Lennox
SL280 Furnace · Elite · two-stage · 80% · metal vent
Elite 80% two-stage (SL280UHV / EL280). Category I metal vent. VS SKUs may show the same SureLight 7-seg E2xx family as EL296V — if you see E223 it is still metal-vent draft, not a PVC trap. Flash SKUs use Merit-like 1–9 flashes. Identify the display and the vent before you cut anything.
Not EL296V (96% PVC collector and trap — same E223 number, opposite wet/dry checks). Not ML180 (Merit flash, single-stage; same 80% vent, different board and staging).
Walk this in Diagnose This plate
AFUE 80% two-stage · Category I metal vent
Display VS SKUs: SureLight 7-seg E2xx. Other SKUs: Merit-like 1–9 flash
Staging Two-stage valve · two-speed inducer
Sister SKU SL280UHV · EL280 / EL280UH This board SureLight 7-seg or Merit LED — read the door
First minute: 7-seg E-prefix or flashing LED? VS 80% SKUs speak E2xx. Flash SKUs speak 1–9 like ML180. E223 / E225 / E229 on this plate are metal-vent draft. Do not prime a 96% trap that is not there. 3-flash on a flash SKU is the same metal-vent story as ML180, with a second stage in play. Confirm any odd extra code on THAT door card. Sequence W1. Low inducer → low PS (E223 or 3-flash if metal-vent draft will not make) → HSI → low-fire valve → flame. W2. High inducer → high PS (E225). Common-vent / chimney load shows up here first on cold days. Faults on this IFC E223 / 3-flash
Low PS open / draft lockout Low-fire prove failed. On this 80% that is chimney, inducer, common vent — not a drowned 96% trap.
Metal vent, liner, common-vent sizing, inducer wheel, burner-box intake. If the display is E223 you are on a SureLight VS SKU. Same number as EL296V, opposite vent physics. E225
High PS failed OPEN lockout High-fire prove failed. Chimney that passed on low will fail on high.
Inducer actually high? Common vent / wind / liner. High hose not teed to the low switch. E229
Ignition on high fire info Low prove failed; IFC lit on high. OEM: fix low-fire draft, not a separate high-fire repair.
Same metal-vent path as E223. Do not start on the high-fire manifold screw. E250 / 4-flash
Limit warn Airflow / overtemp. 5-flash on a flash SKU is still rollout.
VS heat CFM or heat tap, filter, coil. Rollout: exchanger and metal flue. E270 / 7-flash
Ignition lockout lockout Max retries, no flame current (7-seg) or ignition lockout (flash).
Watch a try. HSI, gas, rod. If E271 / 6-flash stores, draft died — go back to the vent. E207 / E290
HSI / ignitor circuit lockout Ignitor open or trigger fault (7-seg SKUs).
Ohms and 120 VAC during trial. Workflows Identify 80% vs 96% before cutting a trap E223 or 3-flash, first minute on an Elite / Merit Lennox.
Plate: SL280 / EL280 / ML180 = 80% metal vent. EL296 / ML196 = 96% PVC. E223 on metal vent is chimney / inducer / common vent. E223 on EL296V is trap / PVC / inducer port. 3-flash on SL280 flash SKUs is the ML180 story, not the ML196 story. Do not install a condensing trap on an 80%. Do not chase a chimney liner on a 96%. Test points
Vent Metal Category I. Draft at the hood / collector.
Display E-prefix = SureLight VS SKU. Flashes = Merit-like SKU. Same 80% physics either way.
LPS / HPS Two-stage = two proves. High fire loads the chimney harder. Gotchas EL296V techs see E223 and cut a trap. There is no 96% collector on this furnace. ML180 is the single-stage Merit 80% with flashes only. This Elite can be 7-seg or flash — read the door. EL280 is the same Elite 80% family under the older badge. Related plates lennox-el296v — Elite 96% VS. Same SureLight E2xx numbers on VS SKUs — PVC trap physics, not metal vent. lennox-ml180 — Merit 80% single-stage flash. Same metal-vent 3-flash physics, no two-stage / no 7-seg. Terms Privacy Refund policy FieldBench is an independent reference tool and is not affiliated with, authorized by, or endorsed by Goodman, Amana, Daikin, Carrier, Bryant, or any equipment manufacturer. All product names and model numbers are trademarks of their respective owners, used for identification only.