Models
Goodmanfurnace

GR9T96

Two-stage · 9-speed ECM · 96% AFUE

Goodman-badge twin of the Amana AR9T96. Two-stage gas valve, two-speed inducer, 9-speed ECM (tap/profile, not communicating), and a single 7-segment IFC that speaks E0–E9. Conventional 24V thermostat. Low-fire and high-fire each have their own pressure switch — E1/E2 vs E8/E9 are not the old 1-flash Goodman chart.

Not GMVC96 (ComfortBridge variable-speed, triple 7-seg, 14-pin serial motor). Not GMSS96 / GM9S96 (single-stage, one PS, LED flash). Not GMEC96 (two-stage with a constant-torque / X-13 motor, not a 9-speed tap card).

Input / AFUE

Up to 96% · 40–120 kBtu family

Staging

Two-stage gas valve · two-speed inducer · dual pressure switches

Blower

9-speed ECM (tap/profile, not communicating VS)

Heat exch.

Stainless tubular primary + stainless secondary

Ignition

120 VAC silicon nitride HSI

Vent

PVC 2-pipe or 1-pipe · 40 ng/J Low NOx (not SCAQMD/SJV)

Tstat

Conventional 24V · Y/Y1 Y2 G R C W/W1 W2

Sister SKU

GD9T96 downflow · Amana AR9T96 / AD9T96 same IFC (PCBBF132 family)

This board

Self-diagnostic IFC · single 7-segment (read Seg3→Seg2→Seg1 left to right)

  • Codes sit on the IFC in the blower compartment. Do not kill power — that clears the active code.
  • Read left to right. Idle / no fault is a quiet or dashed display; faults prefix E, EE, L, U, F, S, r.
  • E1/E2 are the LOW-FIRE pressure switch. E8/E9 are the HIGH-FIRE pressure switch. Do not treat them as the old 2-flash / 3-flash single-switch chart.
  • A2L pair codes (FE3, LE4, SE5, rE6) only apply when this furnace is tied to an R-32 / A2L outdoor. Ignore them on R-410A pairs.

In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.

Universal swap

Read the silk

Same IFC family as AR9T96. PCBBF132 → 50M56-743. Not a 50A55.

Silk: PCBBF132 · PCBBF132S

White-Rodgers

  • 50M56-743

    WR OEM-style replacement for PCBBF132 / PCBBF132S — the GR9T96 / AR9T96 card.

ICM

Honeywell

  • 50A55-843 / 50M56U-843 / S9200U1000.
  • ICM2810 (136/140 only).
  • ICM2811 (110/123).
  • GMVC96 ComfortBridge board.

After you pull the dead card

  1. 1Kill power. Photograph the silk-screen part number on the dead board before you pull it.
  2. 2Match staging (1 vs 2 vs modulating), igniter (carbide / nitride / spark), and motor (PSC / ECMx / 9-speed tap / serial VS).
  3. 3Set heat-off delay and any 80+/90+ jumper to the door card. Prove one full try and flame µA before you leave.

Field wiring

Written landings for Goodman GR9T96. Not a factory schematic.

Furnace · two-stage 24V
R / C / W1 / W2 / Y / GGas furnace

Two-stage conventional furnace. W1 low fire, W2 high fire. Outdoor staging is Y or Y1/Y2 — separate from the gas valve.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → R120V / 24V
  2. 2Low. W1 → inducer LOW → LPS → HSI → valve LOWFirst fire
  3. 3High. W2 → inducer HIGH → HPS → valve HIGHSecond solenoid
  4. 4Flame. Rod → IFCµA DC both stages
  5. 5Blow. IFC → heat blowerAfter flame

This indoor

9-speed two-stage. W1/W2. GSXC on Y1/Y2, not 1/2.

24V two-stage heat

Door has W1 and W2. Not Infinity. Not ComfortBridge.

Two-stage thermostat

A single-W stat never proves high fire. That is not a weak inducer.

  • R24V hot24V
  • CCommon24V
  • W1Low-fire heat24V
  • W2High-fire heat24V
  • Y / Y1Cool24V
  • Y2Outdoor high if the condenser is two-stage24V
  • GFan24V

Two-stage IFC

W2 is high fire. Do not tee the pressure-switch hoses because there are two stages.

  • RHot24V
  • CCommon to outdoor24V
  • W1Low fire24V
  • W2High fire24V
  • YCool out24V
  • GBlower / cool tap24V

Landing

  • 24VStat W1IFC W1

    Low fire

  • 24VStat W2IFC W2

    High fire. Missing W2 = stuck on low.

  • 24VStat YIFC Youtdoor Y

    Cool

  • 24VC throughout

    Common

IFC harness — two-stage heat

W1 then W2. Low-fire prove is not high-fire prove.

Transformer + fuse

Same 24V transformer as single-stage. Fuse still kills the whole strip.

  • L1 / N120VLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout. A limit trip is not an E9 / 32 pressure-switch story.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + two pressure switches

W1 = inducer low + LPS. W2 = inducer high + HPS. Separate hoses. Do not tee.

  • IND LO120V low-speed inducerLine
  • IND HI120V high-speed inducerLine
  • LPSLow-fire prove24V
  • HPSHigh-fire prove24V
  • HOSESOne hose per switch. Never tee LPS and HPS24V

HSI + two-stage valve

Igniter 120V. Low solenoid on W1. Second solenoid on W2 after HPS closes.

  • HSI120V igniterLine
  • MV / LO24V low-fire solenoid24V
  • HV / HI24V high-fire solenoid24V
  • FLAMEµA DC on the rod24V

9-speed tap ECM

F01–F09 on the harness. Heat tap and cool tap are separate. Not a 14-pin serial motor and not a run cap.

  • F01–F09Speed taps on the IFC / harness24V
  • HEATDefault often F02 — F01 is an E3 generator on many 9-speed doors24V
  • COOL / Y / GCool tap. Wrong tap freezes the coil and looks like LPS outdoors.24V

Landing

  • LineW1IFCinducer LOWLPS

    120V inducer, 24V prove

  • LineIFCHSIvalve LOW

    120V igniter, 24V low solenoid

  • 24VW2inducer HIGHHPSvalve HIGH

    Missing W2 = stuck on low

  • 24VFlame rodIFC

    µA DC

  • LineIFCheat blower

    After flame. Motor class on this plate.

Prove it

  • W1 then W2 at the IFC under a 2-heat call.
  • If it never stages, W2 is missing at the board — not a bad gas valve until that is proven.

Do not

  • Do not convert this to Infinity by landing W on a random terminal.
  • Do not apply AMVC / ARVT ComfortBridge menus or a memory card.

926T / 59TP6 / AR9T96 / GR9T96 / S9V2 / EL296E class. Same landing on 80% metal-vent cousins — the vent is not the wire.

Sequence

  1. 1

    W1

    IFC proves limits/rollout closed, starts inducer on low speed.

  2. 2

    Prove low PS

    Low-fire pressure switch must close. If it is already closed with inducer off → E1. If it never closes → E2.

  3. 3

    HSI warm

    Silicon nitride igniter ~17–27 s (OEM). Open igniter → En / E7.

  4. 4

    Low-fire valve

    First-stage solenoid opens. Flame must prove at the rod. Failures stack toward E0 lockout.

  5. 5

    Blower delay

    Heat-on delay, then ECM on the selected heat tap (not a communicating CFM request).

  6. 6

    W2 / high fire

    Inducer goes high. High-fire PS must close (E9 if open, E8 if it was already closed). Second-stage solenoid opens.

  7. 7

    Satisfied

    Valve off, inducer post-purge, blower heat-off delay. Unexpected flame after valve-off → E4.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

E0

Retry / recycle lockout

lockout

Too many failed ignition attempts or flame losses on this call.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Goodman GR9T96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Watch one full try: inducer, HSI glow, valve click, flame, µA.

    Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Gas supply and manifold (low then high).

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

  3. 3 Prove it is not a switch opening

    Watch the live Goodman GR9T96 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Ground and flame-rod cleanliness.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

E1

Low-fire PS stuck closed

lockout

Low-stage pressure switch is made with the inducer off.

  1. 1 Unplug the switch with the inducer off

    On Goodman GR9T96 this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the LPS. If code changes, switch is welded or hose is holding residual draft.

    Expect: Code changes when the harness is open.

    If fail: Wrong switch, or the IFC input is shorted.

    If pass: Switch/hose path. Go to step 2.

  2. 2 Water in the hose vs a welded switch

    Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Hose routed downhill to the collector? Water in the hose fakes a closed switch.

    Expect: Hose empty. Switch opens with no draft.

  3. 3 IFC input last

    If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Goodman GR9T96 IFC input is shorted. Do not keep swapping switches. IFC input shorted — only after the switch ohms open.

    Expect: Known-good open switch + open harness = code gone. If not, IFC.

E2

Low-fire PS open

lockout

Inducer is on low and the low-fire switch will not close.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Goodman GR9T96 active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer spinning? 120 VAC at inducer on a W1 call.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Collector box, inducer outlet, and condensate trap — this 96% unit will not make pressure with a full trap.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. PVC intake/exhaust (bird screen, ice, long run, wind).

    Expect: LPS / HPS: Both NO. Closed only when that inducer speed is making the collector setpoint. Never teed.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

E3

Open high limit

warn

Primary limit opened. Airflow or overfire — not a charge problem.

  1. 1 Airflow before you touch the limit

    On Goodman GR9T96 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, blower wheel, A-coil, heat-speed tap (9-speed: wrong tap is the #1 callback).

    Expect: ECM heat tap: Match the installer’s tap to the rise range on the rating plate (typically 35–65°F).

  2. 2 Measure static and temperature rise

    Total external static vs the Goodman GR9T96 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Static vs blower chart for this cabinet size.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Manifold pressure on low and high vs rating plate.

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

E4

Flame when valve should be off

hazard

Rod sees flame with both solenoids de-energized.

  1. 1 Shut the gas cock first

    On Goodman GR9T96 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground or IFC flame circuit.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

E5

Open fuse

warn

3 A (typical) automotive fuse on the IFC is open.

  1. 1 Find the 24 V short before you replace the fuse

    On Goodman GR9T96 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. 24 V short on W, Y, G, humidifier, or EAC.

    Expect: Fuse out. 24 V transformer still good. Harness isolated.

  2. 2 Replace the fuse with the harness off

    New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC). Unplug tstat harness and replace fuse. If it blows again the short is on the board or gas valve harness.

    Expect: Fuse holds with harness off. Dies when the shorted lead lands.

  3. 3 If it blows with the harness off

    Short is on the Goodman GR9T96 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.

    Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.

E6

Low flame signal

warn

Flame is present but µA is below the IFC threshold.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Goodman GR9T96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod with a non-scratch pad — not sandpaper.

    Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Chassis ground to burner box and IFC.

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

  3. 3 Prove it is not a switch opening

    Watch the live Goodman GR9T96 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Manifold pressure / orifice / LP conversion.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

E7

Igniter relay fault

lockout

IFC did not see the igniter circuit behave as commanded.

  1. 1 Ohms at the igniter, then at the IFC

    On Goodman GR9T96 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Igniter ohms cold (OEM — typically 30–115 Ω class, confirm sticker).

    Expect: HSI: Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use a 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. 120 VAC to igniter during warm-up.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter. Cracked nitride element.

    Expect: One clean light after a known-good igniter and a proven ground.

E8

High-fire PS stuck closed

lockout

High-stage pressure switch is made with the inducer not on high.

  1. 1 Prove the switch is made with inducer not on high

    On Goodman GR9T96 this code means the high-fire switch is closed when it should be open. Do not treat it as the low-fire stuck-closed code. Write the live display, then unplug the high-fire switch only.

    Expect: Code should change when the high-fire harness is open.

    If fail: IFC input shorted or you unplugged the wrong switch.

  2. 2 Hose water and a welded switch

    Water in the high-fire hose holds residual draft and fakes a closed switch. Route downhill to the collector. Ohm the switch with the hose off — a welded high-fire switch stays closed. This is the second switch — do not confuse with E1. Welded HPS or water-filled hose.

    Expect: Hose dry. Switch opens with no draft.

  3. 3 Confirm the IFC is not commanding high

    W2 shorted to W1, a communicating stat stuck on high, or an IFC that never drops inducer speed will keep this code alive. Measure W2 at the board and watch inducer speed after you open the high-fire harness. IFC calling high when it should be low — W2 shorted to W1.

    Expect: Inducer on low (or off) with W2 open. High-fire switch ohms open.

E9

High-fire PS open

lockout

Inducer on high, high-fire switch never closes. Classic ‘runs on low, will not go high.’

  1. 1 Prove the high-fire call

    Write the live Goodman GR9T96 code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. Inducer actually changes speed on W2? Listen / amp it.

    Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.

    If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.

    If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’

  2. 2 Prove the inducer actually went high

    Listen and amp the inducer on low vs high. No speed-up → IFC high output or inducer winding. Speed-up and this code still live → high-fire PS path (hose, switch, vent). HPS hose on the high-fire tap, not teed to the low switch.

    Expect: LPS / HPS: Both NO. Closed only when that inducer speed is making the collector setpoint. Never teed.

    If fail: Measure 120 VAC on the high-speed inducer lead during the high call. 0 V = IFC. Voltage + dead motor = inducer.

  3. 3 Isolate the HIGH hose and switch

    High-fire hose on the high tap only — a tee with the low switch is the common first-install miss on this dual-switch plate. Blow the hose, confirm it is dry and downhill to the collector. Ohm the high-fire switch: it is NO and must close only on high draft. Vent capacity / wind / shared chase. High fire needs more draft than E2 ever saw.

    Expect: LPS / HPS: Both NO. Closed only when that inducer speed is making the collector setpoint. Never teed.

    If fail: Welded open, cracked hose, or water in the line. Replace the failed part — do not leave a jumper.

    If pass: Switch and hose good → step 4 (vent / condensate / IFC).

  4. 4 Vent, condensate, and the IFC input

    High fire needs more draft than a low-fire code ever saw. Check PVC size on this cabinet, shared chase, wind, ice, bird screen, and condensate backing into the collector only on high. If the switch closes on known draft and the code stays, the Goodman GR9T96 IFC input is the last call.

    Expect: Clear vent, dry collector, known-good switch, then IFC.

EA

Line polarity / ground

lockout

L1/N reversed or chassis ground missing. HSI and flame sense both suffer.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Goodman GR9T96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Hot and neutral at the IFC, not just the disconnect.

    Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Burner box to IFC ground screw.

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

  3. 3 Prove it is not a switch opening

    Watch the live Goodman GR9T96 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Twinned jobs — follow the twinning kit, then look at EEJ.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

Eb / Ec

Gas valve circuit

lockout

Internal (Eb) or external (Ec) gas-valve electrical fault.

  1. 1 Coil ohms and 24 VAC during trial only

    On Goodman GR9T96 measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Valve coil ohms, 24 VAC at the harness during trial.

    Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.

  2. 2 Do not energize a leaking valve

    If the unexpected-flame code is also in history, shut the cock and replace the valve. Applying 24 V as a ‘test’ and walking away is a gas leak. Do not apply 24 V to a leaking valve as a ‘test’ and walk away.

    Expect: No flame with the cock shut and solenoids de-energized.

  3. 3 IFC relay vs the valve

    Voltage at the harness and a dead coil = valve. No voltage during a known trial = IFC relay or a lockout that never opened the valve (look at the live code).

    Expect: Known trial + 24 VAC + good coil = flame. Otherwise IFC.

Ed

Open rollout

hazard

Manual-reset rollout opened. Treat as flame outside the exchanger until proven otherwise. Door chart may render this as a distinctive 7-seg character — confirm on the unit sticker.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Goodman GR9T96 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Primary exchanger cracks, burner alignment, crossover. Blocked secondary / condensate / flue.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Goodman GR9T96 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Reset only after the cause is fixed. Recurring rollout is a CO / fire call.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

En

Igniter open

lockout

Igniter circuit measures open.

  1. 1 Ohms at the igniter, then at the IFC

    On Goodman GR9T96 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the igniter plug, then at the IFC.

    Expect: HSI: Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use a 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Harness rub-through on the collector.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

EEH

Grounding error

lockout

IFC failed its ground check (sister to EA).

  1. 1 Hot and neutral at the IFC, not the disconnect

    On Goodman GR9T96 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green ground to cabinet and IFC.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Painted screw, missing star washer.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

EEJ

Twin error

lockout

Twinning miswire or twin terminal active on a standalone unit.

  1. 1 Is this cabinet actually twinned?

    On a standalone Goodman GR9T96, nothing belongs on the TWIN terminal. A leftover jumper throws this. If not twinned, nothing should be on the TWIN terminal.

    Expect: TWIN empty on a single cabinet.

  2. 2 Twinned pair must be the same IFC family

    Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin. Twinned pair must be same family / same IFC revision.

    Expect: Same model family, same IFC, kit installed per the twinning sheet.

  3. 3 Phasing and 24 V

    Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.

    Expect: In-phase 24 V. Continuous twin lead.

LE1 / UE2

Circulator current

lockout

ECM current too low (LE1) or unexpected (UE2).

  1. 1 Is the wheel free?

    Spin the Goodman GR9T96 blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Harness seated at motor and IFC. 9-speed ECM is tap-driven — a half-seated plug throws these.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Locked rotor, wet winding, or wrong motor for the cabinet.

    Expect: ECM heat tap: Match the installer’s tap to the rise range on the rating plate (typically 35–65°F).

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call. Do not put a PSC motor or a ComfortBridge serial motor on this IFC.

    Expect: Static on the blower chart. Matching motor / shared-data card.

FE3 / LE4 / SE5 / rE6

A2L mitigation

hazard

Leak / comm / relay alarm from the A2L board when paired with R-32 or R-454B outdoor.

  1. 1 Confirm this pair is actually A2L

    On Goodman GR9T96 FE3 / LE4 / SE5 / rE6-class codes are only valid when this furnace is tied to an R-32 or R-454B outdoor. On R-410A this is a miswired mitigation harness — not a leaking indoor coil.

    Expect: Outdoor refrigerant from the outdoor nameplate, not from memory.

    If fail: Remove / correct the mitigation harness. Do not condemn the IFC.

  2. 2 Sensor location and the mitigation blower

    If it is a real A2L pair, follow the OEM mitigation sequence: sensor location, ventilation blower, relay. Only valid on A2L pairs. On 410A, this is a miswired mitigation harness. Leak sensor location, ventilation blower, and OEM mitigation sequence before you condemn the IFC.

    Expect: Sensor seated where the I/O shows. Mitigation blower runs on a test.

  3. 3 Do not bypass mitigation

    Never jump an A2L alarm to get heat. Find the leak or the failed sensor. Recurring mitigation with a clean sensor is a refrigerant leak until proven otherwise.

    Expect: Alarm clears only after the leak/sensor is fixed.

Workflows

No heat on W1

Tstat calling heat, indoor is cold, or E0/E2/E7.

  1. 1 Prove the call and the live code

    Read the 7-seg before you pull power. Write the code.

    Expect: Write whatever Self-diagnostic IFC · single 7-segment (read Seg3→Seg2→Seg1 left to right) is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Door switch in? 120 VAC at L1, 24 VAC across the fuse (E5 if open).

    Expect: Prove low PS: Low-fire pressure switch must close. If it is already closed with inducer off → E1. If it never closes → E2.

  3. 3 Confirm with a number, then the next part

    W1 present at the IFC (not just at the stat). R to W ~24 VAC. Inducer on low? If silent → inducer / IFC output. If running and E2 → trap, hose, LPS, vent. If E1 with inducer off → unplug LPS. Code change = switch/hose. No change = IFC.

    Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal. · Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Runs on low, will not go high

Comfort complaint or long run times. Often E9.

  1. 1 Prove the call and the live code

    Confirm the thermostat is actually closing W2 (or the IFC staging timer has expired).

    Expect: Write whatever Self-diagnostic IFC · single 7-segment (read Seg3→Seg2→Seg1 left to right) is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Listen for inducer speed-up. No speed-up → W2 / IFC. Speed-up + E9 → high-fire PS path.

    Expect: Prove low PS: Low-fire pressure switch must close. If it is already closed with inducer off → E1. If it never closes → E2.

  3. 3 Confirm with a number, then the next part

    HPS hose on the high tap only. A tee with the LPS is a common first-install miss. Manifold high-fire vs plate. A valve that never opens stage 2 looks like an airflow complaint. Vent and intake sized for high fire on this cabinet — 2" that passed on low will fail on a 100–120 kBtu high fire.

    Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal. · Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

E3 limit trips

Blower on, burners drop, E3.

  1. 1 Prove the call and the live code

    This is a 9-speed ECM. Read the heat tap on the IFC / motor harness before you replace a limit.

    Expect: Write whatever Self-diagnostic IFC · single 7-segment (read Seg3→Seg2→Seg1 left to right) is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Total external static vs the GR9T96 blower chart for this cabinet (B/C/D).

    Expect: Prove low PS: Low-fire pressure switch must close. If it is already closed with inducer off → E1. If it never closes → E2.

  3. 3 Confirm with a number, then the next part

    Filter, wheel, coil. A new 5" media cabinet the installer added will trip E3 all winter. Clock the meter / manifold — overfire trips limits with a clean filter. Secondary / condensate — a drowned coil raises head in the exchanger and trips limit.

    Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal. · Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Flame rod

Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.

Manifold low / high

Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

LPS / HPS

Both NO. Closed only when that inducer speed is making the collector setpoint. Never teed.

HSI

Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use a 80% Norton chart.

ECM heat tap

Match the installer’s tap to the rise range on the rating plate (typically 35–65°F).

Gotchas

  • Techs treat GR9T96 like GMVC96 and start looking for ComfortBridge menus. There are none.
  • E2 vs E9: fixing the trap clears low fire and the callback is ‘still no high fire’ because the HPS hose was never on the high tap.
  • 9-speed ECM on the wrong heat tap is the silent E3 generator. It is not a bad limit.
  • GD9T96 is the downflow twin — drain and secondary orientation change, codes do not.
  • Amana AR9T96 is the same IFC and the same chart. Do not pull a GMVC96 communicating board or a GMEC96 CT motor into this cabinet.
  • Warehouse ‘Goodman 96% IFC’ often ships the communicating board. It will not run this 9-speed motor.

Related plates

Install this plate

Install GR9T96 as the Goodman 24V two-stage 9-speed 96%. Same IFC as AR9T96 — not GMVC96.

Cat IV PVC · 24V W1/W2 · 9-speed tap ECM · dual PS · PCBBF132 family

Cabinet & air

  • Full plate matters: GR9T960403BN vs 1205DN. Heat tap and static tables are per cabinet.
  • GD9T96 is the downflow twin. Do not treat an upflow GR9T96 as a downflow without the OEM kit.
  • 9-speed tap/profile motor. A 14-pin ComfortBridge serial ECM will not run on this IFC.

Vent & condensate

  • PVC 2-pipe or 1-pipe, Cat IV. Prime the trap. Collector hose routing downhill — water in the hose fakes E1/E8.
  • Low-fire PS and high-fire PS are separate. Tee = first-day callback.
  • 40 ng/J Low NOx. Not the SCAQMD ultra-low-NOx plate.

Gas, electrical, thermostat

  • Conventional 24V: Y/Y1 Y2 G R C W/W1 W2. No ComfortBridge pair.
  • Set low-fire manifold, then high. Use the GR9T96 door card, not GMSS96 or GMVC96.
  • Polarity / ground: EA / EEH. Twin terminal unused unless the twinning kit is actually installed.

First fire

  1. 1W1: inducer low → LPS → HSI → low fire → heat tap.
  2. 2W2: inducer high → HPS → second solenoid. Stays on low → E9 / vent / HPS hose.
  3. 3Rise vs this cabinet’s 9-speed heat tap. Move the tap, not the orifice, for airflow-limited rise.

Do not on Goodman GR9T96

  • Do not swap this IFC with a GMVC96 ComfortBridge board. Different motor plug, different display, different recall.
  • Do not apply GMSS96 3-flash language. This is E1/E2 vs E8/E9.
  • Do not use a GMEC96 X-13 motor on the 9-speed harness.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • GR9T96 product pageProduct pageGoodman-badge twin of Amana AR9T96.Open manufacturer PDF
  • GR9T96 specification sheetSpec sheetSearch this plate in the Goodman literature library.Open manufacturer PDF
  • Goodman literature libraryLiterature searchSearch Goodman GR9T96 on the maker’s literature page.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • PWCFURNUQNTE

    warranty sheet

    Goodman gas furnace limited warranty — unit-replacement certificate

    Registered furnace — parts / heat exchanger / unit replacement terms · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal