GR9S96
Single-stage · 9-speed ECM · 96% AFUE · 7-seg EE-codes
Current Goodman single-stage 96% with a 9-speed ECM and a 7-segment IFC that speaks EE0 / EE1 / EE2 (not flash, not GR9T96 E8/E9). One pressure switch, one inducer speed. GD9S96 is the downflow twin. GR9S92 is the 92% cousin — same EE-card, still a collector. This is the plate replacing a lot of GMSS96 flash boards in the field.
Not GR9T96 (two-stage, E1/E2 vs E8/E9, dual PS). Not GMSS96 (LED 1–9 flash, no 7-seg). Not GMVC96 (ComfortBridge triple 7-seg, serial VS). Not Amana AR9S96 (same one-PS 9-speed idea, door card 0140F20003-B prints E0–E7 — not EE0/EE1/EE2). Do not apply AR9T96 high-fire codes — there is no high-fire switch.
Input / AFUE
Up to 96% · 40–120 kBtu · GR9S92 is the 92% cousin
Staging
Single-stage gas valve · single-speed inducer · one pressure switch
Blower
9-speed ECM taps — not communicating, not a flash-board PSC
Display
7-segment · read Seg3→Seg2→Seg1 · EE0 / EE1 / EE2 / E11
Ignition
120 VAC silicon nitride HSI
Tstat
Conventional 24V · W Y G R C — leftover W2 is unused
Sister SKU
GD9S96 downflow. Amana AR9S96 looks similar but uses 0140F20003-B E0–E7 — not this EE card.
This board
Self-diagnostic IFC · single 7-segment (Seg3→Seg2→Seg1)
- Read left to right. This card prints EE0 / EE1 / EE2 — three characters, E E and a digit. That is not GR9T96 E0 / E1 / E2, even though the physics rhyme.
- EE1 (E E 1) is PS stuck closed. E11 (E 1 1) is open rollout. Those are different codes. Write all three characters.
- One pressure switch only. There is no E8/E9 high-fire pair on this IFC.
- A2L pair codes (EAF, EAL, EAS, Ear) only apply when this furnace is tied to an R-32 / A2L outdoor. Ignore them on R-410A pairs.
In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.
Universal swap
9-speed tap, Goodman EE card. No 50A55. ICM2810 only if the silk is PCBBF136 or PCBBF140 — not because the cabinet says GR9S96.
Silk: PCBBF136 · PCBBF140
White-Rodgers
—ICM
- ICM2810
for PCBBF136 / PCBBF140 only. This EE door is not the Amana 0140F20003-B card.
Honeywell
—- 50A55-843 / 50M56U-843 / 50M56X-843 / S9200U1000.
- 50M56-743 (PCBBF132 two-stage AR9T96/GR9T96).
- Amana AR9S96 board — different door (E0–E7 vs EE0/EE1/EE2).
After you pull the dead card
- 1Kill power. Photograph the silk-screen part number on the dead board before you pull it.
- 2Match staging (1 vs 2 vs modulating), igniter (carbide / nitride / spark), and motor (PSC / ECMx / 9-speed tap / serial VS).
- 3Set heat-off delay and any 80+/90+ jumper to the door card. Prove one full try and flame µA before you leave.
Field wiring
Written landings for Goodman GR9S96. Not a factory schematic.
Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → transformer → R120V in, 24V out
- 2Call. Stat W → IFC W~24 VAC
- 3Draft. IFC → inducer → PS close120V motor, 24V prove
- 4Ignite. IFC → HSI120 VAC
- 5Gas. IFC → valve~24 VAC
- 6Flame. Rod → IFCµA DC
- 7Blow. IFC → heat speedAfter flame prove
This indoor
EE-card 9-speed. One W. Not GMSS96 LED.
24V single-stage heat
Door card is one-stage. Twin terminal empty unless the job is actually twinned.
Wall thermostat
Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.
- R24V hot from the IFC24V
- CCommon24V
- WHeat24V
- YCool — also starts the outdoor24V
- GFan24V
Furnace IFC
Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.
- RHot to the stat24V
- CCommon — must reach the outdoor24V
- WHeat call24V
- YCool in / cool out24V
- GBlower24V
- TWINEmpty unless twinned24V
Landing
- 24VIFC Rstat R
~24 VAC hot
- 24VIFC Cstat Coutdoor C
Common
- 24VStat WIFC W
Heat. Stays in this cabinet.
- 24VStat YIFC Youtdoor Y
Cool / contactor
- 24VStat GIFC G
Fan. Does not go outdoors.
IFC harness — single-stage heat
After W arrives. This is the gas train, not the thermostat strip.
Transformer + fuse
120V primary. 24V secondary. Dark stat = fuse / door / transformer first.
- L1 / N120V to the IFCLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout in series. Open anywhere kills heat.
- DOORInterlock24V
- LIMITMain limit — rise / no airflow24V
- ROLLOUTManual reset. Do not jumper and leave24V
Inducer + one pressure switch
W → inducer 120V → PS closes → IFC continues. One hose, one switch.
- IND120V from the IFC to the inducerLine
- PS24V prove back to the IFC24V
- HOSESingle hose. Do not add a second because two-stage boards have two.24V
HSI + single valve
Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.
- HSI120V hot-surface igniter — not 24VLine
- VALVE24V to the single solenoid24V
- FLAMEµA DC on the rod. Not a 24V circuit24V
9-speed tap ECM
F01–F09 on the harness. Heat tap and cool tap are separate. Not a 14-pin serial motor and not a run cap.
- F01–F09Speed taps on the IFC / harness24V
- HEATDefault often F02 — F01 is an E3 generator on many 9-speed doors24V
- COOL / Y / GCool tap. Wrong tap freezes the coil and looks like LPS outdoors.24V
Landing
- LineL1IFCinducer
120 VAC after W
- 24VIFCPSIFC
~24 VAC prove. Open PS = no ignition.
- LineIFCHSI
120 VAC during trial
- 24VIFCgas valve
~24 VAC after flame prove starts
- 24VFlame rodIFC
µA DC. Not 24V.
- LineIFCblower
IFC heat speed / tap
Prove it
- 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
- W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.
Do not
- Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
- Do not hunt W2 / E8 / high-fire on a one-stage door.
- TWIN must be empty on a standalone.
9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.
Sequence
- 1
W
IFC proves limits/rollout closed, starts the single-speed inducer.
- 2
Prove PS
The only pressure switch must close. Already closed with inducer off → EE1. Never closes → EE2.
- 3
HSI / valve
Nitride warm-up, then the single solenoid. Open igniter → EEn. Failures stack toward EE0.
- 4
Blower
Heat-on delay, then the 9-speed ECM on the selected heat tap. Wrong tap is the silent EE3.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
EEE
Internal / IRQ loss
IFC internal fault or interrupt loss.
1 Write the live code and watch one cycle
On Goodman GR9S96 read Self-diagnostic IFC · single 7-segment (Seg3→Seg2→Seg1) before you pull power. Write EEE exactly. Watch one full sequence and note which step dies. Power cycle once. Repeat EEE = board, after 120/24 and the door switch are proven.
Expect: W: IFC proves limits/rollout closed, starts the single-speed inducer.
2 Prove the circuit this code names
Use the Goodman GR9S96 door card and the test points on this plate. Isolate the named switch, sensor, or output with a meter — do not swap the IFC first.
Expect: Pressure switch: One NO switch. Closed only with inducer up.
3 Confirm with a number, then the next part
If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.
Expect: Display: Three characters left to right. EE1 ≠ E11.
EE0
Retry / recycle lockout
Too many failed ignition attempts or flame losses on this call.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Goodman GR9S96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Watch one full try: inducer, HSI, valve, flame, µA.
Expect: Flame rod: µA per this door card — not the GMSS96 flash sticker.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Gas, rod, ground. Do not keep resetting.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Goodman GR9S96 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
EE1
PS stuck closed
The only pressure switch is made with the inducer off. Display is E E 1 — not E11 (rollout).
1 Treat this as flame outside the exchanger
Do not reset the Goodman GR9S96 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Unplug the PS. If the code changes, switch is welded or the hose is holding residual draft. Hose downhill to the collector? Water fakes a closed switch.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Goodman GR9S96 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
EE2
PS open
Inducer is on and the only switch will not close. The winter 96% call on this new 7-seg single.
1 Prove inducer and the live code
Do not pull power — that clears the Goodman GR9S96 active code. Write EE2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer 120 VAC and spinning.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Collector, trap, PVC intake/exhaust, ice, wind.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Hose on the only tap. There is no high-fire hose to move.
Expect: Pressure switch: One NO switch. Closed only with inducer up.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
EE3
Open high limit
Primary limit opened. Airflow or overfire.
1 Airflow before you touch the limit
On Goodman GR9S96 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). This is a 9-speed ECM. Read the heat tap before you replace a limit.
Expect: 9-speed heat tap: Match the installer’s tap to the rise range on the rating plate (typically 35–65°F).
2 Measure static and temperature rise
Total external static vs the Goodman GR9S96 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Filter, coil, TES vs the GR9S96 blower chart for this cabinet (A/B/C/D).
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Manifold vs plate — overfire trips limits with a clean filter.
Expect: Manifold on plate. Limit closed when cool.
EE4
Flame when valve should be off
Rod sees flame with the solenoid de-energized.
1 Shut the gas cock first
On Goodman GR9S96 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
EE5
Open fuse
24 V fuse on the IFC is open.
1 Find the 24 V short before you replace the fuse
On Goodman GR9S96 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. Short on W, Y, G, humidifier, EAC.
Expect: Fuse out. 24 V transformer still good. Harness isolated.
2 Replace the fuse with the harness off
New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC). Unplug the tstat harness and replace the fuse.
Expect: Fuse holds with harness off. Dies when the shorted lead lands.
3 If it blows with the harness off
Short is on the Goodman GR9S96 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.
Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.
EE6
Low flame signal
Flame present, µA below threshold.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Goodman GR9S96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod with a non-scratch pad.
Expect: Flame rod: µA per this door card — not the GMSS96 flash sticker.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Chassis ground, manifold, LP conversion.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Goodman GR9S96 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
EEL
Ignitor relay fault
IFC did not see the igniter circuit behave as commanded.
1 Ohms at the igniter, then at the IFC
On Goodman GR9S96 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Igniter ohms cold, 120 VAC during warm-up, cracked nitride.
Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
EEA
Reversed polarity / ground
L1/N reversed or chassis ground missing.
1 Hot and neutral at the IFC, not the disconnect
On Goodman GR9S96 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot and neutral at the IFC. Burner-box ground screw.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
EEb / EEC
Gas valve circuit
Internal (EEb / ASME) or external (EEC) gas-valve electrical fault.
1 Coil ohms and 24 VAC during trial only
On Goodman GR9S96 measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Valve coil ohms, 24 VAC at the harness during trial.
Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.
2 Do not energize a leaking valve
If the unexpected-flame code is also in history, shut the cock and replace the valve. Applying 24 V as a ‘test’ and walking away is a gas leak.
Expect: No flame with the cock shut and solenoids de-energized.
3 IFC relay vs the valve
Voltage at the harness and a dead coil = valve. No voltage during a known trial = IFC relay or a lockout that never opened the valve (look at the live code).
Expect: Known trial + 24 VAC + good coil = flame. Otherwise IFC.
E11
Open rollout
Display is E 1 1 — not EE1 (PS closed). Manual-reset rollout. Treat as flame outside the exchanger until proven otherwise.
1 Treat this as flame outside the exchanger
Do not reset the Goodman GR9S96 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Primary exchanger, burner alignment, crossover, blocked secondary / condensate / flue. Reset only after the cause is fixed.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Goodman GR9S96 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
EEn
Ignitor open
Igniter circuit measures open.
1 Ohms at the igniter, then at the IFC
On Goodman GR9S96 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the igniter plug, then at the IFC.
Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Harness rub-through on the collector.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
EEH
Twin error
Twinning miswire or twin terminal active on a standalone unit.
1 Is this cabinet actually twinned?
On a standalone Goodman GR9S96, nothing belongs on the TWIN terminal. A leftover jumper throws this. If not twinned, nothing should be on the TWIN terminal.
Expect: TWIN empty on a single cabinet.
2 Twinned pair must be the same IFC family
Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin.
Expect: Same model family, same IFC, kit installed per the twinning sheet.
3 Phasing and 24 V
Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.
Expect: In-phase 24 V. Continuous twin lead.
E10
Grounding error
IFC failed its ground check (sister to EEA).
1 Hot and neutral at the IFC, not the disconnect
On Goodman GR9S96 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green ground to cabinet and IFC. Painted screw, missing star washer.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
EbL / EbU
Circulator current
9-speed ECM current too low (EbL) or unexpected (EbU).
1 Is the wheel free?
Spin the Goodman GR9S96 blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Harness seated at motor and IFC. A half-seated tap plug throws these.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Locked rotor, wet winding, or a PSC motor someone hung on this IFC.
Expect: 9-speed heat tap: Match the installer’s tap to the rise range on the rating plate (typically 35–65°F).
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
EAF / EAL / EAS / Ear
A2L mitigation
Leak / comm / relay alarm from the A2L board when paired with R-32 or R-454B outdoor.
1 Confirm this pair is actually A2L
On Goodman GR9S96 FE3 / LE4 / SE5 / rE6-class codes are only valid when this furnace is tied to an R-32 or R-454B outdoor. On R-410A this is a miswired mitigation harness — not a leaking indoor coil.
Expect: Outdoor refrigerant from the outdoor nameplate, not from memory.
If fail: Remove / correct the mitigation harness. Do not condemn the IFC.
2 Sensor location and the mitigation blower
If it is a real A2L pair, follow the OEM mitigation sequence: sensor location, ventilation blower, relay. Only valid on A2L pairs. On 410A this is a miswired mitigation harness.
Expect: Sensor seated where the I/O shows. Mitigation blower runs on a test.
3 Do not bypass mitigation
Never jump an A2L alarm to get heat. Find the leak or the failed sensor. Recurring mitigation with a clean sensor is a refrigerant leak until proven otherwise.
Expect: Alarm clears only after the leak/sensor is fixed.
Workflows
EE2 no heat
Inducer runs, 7-seg EE2, no ignition. Overnight 96% single.
1 Prove the call and the live code
Write E E 2 — not GMSS96 3-flash and not GR9T96 E2/E9.
Expect: Write whatever Self-diagnostic IFC · single 7-segment (Seg3→Seg2→Seg1) is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Prove inducer 120 VAC and spinning.
Expect: Prove PS: The only pressure switch must close. Already closed with inducer off → EE1. Never closes → EE2.
3 Confirm with a number, then the next part
Open the trap and the collector. GR9S96 still drowns overnight. One hose, one switch. Ohms the PS with inducer on (close) and off (open). If PS closes and IFC still EE2s, IFC input is the fault.
Expect: Display: Three characters left to right. EE1 ≠ E11. · Pressure switch: One NO switch. Closed only with inducer up.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
EE3 limit trips
Heat works, then drops, EE3.
1 Prove the call and the live code
This is a 9-speed ECM. Read the heat tap before you change a limit.
Expect: Write whatever Self-diagnostic IFC · single 7-segment (Seg3→Seg2→Seg1) is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
TES vs the GR9S96 chart for this cabinet letter (A/B/C/D).
Expect: Prove PS: The only pressure switch must close. Already closed with inducer off → EE1. Never closes → EE2.
3 Confirm with a number, then the next part
Filter, wheel, coil. A new 5" media cabinet is the usual. Clock the meter / manifold — overfire trips limits with a clean filter.
Expect: Display: Three characters left to right. EE1 ≠ E11. · Pressure switch: One NO switch. Closed only with inducer up.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Which Goodman 96% is this?
Plate is oily or the last tech mixed boards.
1 Prove the call and the live code
Single 7-seg with EE0/EE1/EE2 on the door + 9-speed tap motor + one PS = GR9S96. Stay here.
Expect: Write whatever Self-diagnostic IFC · single 7-segment (Seg3→Seg2→Seg1) is showing. In standby (no W/Y/G), hold the fault-recall pushbutton more than 2 seconds. Last 6 faults play most-recent first. Power cycle erases the active code, not always the stored stack.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Single 7-seg with E8/E9 on the door + two PS = GR9T96.
Expect: Prove PS: The only pressure switch must close. Already closed with inducer off → EE1. Never closes → EE2.
3 Confirm with a number, then the next part
Red LED flash 1–9, no 7-seg = GMSS96 / GM9S96. Triple 7-seg + menu buttons + 14-pin serial motor = GMVC96.
Expect: Display: Three characters left to right. EE1 ≠ E11. · Pressure switch: One NO switch. Closed only with inducer up.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Display
Three characters left to right. EE1 ≠ E11.
Pressure switch
One NO switch. Closed only with inducer up.
9-speed heat tap
Match the installer’s tap to the rise range on the rating plate (typically 35–65°F).
Flame rod
µA per this door card — not the GMSS96 flash sticker.
Gotchas
- Warehouse ‘Goodman 96% IFC’ often ships a GR9T96 two-stage board or a GMSS96 flash board. The motor and the door card have to match.
- EE1 is PS closed. E11 is rollout. Reading only the last digit gets someone hurt.
- GMSS96 3-flash videos do not apply. This board does not flash.
Related plates
- amana-ar9s96Amana single-stage 9-speed cousin. One PS, 9-speed taps — but the door is 0140F20003-B E0–E7, not this EE0/EE1/EE2 card.
- goodman-gr9t96Two-stage 9-speed cousin. Dual PS, E1/E2 vs E8/E9. Wrong high-fire codes for this cabinet.
- goodman-gmss96Older single-stage flash 96%. Same one-PS physics, LED 1–9 instead of EE-codes.
- goodman-gms8080% single-stage flash. Same 3-flash idea, metal vent, no collector.
Install this plate
Install GR9S96 as single-stage 9-speed with a 7-seg EE card. It is not GMSS96 and not GR9T96.
Cat IV PVC · single-stage · one PS · 9-speed taps · 7-seg EE0/EE1/EE2/E11 · leftover W2 unused
IFC & motor
- 7-segment, read Seg3→Seg2→Seg1. EE2 is the only pressure-switch open code. There is no E8/E9.
- 9-speed tap ECM like GR9T96 — but one gas stage. Heat tap still has to match this cabinet.
- GD9S96 is downflow. GR9S92 is the 92% cousin (same idea, smaller secondary).
Vent & stat
- One hose, one PS, primed trap. EE2 = inducer / trap / PVC / wind.
- 24V W Y G R C. Cap W2. A W2 jumper will not make this furnace two-stage.
First fire
- 1W: inducer → PS (EE2 if it will not close) → HSI → valve → 9-speed heat tap.
- 2Confirm the door sticker is EE0/EE1/EE2, not the GMSS96 1–9 flash card and not GR9T96 E1–E9.
Do not on Goodman GR9S96
- Do not apply GR9T96 high-fire E8/E9. There is no second switch.
- Do not count LED flashes. If you are counting flashes you are on GMSS96.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- GR9S96 product pageProduct pageSingle-stage 9-speed 96% — EE-codes, not GMSS96 flash.Open manufacturer PDF
- GR9S96 specification sheetSpec sheetSearch this plate in the Goodman literature library.Open manufacturer PDF
- Goodman literature libraryLiterature searchSearch Goodman GR9S96 on the maker’s literature page.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
PWCFURNUQNTE
warranty sheetGoodman gas furnace limited warranty — unit-replacement certificate
Registered furnace — parts / heat exchanger / unit replacement terms · Limited warranty certificate
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal