GR9S80
Single-stage · 9-speed ECM · 80% Cat I
Goodman single-stage 80% 9-speed. Twin of Amana AR9S80. One pressure switch, 9-speed taps, Category I 4" metal vent. E2 is a chimney. Not GMS80 flash and not GR9S96 (96% 9-speed EE card).
Not AR9S80 only by badge — use this Goodman plate so the SKU search hits. Not GR9S96 (PVC, EE0/EE1/EE2). Not GR9T80 (two-stage, E8/E9). Not GMS80 (LED 1–9).
AFUE
80% single-stage · Cat I 4" metal
Blower
9-speed taps. Heat default typically F02. F01 not for heat.
Sister SKU
GD9S80 downflow · Amana AR9S80 / AD9S80 same IFC idea
This board
Self-diagnostic IFC · single 7-segment · wiring 0140F20001-B
- door card is wiring 0140F20001-B. Read left to right. Do not kill power — that clears the active code.
- Codes are E0–E7, EA, Eb, Ec, Ed, En, plus TWIN, LE1, EEH, and A2L pair tokens. One pressure switch only — E1 stuck closed, E2 open.
- E2 is Category I draft: chimney, B-vent, 4" metal, inducer, common-vent. It is not a 96% trap / PVC / collector story.
- A2L pair codes only apply when this furnace is tied to an R-32 / A2L outdoor. Ignore them on R-410A pairs.
In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.
Universal swap
Same 9-speed story as AR9S80. ICM2810 only if the silk is PCBBF136 / 140.
Silk: PCBBF136 · PCBBF140 · 0140F20001-B
- 50A55-843 ‘80% universal’ — that carton is PSC, not this 9-speed.
- GR9S96 EE card.
After you pull the dead card
- 1Kill power. Photograph the silk-screen part number on the dead board before you pull it.
- 2Match staging (1 vs 2 vs modulating), igniter (carbide / nitride / spark), and motor (PSC / ECMx / 9-speed tap / serial VS).
- 3Set heat-off delay and any 80+/90+ jumper to the door card. Prove one full try and flame µA before you leave.
Field wiring
Written landings for Goodman GR9S80. Not a factory schematic.
Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → transformer → R120V in, 24V out
- 2Call. Stat W → IFC W~24 VAC
- 3Draft. IFC → inducer → PS close120V motor, 24V prove
- 4Ignite. IFC → HSI120 VAC
- 5Gas. IFC → valve~24 VAC
- 6Flame. Rod → IFCµA DC
- 7Blow. IFC → heat speedAfter flame prove
This indoor
80% 9-speed. Same Y/W landing. Metal vent.
24V single-stage heat
Door card is one-stage. Twin terminal empty unless the job is actually twinned.
Wall thermostat
Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.
- R24V hot from the IFC24V
- CCommon24V
- WHeat24V
- YCool — also starts the outdoor24V
- GFan24V
Furnace IFC
Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.
- RHot to the stat24V
- CCommon — must reach the outdoor24V
- WHeat call24V
- YCool in / cool out24V
- GBlower24V
- TWINEmpty unless twinned24V
Landing
- 24VIFC Rstat R
~24 VAC hot
- 24VIFC Cstat Coutdoor C
Common
- 24VStat WIFC W
Heat. Stays in this cabinet.
- 24VStat YIFC Youtdoor Y
Cool / contactor
- 24VStat GIFC G
Fan. Does not go outdoors.
IFC harness — single-stage heat
After W arrives. This is the gas train, not the thermostat strip.
Transformer + fuse
120V primary. 24V secondary. Dark stat = fuse / door / transformer first.
- L1 / N120V to the IFCLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout in series. Open anywhere kills heat.
- DOORInterlock24V
- LIMITMain limit — rise / no airflow24V
- ROLLOUTManual reset. Do not jumper and leave24V
Inducer + one pressure switch
W → inducer 120V → PS closes → IFC continues. One hose, one switch.
- IND120V from the IFC to the inducerLine
- PS24V prove back to the IFC24V
- HOSESingle hose. Do not add a second because two-stage boards have two.24V
HSI + single valve
Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.
- HSI120V hot-surface igniter — not 24VLine
- VALVE24V to the single solenoid24V
- FLAMEµA DC on the rod. Not a 24V circuit24V
9-speed tap ECM
F01–F09 on the harness. Heat tap and cool tap are separate. Not a 14-pin serial motor and not a run cap.
- F01–F09Speed taps on the IFC / harness24V
- HEATDefault often F02 — F01 is an E3 generator on many 9-speed doors24V
- COOL / Y / GCool tap. Wrong tap freezes the coil and looks like LPS outdoors.24V
Landing
- LineL1IFCinducer
120 VAC after W
- 24VIFCPSIFC
~24 VAC prove. Open PS = no ignition.
- LineIFCHSI
120 VAC during trial
- 24VIFCgas valve
~24 VAC after flame prove starts
- 24VFlame rodIFC
µA DC. Not 24V.
- LineIFCblower
IFC heat speed / tap
Prove it
- 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
- W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.
Do not
- Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
- Do not hunt W2 / E8 / high-fire on a one-stage door.
- TWIN must be empty on a standalone.
9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.
Sequence
- 1
W
IFC proves limits/rollout closed, starts the single-speed inducer.
- 2
Prove PS
The only pressure switch must close against the metal vent. Already closed with inducer off → E1. Never closes → E2 (chimney / B-vent / 4" / inducer).
- 3
HSI / valve
Hot-surface igniter warm-up, then the single solenoid. Open igniter → En / E7. Failures stack toward E0.
- 4
Blower
Heat-on delay, then the 9-speed ECM on the selected heat tap (factory F02). F01 is not recommended for heating.
- 5
Satisfied
Valve off, inducer post-purge, blower heat-off delay. Unexpected flame → E4.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
E0
Retry / recycle lockout
Too many failed ignition attempts or flame losses on this call.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Goodman GR9S80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Watch one full try: inducer, HSI glow, valve click, flame, µA.
Expect: Flame rod: µA per this door card. Rising while running is the goal.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Gas supply and manifold vs this 80% plate.
Expect: Manifold: Single-stage plate value. Reduce input 4% per 1000' above 4500'.
3 Prove it is not a switch opening
Watch the live Goodman GR9S80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Ground and flame-rod cleanliness.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E1
PS stuck closed
The only pressure switch is made with the inducer off.
1 Unplug the switch with the inducer off
On Goodman GR9S80 this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the only PS. Code change = welded switch or residual draft in the hose.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Hose holding chimney draft with inducer off — wind on a tall stack can fake E1.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Goodman GR9S80 IFC input is shorted. Do not keep swapping switches. IFC input shorted — only after the switch ohms open.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
E2
PS open — metal-vent draft
Inducer is on and the only switch will not close. This is a chimney / B-vent / 4" metal / inducer call — not a drowned 96% trap.
1 Prove inducer and the live code
Do not pull power — that clears the Goodman GR9S80 active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer 120 VAC and spinning. A dead inducer is E2 with a perfect switch.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Chimney, B-vent, common vent, cap, liner, and 4" connector. Single-wall connector needs 6" to combustibles.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Cold chimney that will not establish draft on a first morning call. Spillage at the draft hood / collector.
Expect: Pressure switch: One NO switch. Closed only with inducer up against the metal vent. Not a 96% collector tap.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E3
Open high limit
Primary limit opened. Airflow or overfire.
1 Airflow before you touch the limit
On Goodman GR9S80 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Heat tap first. Factory default F02. F01 is not recommended for heating.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Goodman GR9S80 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Filter, wheel, coil sitting on an 80%. A new media cabinet will trip E3 all winter.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). TES vs the AR9S80 blower chart for this cabinet. Rise ranges are 20–50 up to 40–70 on 1205D.
Expect: Manifold: Single-stage plate value. Reduce input 4% per 1000' above 4500'.
E4
Flame when valve should be off
Rod sees flame with the solenoid de-energized.
1 Shut the gas cock first
On Goodman GR9S80 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground or IFC flame circuit.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
E5
Open fuse
24 V fuse on the IFC is open.
1 Find the 24 V short before you replace the fuse
On Goodman GR9S80 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. Short on W, Y, G, humidifier, EAC.
Expect: Fuse out. 24 V transformer still good. Harness isolated.
2 Replace the fuse with the harness off
New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC). Unplug the tstat harness and replace the fuse.
Expect: Fuse holds with harness off. Dies when the shorted lead lands.
3 If it blows with the harness off
Short is on the Goodman GR9S80 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.
Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.
E6
Low flame signal
Flame present, µA below threshold.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Goodman GR9S80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod with a non-scratch pad.
Expect: Flame rod: µA per this door card. Rising while running is the goal.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Chassis ground, manifold, LP conversion (this plate uses LPM-31 with an LP switch — not LPM-33).
Expect: Manifold: Single-stage plate value. Reduce input 4% per 1000' above 4500'.
3 Prove it is not a switch opening
Watch the live Goodman GR9S80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E7
Igniter relay fault
IFC did not see the igniter circuit behave as commanded.
1 Ohms at the igniter, then at the IFC
On Goodman GR9S80 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Hot-surface igniter ohms cold per this sticker — not an AR9S96 nitride chart.
Expect: HSI: Hot-surface igniter per SS — not the AR9S96 nitride sticker. 120 VAC during warm-up.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. 120 VAC during warm-up. Cracked element.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
EA
Line polarity / ground
L1/N reversed or chassis ground missing.
1 Hot and neutral at the IFC, not the disconnect
On Goodman GR9S80 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot and neutral at the IFC. Burner-box ground screw.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
Eb / Ec
Gas valve circuit
Internal (Eb) or external (Ec) gas-valve electrical fault.
1 Coil ohms and 24 VAC during trial only
On Goodman GR9S80 measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Valve coil ohms, 24 VAC at the harness during trial.
Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.
2 Do not energize a leaking valve
If the unexpected-flame code is also in history, shut the cock and replace the valve. Applying 24 V as a ‘test’ and walking away is a gas leak.
Expect: No flame with the cock shut and solenoids de-energized.
3 IFC relay vs the valve
Voltage at the harness and a dead coil = valve. No voltage during a known trial = IFC relay or a lockout that never opened the valve (look at the live code).
Expect: Known trial + 24 VAC + good coil = flame. Otherwise IFC.
Ed
Open rollout
Manual-reset rollout. Treat as flame outside the exchanger until proven otherwise.
1 Treat this as flame outside the exchanger
Do not reset the Goodman GR9S80 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Primary exchanger, burner alignment, crossover, blocked flue / chimney. Reset only after the cause is fixed.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Goodman GR9S80 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
En
Igniter open
Igniter circuit measures open.
1 Ohms at the igniter, then at the IFC
On Goodman GR9S80 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the igniter plug, then at the IFC.
Expect: HSI: Hot-surface igniter per SS — not the AR9S96 nitride sticker. 120 VAC during warm-up.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Harness rub-through.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
EEH
Grounding error
IFC failed its ground check (sister to EA).
1 Hot and neutral at the IFC, not the disconnect
On Goodman GR9S80 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green ground to cabinet and IFC. Painted screw, missing star washer.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
TWIN
Twin error
Twinning miswire or twin terminal active on a standalone unit. Door card lists TWIN on 0140F20001-B.
1 Is this cabinet actually twinned?
On a standalone Goodman GR9S80, nothing belongs on the TWIN terminal. A leftover jumper throws this. If not twinned, nothing should be on the TWIN terminal.
Expect: TWIN empty on a single cabinet.
2 Twinned pair must be the same IFC family
Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin. Twinned pair must be same family / same IFC revision.
Expect: Same model family, same IFC, kit installed per the twinning sheet.
3 Phasing and 24 V
Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.
Expect: In-phase 24 V. Continuous twin lead.
LE1
Low circulator current
9-speed ECM current too low.
1 Is the wheel free?
Spin the Goodman GR9S80 blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Harness seated at motor and IFC. A half-seated tap plug throws this.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Locked rotor, wet winding, or a PSC motor someone hung on this IFC.
Expect: ECM taps: Heat default F02. Cool default F04. Two-stage outdoor: 0805C Y2=F08 / Y1=F02; 1205D Y2=F06 / Y1=F05.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
FE3 / LE4 / SE5 / rE6
A2L mitigation
Leak / comm / relay alarm from the A2L board when paired with an R-32 / A2L outdoor.
1 Confirm this pair is actually A2L
On Goodman GR9S80 FE3 / LE4 / SE5 / rE6-class codes are only valid when this furnace is tied to an R-32 or R-454B outdoor. On R-410A this is a miswired mitigation harness — not a leaking indoor coil.
Expect: Outdoor refrigerant from the outdoor nameplate, not from memory.
If fail: Remove / correct the mitigation harness. Do not condemn the IFC.
2 Sensor location and the mitigation blower
If it is a real A2L pair, follow the OEM mitigation sequence: sensor location, ventilation blower, relay. Only valid on A2L pairs. On 410A this is a miswired mitigation harness.
Expect: Sensor seated where the I/O shows. Mitigation blower runs on a test.
3 Do not bypass mitigation
Never jump an A2L alarm to get heat. Find the leak or the failed sensor. Recurring mitigation with a clean sensor is a refrigerant leak until proven otherwise.
Expect: Alarm clears only after the leak/sensor is fixed.
Workflows
E2 on GR9S80
No heat, inducer running.
1 Prove the call and the live code
One switch. Metal vent. Do not dump a 96% trap.
Expect: Write whatever Self-diagnostic IFC · single 7-segment · wiring 0140F20001-B is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Cap, liner, 4" connector, common vent, inducer wheel.
Expect: Prove PS: The only pressure switch must close against the metal vent. Already closed with inducer off → E1. Never closes → E2 (chimney / B-vent / 4" / inducer).
3 Confirm with a number, then the next part
Heat tap F02. F01 is an E3 generator on this family.
Expect: Pressure switch: One NO switch. Closed only with inducer up against the metal vent. Not a 96% collector tap. · Manifold: Single-stage plate value. Reduce input 4% per 1000' above 4500'.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Pressure switch
One NO switch. Closed only with inducer up against the metal vent. Not a 96% collector tap.
Manifold
Single-stage plate value. Reduce input 4% per 1000' above 4500'.
Flame rod
µA per this door card. Rising while running is the goal.
HSI
Hot-surface igniter per SS — not the AR9S96 nitride sticker. 120 VAC during warm-up.
ECM taps
Heat default F02. Cool default F04. Two-stage outdoor: 0805C Y2=F08 / Y1=F02; 1205D Y2=F06 / Y1=F05.
Vent
4" Category I metal. Single-wall connector 6" to combustibles. B-vent 1".
Gotchas
- GR9S96 is the 96% 9-speed Goodman — EE card, PVC. Wrong page if you have a chimney.
- GMS80 is the older LED 80%. If you are counting flashes, leave this 7-seg chart.
Related plates
Install this plate
Install Goodman GR9S80 as Single-stage · 9-speed ECM · 80% Cat I.
Single-stage · 9-speed ECM · 80% Cat I
This plate — not the sister SKU
- Not AR9S80 only by badge — use this Goodman plate so the SKU search hits. Not GR9S96 (PVC, EE0/EE1/EE2). Not GR9T80 (two-stage, E8/E9). Not GMS80 (LED 1–9).
- GR9S96 is the 96% 9-speed Goodman — EE card, PVC. Wrong page if you have a chimney.
- GMS80 is the older LED 80%. If you are counting flashes, leave this 7-seg chart.
IFC on this door
- door card is wiring 0140F20001-B. Read left to right. Do not kill power — that clears the active code.
- Codes are E0–E7, EA, Eb, Ec, Ed, En, plus TWIN, LE1, EEH, and A2L pair tokens. One pressure switch only — E1 stuck closed, E2 open.
- E2 is Category I draft: chimney, B-vent, 4" metal, inducer, common-vent. It is not a 96% trap / PVC / collector story.
- A2L pair codes only apply when this furnace is tied to an R-32 / A2L outdoor. Ignore them on R-410A pairs.
Hardware
- AFUE: 80% single-stage · Cat I 4" metal
- Blower: 9-speed taps. Heat default typically F02. F01 not for heat.
- Sister SKU: GD9S80 downflow · Amana AR9S80 / AD9S80 same IFC idea
First fire
- 1One switch. Metal vent. Do not dump a 96% trap.
- 2Cap, liner, 4" connector, common vent, inducer wheel.
- 3Heat tap F02. F01 is an E3 generator on this family.
Do not on Goodman GR9S80
- Not AR9S80 only by badge — use this Goodman plate so the SKU search hits. Not GR9S96 (PVC, EE0/EE1/EE2). Not GR9T80 (two-stage, E8/E9). Not GMS80 (LED 1–9).
- GR9S96 is the 96% 9-speed Goodman — EE card, PVC. Wrong page if you have a chimney.
- GMS80 is the older LED 80%. If you are counting flashes, leave this 7-seg chart.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Goodman literature libraryLiterature searchSearch the exact plate (GR9T960804CN, GR9S960603BN). Full I/O PDFs are often dealer-gated.Open manufacturer PDF
- Goodman literature libraryLiterature searchSearch Goodman GR9S80 on the maker’s literature page.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
PWGFURNSUNTE
warranty sheetGoodman gas furnace limited warranty — standard certificate
Registered 80% 9-speed furnace warranty terms · Limited warranty certificate
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal