Goodman/Amana two-stage or communicating heat pump outdoor (GSZC18 / GSZC16 / ASZC18). Reversing valve plus defrost control live on the outdoor board. Codes are outdoor, not furnace E-codes. GSZB16 is listed as a search alias only — many GSZB units are single-stage with a simpler defrost board.
Not GSXC18 (AC-only, no reversing valve, no defrost). Not GSX14 piston AC. GSZB14 / GSZB16 single-stage heat pumps use a simpler time/temp defrost board — do not apply this communicating / two-stage outdoor chart to those DST boards.
Two-stage (GSZC) · GSZB single-stage cousins use a different defrost board
Reversing valve
Present. Energize direction is board-specific — read the outdoor diagram
Defrost
Timed / demand on the outdoor control (not a furnace IFC function)
Pair
ComfortBridge indoor (GMVC / AVPTC) or 24V Y1/Y2 + O/B
Sister SKU
GSZC16 · Amana ASZC18 same family
This board
Outdoor heat-pump control · defrost + RV + pressure
Codes live on the outdoor board. Indoor furnace E2/E9 is a different chart.
HPS / LPS are pressure. Defrost-sensor and ‘stuck in defrost’ are this board, not the indoor IFC.
Comm / U-style codes are valid only on a ComfortBridge pair. On 24V Y1/Y2 they mean a miswire.
Write the outdoor LED/display before you pull the disconnect.
Sequence
Y1 cool. Outdoor runs cool capacity. Indoor blower on cool. Reversing valve in the cool position per THIS outdoor diagram.
O/B reversing valve. Read the outdoor diagram. Do not assume Carrier O-on-cool. Goodman boards have shipped O energized in cool on some and B energized in heat on others. Confirm B vs O on the board silkscreen / IO before you swap a stat or an air handler.
Heat (HP). Y (and O/B as required) at the outdoor. Compressor and outdoor fan in heat. Indoor is the condenser. If the outdoor is running in cool while the house wants heat, the RV did not shift or O/B is wrong.
Defrost timed / demand. Outdoor board terminates defrost on coil sensor and/or time. Sensor open/short or a failed board leaves the unit iced or stuck in defrost (outdoor fan off, RV in cool, steam / water under the unit for too long).
Faults on this IFC
HPS
High pressure
lockout
Discharge / liquid pressure opened the high-pressure switch. In heat this is often indoor airflow; in cool this is outdoor airflow or overcharge.
SC / SH in the running mode. Restriction vs overcharge.
Fan running in that mode? A unit stuck in defrost will look like a cool-mode HPS if you are not watching the RV.
LPS
Low pressure
lockout
Suction dropped out — charge, airflow in the evaporating coil, or a coil iced over in heat.
Heat mode: outdoor coil iced, outdoor fan, defrost not running. Do not add gas on an iced outdoor.
Cool mode: indoor airflow, freeze, TXV.
Weigh-out if the history is a leak. LPS on a heat pump is not automatically ‘low on 410A.’
Defrost sensor / stuck in defrost
Defrost path
lockout
Outdoor coil sensor open/short/out of range, or the board will not leave defrost (fan off, RV shifted to cool, long steam).
Ohms the outdoor coil / defrost sensor vs the board chart. Unplugged sensor is a stuck-defrost classic.
Board initiating defrost on time with a warm coil? Bad sensor or bad board — prove the sensor first.
Outdoor fan must restart when defrost terminates. A dead fan motor ices the coil again on the next heat call.
RV / no shift
Reversing valve / no shift
lockout
Unit runs the opposite mode, or pressures never swap when O/B is commanded.
Voltage at the RV solenoid during the call that should energize it. Confirm O vs B on THIS outdoor diagram — do not assume Carrier O-on-cool.
Solenoid ohms / mechanical valve stuck. Tap test is not a repair.
Suction line temp and gauge swap are the prove. Indoor blowing cool on a heat call with the outdoor running is RV or O/B until proven otherwise.
U / Comm
ComfortBridge / U-style comm
lockout
Indoor-outdoor data pair. Valid only on a communicating pair (GMVC / AVPTC / AMVC). On a 24V furnace indoor this is a miswire, not a failed outdoor board.
Data pair polarity, splices, outdoor board power.
Indoor must be a communicating IFC. GR9T96 / GMEC96 / GMSS96 cannot clear a U / comm fault on data wire.
U4-class comm with a 24V furnace: land Y1/Y2/O/B/C or change the indoor. The outdoor will not learn 24V through the data pins.
Outdoor fan
Failed outdoor fan
lockout
Fan not running in cool, or not restarting after defrost in heat. Ices the outdoor in heat; high-heads in cool.
Voltage at the fan motor / ECM plug when the board is commanding fan.
Capacitor only on PSC fans — many of these outdoors are ECM. Confirm the motor family.
Blade ice, seized bearing, control output. A fan that dies mid-defrost leaves a block of ice and an LPS/HPS sandwich.
Workflows
No heat pump heat
Indoor calling heat, outdoor running in cool or not shifting, house cold.
Confirm the indoor is actually asking the outdoor for HP heat — not W-only furnace heat with Y open.
Read O vs B on the outdoor diagram. A Carrier-wired O-on-cool stat on a B-on-heat Goodman board runs the RV backwards.
Voltage at the RV solenoid on the call that should energize it. No voltage → board / O-B landing. Voltage, no shift → valve.