Goodman
GMS80 Furnace · Single-stage · 80% AFUE · LED flash · metal vent
Goodman 80% single-stage with the 1–9 LED chart. Category I metal vent. No secondary collector, no PVC trap story. 3-flash is chimney / inducer / draft switch. GMES80 is the multi-speed ECM 80% cousin — same flashes, different blower. GDS80 / GDH80 are downflow 80%.
Not GMSS96 / GMSS92 (condensing — 3-flash is a trap). Not GR9T96 / GR9S96 (7-seg). Not GMVC80 communicating 80% if the board has a triple 7-seg — that is a different IFC.
Walk this in Diagnose This plate
AFUE 80% · Category I metal vent
Display Red LED 1–9 flash
Blower GMS80: multi-speed PSC. GMES80: multi-speed ECM This board Single-stage LED IFC (80%)
Same 1–9 meanings as GMSS96. Physics do not match. 3-flash = metal-vent draft, not a drowned 96% collector. 6-flash rollout is still a hazard. 4-flash is still the dirty A-coil on top of an 80%. Sequence W. Inducer → metal-vent PS → HSI → valve → flame → blower. Chimney and common vent matter. Faults on this IFC 3 flash
PS open lockout Metal-vent draft not proven.
Cap, liner, common-vent tables, inducer wheel. PS hose on the inducer housing — flue condensate on a long metal run, not a 96% collector. Do not cut a PVC trap that does not exist. 4 flash
Limit warn Airflow. 80% coils still dirty.
Filter, heat tap, A-coil on top. 6 flash
Rollout hazard Flame containment.
Exchanger, burners, flue. Reset only after cause. 7 / 8 flash
Flame / igniter warn Rod or HSI.
µA, nitride or Norton per this cabinet, gas. Workflows 3-flash on GMS80 Do not dump the condensate trap.
This furnace has no secondary drain. Look at the metal vent and the inducer. Common-vented water heater: run the tables before you change the switch. Then the PS hose to the inducer housing. Test points
Vent Cat I. Spillage is a fail. Gotchas GMES80 is the ECM 80% — same 3-flash, different motor. GDS80 / GDH80 downflow 80% same chart. A tech who just left a GMSS96 will pull a trap that is not here. Related plates goodman-gmss96 — 96% flash. Same 1–9 numbers, PVC trap instead of a chimney. goodman-gmss92 — 92% flash. Still condensing — trap exists. bryant-800s — Bryant 80% single-stage two-digit 31 is the metal-vent analog (different OEM numbers). Terms Privacy Refund policy FieldBench is an independent reference tool and is not affiliated with, authorized by, or endorsed by Goodman, Amana, Daikin, Carrier, Bryant, or any equipment manufacturer. All product names and model numbers are trademarks of their respective owners, used for identification only.