Lennox
ML180 Furnace · Merit · 80% · metal vent · LED flash
Merit 80% Category I furnace. Same 1–9 flash numbers as ML196, opposite physics on 3-flash: chimney, inducer, common vent — not a drowned 96% trap. Metal vent, no secondary collector.
Not ML196 (96% PVC — same flashes, trap/collector checks). Not EL296V (E2xx 7-seg). Not SL280 / EL280 (Elite 80% two-stage; may have SureLight 7-seg on VS SKUs).
Walk this in Diagnose This plate
AFUE 80% · Category I metal vent
Display Single red LED flash chart — same numbers as ML196
Sister SKU ML180UH upflow · ML180DF downflow This board Merit LED IFC
1 unexpected flame, 2 PS closed, 3 PS open, 4 primary limit, 5 rollout, 6 PS lockout, 7 ignition lockout, 8 flame lost lockout, 9 polarity. Same count as ML196. The vent is not the same. 3-flash here is metal vent / draft, not PVC. LED off = no power. Steady on = idle on many of these. Sequence W. Inducer → PS (3-flash if the metal-vent path will not make) → HSI → valve → flame → blower. Faults on this IFC 1 flash
Unexpected flame hazard Flame with the valve off.
Shut the cock. Leaking valve. 2 flash
PS closed lockout Switch made with inducer off.
Welded switch or hose holding chimney draft. Not a 96% trap story. 3 flash
PS open lockout Draft not proven. On this 80% that is chimney / inducer / common vent — not a drowned 96% trap.
Metal vent, chimney liner, common-vent sizing, inducer wheel, intake at the burner box. Do not cut a PVC trap. There isn’t one. If the last tech installed a condensate kit on an 80%, you are on the wrong physics. 4 flash
Primary limit warn Airflow / overtemp.
Blower speed, filter, coil, rise. 80% cabinets still starve on a media filter. 5 flash
Rollout hazard Flame containment. Hazard.
Exchanger, burners, blocked metal flue, downdraft. Reset only after the cause is gone. 6 flash
PS lockout lockout Hardened 3-flash.
Fix chimney / inducer / common vent, then reset. 7 flash
Ignition lockout lockout Failed to light.
8 flash
Flame lost lockout lockout Had flame, then lost it.
Rod, ground, downdraft after blower-on. 9 flash
Polarity lockout L1/N reversed or ground missing.
Hot/neutral at the IFC. Chassis ground. Workflows 3-flash on metal vent Merit LED, 80% plate, no heat.
Data plate: ML180 = Category I metal. Dumping a ‘96% trap’ story here wastes the call. Chimney, liner, common vent, inducer, burner-box intake. Spillage at the draft hood / collector is the clue. If you see E223 on a 7-seg, you are not on an ML — and if the plate says 80% you want SL280, not EL296V. Test points
Vent Metal Category I. Draft at the hood / collector, not a PVC trap.
Flash count Same 1–9 as ML196. Physics follow the plate, not the number. Gotchas Techs who just left an ML196 will cut a trap story on 3-flash. There is no 96% collector on this furnace. SL280 / EL280 is the Elite 80% two-stage. Some of those have SureLight 7-seg — still metal vent if E223 shows. Related plates lennox-ml196 — Merit 96% PVC. Same 1–9 flashes, opposite 3-flash physics. lennox-sl280 — Elite 80% two-stage. Metal vent like this plate; may speak E2xx on VS SKUs. Terms Privacy Refund policy FieldBench is an independent reference tool and is not affiliated with, authorized by, or endorsed by Goodman, Amana, Daikin, Carrier, Bryant, or any equipment manufacturer. All product names and model numbers are trademarks of their respective owners, used for identification only.