Amana
AM9S96 Furnace · Single-stage · multi-speed · 96% AFUE
Single-stage 96% with one pressure switch and a flash-code or simple 7-seg IFC. Use the 1–9 flash chart. Do not apply AR9T96 E8/E9 high-fire codes — there is no high-fire switch. Do not apply AR9S96 0140F20003-B E0–E7 (that is the current 9-speed 7-seg single). Do not apply AMVC96 / ARVT96 ComfortBridge E/b/d codes.
Not AR9T96 (two-stage, dual PS, 7-seg E1–E9). Not AR9S96 (current single-stage 9-speed, 0140F20003-B, E0–E7 — not this flash card). Not ARVT96 / AMVC96 (communicating VS). GMSS96 is the Goodman-badge single-stage chart — same flash family, different listing.
Walk this in Diagnose This plate
Input / AFUE Up to 96% · 40–120 kBtu family · single-stage heat
Staging Single-stage gas valve · single-speed inducer · one pressure switch
Blower Multi-speed ECM or PSC depending on exact SKU
Heat exch. Stainless tubular primary + stainless secondary
Ignition 120 VAC silicon nitride HSI
Vent PVC 2-pipe or 1-pipe
Tstat Conventional 24V · W Y G R C
Sister SKU AMH96 · Goodman GM9S96 same flash family · GMSS96 lives on the Goodman chart This board Single-stage IFC · red LED flash or basic 7-seg
Count flashes between the long pause. Rapid flash is polarity, not ‘code 10’. LED off = no 120/24. LED steady on (some revs) = idle with 24 V present. One pressure switch only. 2-flash closed-with-inducer-off, 3-flash open-with-inducer-on. Do not read this as an AR9T96 E-code card or an AMVC96 triple-7-seg menu. Sequence W. Inducer on → single PS closes → HSI → valve → flame → blower delay. Prove. One NO pressure switch. Already closed with inducer off → 2-flash. Never closes → 3-flash. No W2 path. There is no high-fire prove. A ‘W2’ wire is unused or tied for an AC stage, not furnace high fire. Faults on this IFC 1 flash
Retry lockout lockout Ignition retries exceeded.
Watch one full try: inducer, HSI glow, valve click, flame. Gas cock, manifold vs plate, orifice. Rod µA and chassis ground. Do not keep resetting — find which step dies. 2 flash
PS closed, inducer off lockout Single switch welded or IFC input shorted.
Unplug the only PS. Code change = switch or water in the hose. Hose routed downhill? Residual draft fakes closed. IFC input shorted — only after the switch ohms open. 3 flash
PS open, inducer on lockout Draft / trap / hose / inducer.
Trap, collector, and vent first — these 96%s drown a collector overnight. Inducer 120 VAC and spinning. Hose dry and on the only collector tap. If the PS closes and the IFC still 3-flashes, the IFC input is the fault. 4 flash
Open limit warn Airflow or overfire.
Filter, coil, return, heat-speed tap. A 96% coil on a low heat tap will limit. Rise vs rating plate. Clock the meter — overfire trips limits with a clean filter. 5 flash
Flame with valve off hazard Leaking valve or false flame sense.
Shut the gas cock. If flame stays, leaking valve — replace, do not jump. Rod shorted to ground or IFC flame circuit. 6 flash
Rollout open hazard Flame containment.
Exchanger, burners, flue. Blocked secondary / condensate. Reset only after the cause is fixed. Recurring rollout is a CO / fire call. 7 flash
Low flame warn Weak µA.
Clean rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC. Manifold / orifice / LP conversion. 8 flash
Igniter fault lockout Open / cracked HSI.
Ohms at the igniter plug, then at the IFC. 120 VAC during trial. Cracked nitride element. 9 flash
Polarity / ground lockout L1/N or chassis ground.
Hot and neutral at the IFC, not just the disconnect. Burner-box ground screw. Rapid flash on some revs is the same polarity complaint, not a high count. Workflows No heat (single-stage 96%) AM9S96 / AMH96 / GM9S96. Tstat calling W, indoor cold.
Count flashes. Do not use an AR9T96 E-code card or an AMVC96 ComfortBridge menu. Door switch in? 120 VAC at L1, 24 VAC across the fuse. W present at the IFC (not just at the stat). R to W ~24 VAC. 3-flash: trap and vent first — these 96%s drown a collector overnight. 2-flash with inducer off: unplug the only PS. Code change = switch/hose. 8-flash / no glow: HSI ohms and 120 VAC during trial. 1-flash after flame drop: rod and ground. One PS only — if you see a second hose hanging, someone mixed this cabinet with a two-stage collector. 4-flash limit trips Blower on, burners drop, 4-flash.
Heat-speed tap first. A 96% coil on top of a furnace left on a low heat tap will limit all winter. Filter, wheel, coil, return size. A new media cabinet the installer added is the usual callback. Rise vs plate. Clock the meter if rise is high with a clean filter. Secondary / condensate — a drowned coil raises head in the exchanger and trips limit. Test points
Pressure switch One NO switch. Closed only after inducer is up.
Manifold Single-stage plate value only — no low/high pair.
Flame rod µA per this door card. Rising while running is the goal.
HSI Nitride, 120 VAC during warm-up. Cold ohms per sticker.
Heat tap / rise Match the installer’s tap to the rise range on the rating plate (typically 35–65°F). Gotchas GMSS96 is the Goodman-badge listing of this flash family — use the Goodman GMSS96 chart, not this alias. A leftover W2 from a previous two-stage furnace does nothing useful here and confuses the next tech. Do not install a second pressure switch ‘because two-stage boards have two.’ AR9T96 E8/E9 and AMVC96 b/d codes do not apply. One switch, flash count, conventional 24V. Related plates amana-ar9s96 — Current single-stage 9-speed 96% — 7-seg E0–E7 on 0140F20003-B, not this LED 1–9 flash card. amana-ar9t96 — Two-stage 9-speed cousin — dual PS, 7-seg E1/E2 vs E8/E9. Do not use that chart on this single-stage flash IFC. amana-amvc96 — ComfortBridge communicating VS cousin. Triple 7-seg, serial ECM, memory card. Not this board. Terms Privacy Refund policy FieldBench is an independent reference tool and is not affiliated with, authorized by, or endorsed by Goodman, Amana, Daikin, Carrier, Bryant, or any equipment manufacturer. All product names and model numbers are trademarks of their respective owners, used for identification only.