ML196 Furnace · Merit · single- or two-stage · LED flash · 96%
Merit 96% condensing furnace using the 1–9 single-LED flash chart (or older dual-LED on G-series replacements). No E2xx 7-seg. PVC collector and trap. ML193 is a 93% condensing cousin with the same flash language — not this plate.
Not EL296V (E223/E229 7-seg). Not SLP99V. Not ML180 (same 1–9 numbers, 80% metal vent — opposite 3-flash physics). Not ML193 as this plate (93% condensing cousin — same flashes, different exchanger/vent kit). Not ML296 (two-stage Merit flash, different cabinet).
Walk this in Diagnose This plate
AFUE 96% condensing · PVC
Display Single red LED flash chart
Sister / cousin ML196UH upflow · ML193 93% cousin (same flashes, not this plate) This board Merit LED IFC
1 unexpected flame, 2 PS closed, 3 PS open, 4 primary limit, 5 rollout, 6 PS lockout, 7 ignition lockout, 8 flame lost lockout, 9 polarity. LED off = no power. Steady on = idle on many of these. Older G40/G61 dual-LED (DS1/DS2) is a different chart — do not use it here. Sequence W. Inducer → PS close (3-flash if not, 2-flash if it was already closed) → HSI → valve → flame → blower. Lockouts. Repeated 3-flash hardens to 6. Failed light-off hardens to 7. Flame lost after prove hardens to 8. Faults on this IFC 1 flash
Unexpected flame hazard Flame with the valve off.
Shut the cock. Leaking valve. 2 flash
PS closed lockout Pressure switch is made with the inducer off.
Unplug the switch. Water in the hose or a welded disc. 96% residual draft from a shared vent. 3 flash
PS open lockout Draft not proven. On this 96% that is trap / PVC / collector — not a chimney.
Condensate trap, collector, PVC intake/exhaust, inducer. Do not pull the ML180 metal-vent playbook. Same flash, opposite wet/dry checks. 4 flash
Primary limit warn Airflow / overtemp.
Tap or PSC speed, filter, coil, rise. 5 flash
Rollout hazard Flame containment. Hazard.
Exchanger, burners, flue. Reset only after the cause is gone. 6 flash
PS lockout lockout Hardened 3-flash / 2-flash. Retries used up on draft.
Fix the 3-flash physics (trap/PVC) before you reset. 7 flash
Ignition lockout lockout Failed to light / prove flame.
HSI, gas cock, valve 24 VAC, rod. 8 flash
Flame lost lockout lockout Had flame, then lost it. Retries used up.
Rod, ground, manifold after blower-on, vent that starves the flame. 9 flash
Polarity lockout L1/N reversed or ground missing.
Hot and neutral at the IFC. Chassis ground. Flame sense will not work reversed. Workflows 3-flash on 96% PVC No heat, inducer running or not, Merit LED.
Data plate: ML196 = Category IV PVC. This is not ML180 metal vent. Do not cut a chimney story here. Trap, collector, PVC slope, inducer. A drowned 96% trap is the usual 3-flash. If you see E223 on a 7-seg, you are not on an ML — go to EL296V. Repeated 3-flash becomes 6-flash lockout. Fix draft, then reset. Test points
Flash count Long pause between groups. Count twice.
Trap Clear and primed on this 96%. A dry or plugged trap is 3-flash. Gotchas ML180 uses the same 1–9 numbers. 3-flash there is chimney/inducer, not a drowned trap. ML193 is a 93% condensing cousin — same flashes, not this plate. Still PVC, still not metal vent. ML296 is two-stage Merit with flash codes. EL296V is Elite with E2xx. The names are designed to confuse you. Related plates lennox-ml180 — Merit 80% metal vent. Same 1–9 flashes, opposite 3-flash physics. lennox-el296v — Elite 96% 7-seg E2xx. If you are counting flashes you are not on that board. Terms Privacy Refund policy FieldBench is an independent reference tool and is not affiliated with, authorized by, or endorsed by Goodman, Amana, Daikin, Carrier, Bryant, or any equipment manufacturer. All product names and model numbers are trademarks of their respective owners, used for identification only.