
Gotchas
- GSXC18 in the same yard is 410A. Do not swap driers, pistons, or charge charts across refrigerants.
- Amana ALXT7C is the badge twin.