Rheem

RA14AZ

AC · Endeavor Classic / Plus · single-stage · R-454B

Current Rheem Endeavor single-stage (RA14AZ / RA15AZ / RA16AZ). A2L R-454B. Contactor + dual cap. Same electrical story as RA16 — wrong refrigerant to top off.

Not RA16 / RA14 (R-410A). Not RA17AZ two-stage. Not RA19AY inverter.

Walk this in Diagnose

This plate

Refrigerant
R-454B (A2L)
Stages
Single-stage · one Y
Sister
RA15AZ Plus · RA16AZ · Ruud WA14AZ

This board

Endeavor contactor · R-454B nameplate

  • No inverter. No Y2.
  • Nameplate R-454B. RA16 410A ounces are the wrong book.

Sequence

  1. Y. Indoor stat Y → 24 VAC across outdoor C and contactor coil. Contactor pulls in → compressor + outdoor fan on the dual cap.
  2. HPS. High-pressure switch opening drops the coil. Contactor drops. No inverter alarm, just silence or chatter.
  3. Charge. Piston indoor: set by superheat. TXV indoor: set by subcooling. Rating-plate weigh-in is a starting point, not the Greenspeed-only method.

Faults on this IFC

  • HPS

    High pressure switch open

    lockout

    Outdoor HPS opened — coil circuit is dead. Not an inverter pressure fault and not an L-code.

    • HPS continuity, reset if manual, wiring in series with the coil.
    • Outdoor airflow: dirty coil, bent fins, fan not running (see ODF / cap).
    • Overcharge or non-condensables — confirm indoor metering before you recover (SH vs SC).
    • Do not treat this as a 25VNA drive trip.
  • ODF

    Outdoor fan fail

    warn

    Fan not turning. Compressor may still run and then HPS.

    • Dual-cap FAN section µF vs sticker. A good HERM and a dead FAN is the usual Comfort call.
    • Fan motor ohms / ground, blade clearance, capacitor wiring (C / FAN / HERM).
    • Not an inverter fan module — there isn’t one.
  • Contactor

    Contactor / coil

    warn

    Will not pull, chatters, or is welded.

    • 24 VAC at the coil under a Y call. Low voltage = long stat wire, weak indoor transformer, or a furnace 24 (fuse) problem.
    • Coil ohms / burned turns. Pitted or welded points — replace, do not file and leave.
    • Chatter: low 24V, bad coil, weak transformer — not an inverter ramp.
  • Cap

    Dual run capacitor

    warn

    HERM and/or FAN section out of rating. Single-stage Comfort dies this way all summer.

    • Both sections vs microfarad rating, not just one.
    • Bulged can, open bleed, wrong replacement (single vs dual, voltage).
    • Hard-start add-ons do not fix a dead FAN section.
  • Charge

    Charge (SH piston / SC TXV)

    warn

    Wrong charge method is as common as wrong charge.

    • Indoor piston: charge by superheat. Indoor TXV: charge by subcooling.
    • Do not use Greenspeed weigh-in-only as the only method unless the factory TXV rating plate on THIS outdoor says so. Most 24ACC are piston/TXV conventional.
    • Line-set length and indoor coil match still matter. Weigh-in after a repair, then finish on SH or SC.

Workflows

RA14AZ charge / no-cool

Plate says R-454B, or a 410A tank is on the truck.

  1. 24 VAC, dual cap, then R-454B SH or SC.
  2. Recover on an A2L-capable machine. Do not top off 410A.
  3. RA17AZ is the two-stage Endeavor.

Test points

Contactor coil
Stable ~24 VAC on Y. Chatter = voltage, coil, or HPS. No ABCD to probe.
Dual cap
HERM and FAN both within ~6% (or OEM) of the stamped µF.
Charge
SH target on piston indoor; SC target on TXV indoor. Weigh-in is a start, not a Greenspeed-only finish.
HPS
Closed at rest. Open under high head = airflow/charge, not an inverter L-code.

Gotchas

  • RA14 without AZ is 410A. The AZ (and the rating plate) is the whole call.