Models
Goodmanfurnace

GMSS96

Single-stage · 96% AFUE · LED flash

Single-stage 96% condensing furnace with one pressure switch and a red LED flash-code IFC. This is the board most ‘Goodman 3-flash’ videos are actually about — not GR9T96, not GMEC96, not GMVC96.

Not GR9T96 (two-stage, dual PS, 7-seg E1–E9). Not GMEC96 (two-stage CT motor, E0–E9). Not GMVC96 (ComfortBridge VS, triple 7-seg). Do not alias those cabinets onto this chart.

Staging

Single-stage gas valve · single-speed inducer · one pressure switch

Blower

Multi-speed ECM or PSC depending on exact SKU

Display

Red LED flash chart — not a 7-segment E-code

Tstat

Conventional 24V · W Y G R C

Sister SKU

GM9S96 / GCSS96 · Amana AM9S96 same flash family

This board

Single-stage LED IFC

  • LED off = no 120/24. LED steady on = idle with 24 V present. Rapid flash = reversed polarity, not a high count.
  • Count flashes between the long pause: 1 lockout, 2 PS closed inducer off, 3 PS open inducer on, 4 limit, 5 flame valve off, 6 rollout, 7 low flame, 8 igniter, 9 polarity/ground.
  • One pressure switch only. Do not apply E8/E9 high-fire codes — there is no high-fire switch.

Active code repeats until power is pulled. Write the flash count first. Power cycle clears live, not always the cause.

Universal swap

Read the silk

Older Goodman single-stage LED. Silk decides: 110/123 → ICM2811. B18099-13 → ICM280. 50A55 only if it is already a WR 50A5x.

Silk: PCBBF110 · PCBBF112 · PCBBF123 · B18099-26 · 0130F00005 · B18099-13

White-Rodgers

  • 50A55-843

    If the silk is already a 50A50 / 50A55 carbide module.

  • 50M56U-843

    Harness kit when the dead board is on the 50M56U single-stage HSI list.

ICM

  • ICM2811

    PCBBF110 / 112 / 123 / 0130F00005 / B18099-26 — ICM.

  • ICM280

    B18099-06 / 08 / 10 / 13 only.

Honeywell

  • S9200U1000

    S9200U1000 list includes B18099-06/08/10/13, 102077-xx, ICM280, and 50A55-843. Not PCBBF110/123.

  • GR9S96 EE 7-seg card. GMVC96 ComfortBridge. PCBBF132 two-stage 9-speed.

After you pull the dead card

  1. 1Kill power. Photograph the silk-screen part number on the dead board before you pull it.
  2. 2Match staging (1 vs 2 vs modulating), igniter (carbide / nitride / spark), and motor (PSC / ECMx / 9-speed tap / serial VS).
  3. 3Set heat-off delay and any 80+/90+ jumper to the door card. Prove one full try and flame µA before you leave.

Field wiring

Written landings for Goodman GMSS96. Not a factory schematic.

Furnace · single-stage 24V
R / C / W / Y / GGas furnace

Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → transformer → R120V in, 24V out
  2. 2Call. Stat W → IFC W~24 VAC
  3. 3Draft. IFC → inducer → PS close120V motor, 24V prove
  4. 4Ignite. IFC → HSI120 VAC
  5. 5Gas. IFC → valve~24 VAC
  6. 6Flame. Rod → IFCµA DC
  7. 7Blow. IFC → heat speedAfter flame prove

This indoor

Flash 96%. One W. Not GR9S96 EE.

24V single-stage heat

Door card is one-stage. Twin terminal empty unless the job is actually twinned.

Wall thermostat

Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.

  • R24V hot from the IFC24V
  • CCommon24V
  • WHeat24V
  • YCool — also starts the outdoor24V
  • GFan24V

Furnace IFC

Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.

  • RHot to the stat24V
  • CCommon — must reach the outdoor24V
  • WHeat call24V
  • YCool in / cool out24V
  • GBlower24V
  • TWINEmpty unless twinned24V

Landing

  • 24VIFC Rstat R

    ~24 VAC hot

  • 24VIFC Cstat Coutdoor C

    Common

  • 24VStat WIFC W

    Heat. Stays in this cabinet.

  • 24VStat YIFC Youtdoor Y

    Cool / contactor

  • 24VStat GIFC G

    Fan. Does not go outdoors.

IFC harness — single-stage heat

After W arrives. This is the gas train, not the thermostat strip.

Transformer + fuse

120V primary. 24V secondary. Dark stat = fuse / door / transformer first.

  • L1 / N120V to the IFCLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout in series. Open anywhere kills heat.

  • DOORInterlock24V
  • LIMITMain limit — rise / no airflow24V
  • ROLLOUTManual reset. Do not jumper and leave24V

Inducer + one pressure switch

W → inducer 120V → PS closes → IFC continues. One hose, one switch.

  • IND120V from the IFC to the inducerLine
  • PS24V prove back to the IFC24V
  • HOSESingle hose. Do not add a second because two-stage boards have two.24V

HSI + single valve

Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.

  • HSI120V hot-surface igniter — not 24VLine
  • VALVE24V to the single solenoid24V
  • FLAMEµA DC on the rod. Not a 24V circuit24V

PSC blower + run cap

Heat / cool / park taps on the motor. The cap is on this blower — not the outdoor dual can.

  • HEATHeat speed tap24V
  • COOLCool speed tap24V
  • PARKUnused leads parked24V
  • CAPRun capacitor on the blowerCap

Landing

  • LineL1IFCinducer

    120 VAC after W

  • 24VIFCPSIFC

    ~24 VAC prove. Open PS = no ignition.

  • LineIFCHSI

    120 VAC during trial

  • 24VIFCgas valve

    ~24 VAC after flame prove starts

  • 24VFlame rodIFC

    µA DC. Not 24V.

  • LineIFCblower

    120V tap + cap

Prove it

  • 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
  • W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.

Do not

  • Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
  • Do not hunt W2 / E8 / high-fire on a one-stage door.
  • TWIN must be empty on a standalone.

9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.

Sequence

  1. 1

    W

    Inducer on → single PS must close → HSI → valve → flame → blower delay.

  2. 2

    No W2 path

    There is no high-fire prove. A leftover W2 wire is unused or tied for an AC stage, not furnace high fire.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

LED off

No power

warn

No 120 VAC or no 24 VAC on the IFC. Not a flash code.

  1. 1 Measure at the IFC under load

    On Goodman GMSS96 line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. Door switch, incoming L1/N, transformer, 3 A fuse.

    Expect: Voltage in the rating-plate window under load.

  2. 2 Drop, breaker, and the whip

    Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. If 24 V is present and the LED is dead, IFC.

    Expect: Minimal drop. Tight lugs. Correct breaker size.

  3. 3 Transformer 24 V last

    If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.

    Expect: 24 V holds under load. Line stays in window.

Steady on

Idle

info

24 V present, no call, no fault. Status.

  1. 1 Confirm this is not a fault

    On the Goodman GMSS96 this readout (Steady on) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the Goodman GMSS96 IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: If the house is cold, the call is not reaching W. Check R to W at the IFC, not just at the stat.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch Single-stage LED IFC through one cycle and write the first real fault that replaces this status word.

    Expect: W: Inducer on → single PS must close → HSI → valve → flame → blower delay.

Rapid flash

Polarity reversed

lockout

L1/N swapped. Not ‘code 10’ and not a high flash count.

  1. 1 Hot and neutral at the IFC, not the disconnect

    On Goodman GMSS96 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot and neutral at the IFC, not just the disconnect.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Burner-box ground. Rapid flash is EA-class, not a PS.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

1 flash

Retry lockout

lockout

Ignition retries exceeded on this call.

  1. 1 Watch one full try — do not reset

    Write the Goodman GMSS96 code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. Watch a try: inducer, HSI, valve, flame.

    Expect: W → No W2 path

  2. 2 Gas and the valve

    Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence. Gas, rod, ground. Do not keep resetting.

    Expect: Manifold: Single-stage plate value only — no low/high pair.

  3. 3 Flame prove, then the lockout timer

    Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.

    Expect: Stable µA after light-off. No new PS/limit code.

2 flash

PS closed, inducer off

lockout

The single switch is made with the inducer not running.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Goodman GMSS96 active code. Write 2 flash. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Unplug the PS. Hose water holding residual draft.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Welded switch or IFC input shorted.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: Single PS: One NO switch. Closed only with inducer up. If you see a second hose hanging, someone mixed this cabinet with a two-stage collector.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

3 flash

PS open, inducer on

lockout

Draft not proven. The call you will see all winter on 96% Goodman singles.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Goodman GMSS96 active code. Write 3 flash. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap and collector first — these 96%s drown overnight.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Inducer 120 VAC and spinning. Hose on the only collector tap.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. PVC intake/exhaust, bird screen, ice, wind.

    Expect: Single PS: One NO switch. Closed only with inducer up. If you see a second hose hanging, someone mixed this cabinet with a two-stage collector.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

4 flash

Open limit

warn

Airflow or overfire.

  1. 1 Airflow before you touch the limit

    On Goodman GMSS96 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, heat-speed tap, rise, coil.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Goodman GMSS96 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. A 96% coil on a furnace left on a low heat tap will limit all season.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).

    Expect: Manifold: Single-stage plate value only — no low/high pair.

5 flash

Flame with valve off

hazard

Leaking valve or false flame sense.

  1. 1 Shut the gas cock first

    On Goodman GMSS96 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, replace the valve.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

6 flash

Rollout open

hazard

Manual-reset rollout. Flame containment until proven otherwise.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Goodman GMSS96 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, crossover, flue, secondary / condensate. Reset only after the cause is fixed.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Goodman GMSS96 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

7 flash

Low flame

warn

Weak µA.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Goodman GMSS96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod, chassis ground, manifold, LP conversion.

    Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold: Single-stage plate value only — no low/high pair.

  3. 3 Prove it is not a switch opening

    Watch the live Goodman GMSS96 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

8 flash

Igniter fault

lockout

Open / cracked HSI or no 120 VAC during trial.

  1. 1 Ohms at the igniter, then at the IFC

    On Goodman GMSS96 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the igniter, then at the IFC.

    Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. 120 VAC during warm-up. Nitride, not an 80% Norton chart.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

9 flash

Polarity / ground

lockout

L1/N or chassis ground. Sister to rapid flash on some revisions.

  1. 1 Hot and neutral at the IFC, not the disconnect

    On Goodman GMSS96 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Burner box to IFC ground screw.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

Workflows

3-flash no heat

Inducer runs, no ignition, LED 3-flash. Overnight no-heat is the classic.

  1. 1 Prove the call and the live code

    Count flashes. Do not open a GR9T96 E-code card on this board.

    Expect: Write whatever Single-stage LED IFC is showing. Active code repeats until power is pulled. Write the flash count first. Power cycle clears live, not always the cause.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Prove inducer 120 VAC and spinning.

    Expect: No W2 path: There is no high-fire prove. A leftover W2 wire is unused or tied for an AC stage, not furnace high fire.

  3. 3 Confirm with a number, then the next part

    Open the trap and the collector — 96% Goodman singles drown overnight. That is the call. Hose dry and on the only tap. Ohms the PS with inducer on (should close) and off (should open). If PS closes and IFC still 3-flashes, IFC input is the fault.

    Expect: Single PS: One NO switch. Closed only with inducer up. If you see a second hose hanging, someone mixed this cabinet with a two-stage collector. · Manifold: Single-stage plate value only — no low/high pair.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Single PS

One NO switch. Closed only with inducer up. If you see a second hose hanging, someone mixed this cabinet with a two-stage collector.

Manifold

Single-stage plate value only — no low/high pair.

LED

Off / steady / rapid / 1–9 counted between the long pause.

Gotchas

  • Do not install a second pressure switch ‘because two-stage boards have two.’
  • A leftover W2 from a previous two-stage furnace does nothing useful here and confuses the next tech.
  • GMEC96 and GMVC96 are not this board. Flash-count videos that cut to a 7-seg are a different furnace.

Related plates

Install this plate

Install GMSS96 as the classic Goodman 96% flash furnace — one PS, red LED 1–9.

Cat IV PVC · single-stage · one PS · multi-speed ECM or PSC · 24V W Y G R C

Vent & IFC

  • One pressure switch. 3-flash is trap / PVC / inducer on this 96% — not a GMS80 chimney.
  • LED flash chart on the door. There is no 7-seg and no EE2. GR9S96 is the other single-stage 96%.
  • Prime the trap. Collector and secondary exist even though the board looks like an 80% flash IFC.

Air & stat

  • Heat/cool taps or ECM profiles. Not 9-speed, not serial VS.
  • Single W. Cap unused W2 so it cannot backfeed the IFC.

First fire

  1. 1W: inducer → PS → HSI → valve → flame → heat tap.
  2. 2Count flashes with power applied. Rapid flash is polarity, not ‘9’.
  3. 3Rise vs the GMSS96 tap chart for this cabinet (0403BN ≠ 1205DN).

Do not on Goodman GMSS96

  • Do not use GR9S96 EE0/EE1/EE2 language on this LED.
  • Do not treat 3-flash like GMS80 (metal vent). Drain the trap first.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Dated GM* certificate

    warranty sheet

    Older Goodman GM* furnace limited warranty

    GM* generation furnace warranty terms · Dated certificate for that generation

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal