Goodman
GSXC18 AC · Two-stage / communicating outdoor · 18 SEER class
Goodman two-stage communicating condensing unit. Outdoor board talks ComfortBridge when paired with a communicating indoor (GMVC / AVPTC family). Faults live on the OUTDOOR board — not furnace E-codes. Will also run 24V Y1/Y2 against a conventional indoor. Amana ASXC18 is its own plate.
Not GSX14 / GSX16 single-stage piston units (contactor + cap only). Not GSZC18 / GSZC16 heat pump (reversing valve + defrost control). Not ASXC18 (Amana-badge — own chart). Not GLXT7C (R-32 two-stage).
Walk this in Diagnose This plate
Stages Two-stage scroll or inverter-adjacent two-step depending on vintage
Metering TXV indoor required for rating
Pair ComfortBridge air handler / furnace (data pair) or conventional 24V Y1/Y2
Sister SKU GSXC16 · Amana ASXC18 / AVXC20 are first-class Amana plates This board Outdoor communicating control
Codes are on the outdoor board, not the furnace IFC. Do not diagnose this unit from an indoor E2/E9. High pressure, low pressure, and comms (ComfortBridge pair only) are the usual three. If the indoor is GR9T96 or GMEC96 (24V), this outdoor must be landed on Y1/Y2 — do not expect ComfortBridge menus indoor. Communicating pair: data pair polarity, one master. Comm faults are invalid on a 24V-only hookup. Sequence Y1 / low. Outdoor starts low capacity. Indoor blower on low/mid Cool tap (24V) or communicating CFM (ComfortBridge indoor). Y2 / high. Second stage. Head and subcooling should rise into the OEM SC window. Communicating pair. GMVC96 / AVPTC indoor requests capacity on the data pair. No conventional Y needed. A 24V GR9T96 on that same pair is a miswire. Faults on this IFC HPS
High pressure lockout Outdoor airflow, overcharge, or restriction opened the high-pressure switch.
Outdoor fan running? Coil dirty, recirc, bent fins. Subcooling vs indoor TXV sheet. Liquid-line drier / restriction. Do not keep resetting HPS into a locked fan. LPS
Low pressure / freeze lockout Suction dropped out — charge, indoor airflow, or TXV.
Indoor filter, blower, coil freeze. Do not add gas on a frozen coil. TXV / restriction. Weigh-out if the history is a leak. Low ambient and wind can nuisance-trip LPS on a light load — still prove charge. Comm
Indoor/outdoor data lockout ComfortBridge data pair only. Invalid as a diagnosis on a 24V Y1/Y2 hookup.
Data pair polarity and splices. This is not 24V Y. Indoor IFC family must be GMVC / AVPTC communicating. GR9T96 / GMEC96 / GMSS96 cannot be the ComfortBridge indoor. One master on the bus. Outdoor board power before you condemn the indoor IFC. Workflows No cool, furnace is GR9T96 Mixed 24V GR9T96 (or GMEC96) indoor + GSXC outdoor.
This pair is 24V. Y1 and Y2 at the outdoor. No ComfortBridge indoor. Do not look for indoor menus. Contactor / outdoor board 24 VAC, then pressures and outdoor fan. Charge by SC on a TXV coil. Superheat is the TXV health check, not the charge method. If someone ran ComfortBridge data wire to a GR9T96, that is a miswire — not a bad outdoor board. Land Y1/Y2/C or change the indoor to GMVC / AVPTC. Indoor cool tap still matters — a 9-speed left on a low cool tap will freeze and look like LPS. Test points
Charge Nameplate + line-set adders. SC per indoor TXV sheet.
Y1 / Y2 24V pair: both present on high stage. Communicating pair: data, not 24 VAC.
Outdoor board LED/display before the disconnect. Codes die when you pull power. Gotchas ASXC18 / AVXC20 are Amana badges — use the Amana ASXC18 chart, do not stay here. GSZC18 is the heat-pump sibling — reversing valve and defrost live on that chart, not here. A GSX14 piston unit in the same yard is a different board. Do not apply this comms story to a contactor-and-cap condenser. GLXT7C is the R-32 two-stage successor. Different refrigerant. Related plates amana-asxc18 — Amana-badge two-stage / comm outdoor. Own chart. goodman-glxt7c — R-32 two-stage successor. Wrong refrigerant. goodman-gxv9s — Goodman inverter AC. Not this two-stage scroll. goodman-gszc18 — Heat-pump sibling. Reversing valve + defrost. Not this AC-only outdoor. goodman-gmvc96 — ComfortBridge indoor that can actually talk to this outdoor on the data pair. goodman-gr9t96 — 24V indoor mix. Y1/Y2 only — no ComfortBridge menus indoor. Terms Privacy Refund policy FieldBench is an independent reference tool and is not affiliated with, authorized by, or endorsed by Goodman, Amana, Daikin, Carrier, Bryant, or any equipment manufacturer. All product names and model numbers are trademarks of their respective owners, used for identification only.