RA14AZ
Endeavor Classic / Plus · single-stage · R-454B
Current Rheem Endeavor single-stage (RA14AZ / RA15AZ / RA16AZ). A2L R-454B. Contactor + dual cap. Same electrical story as RA16 — wrong refrigerant to top off.
Not RA16 / RA14 (R-410A). Not RA17AZ two-stage. Not RA19AY inverter.
Refrigerant
R-454B (A2L)
Stages
Single-stage · one Y
Sister
RA15AZ Plus · RA16AZ · Ruud WA14AZ
This board
Endeavor contactor · R-454B nameplate
- No inverter. No Y2.
- Nameplate R-454B. RA16 410A ounces are the wrong book.
Nothing stored.
Universal swap
Rheem RA14AZ outdoor. No furnace IFC universal. Replace the OEM outdoor control / contactor / drive by the silk.
Silk: RA14AZ
White-Rodgers
—ICM
—Honeywell
—- Indoor furnace universals (50A55, 50M56U, ICM282B, ICM2811, S9200U). This is not an IFC.
- Do not ‘adapt’ a furnace board to an outdoor inverter, defrost PCB, or contactor.
After you pull the dead card
- 1Photograph the outdoor silk. Indoor 50A55 / ICM282B / S9200U do not belong here.
- 2Contactor units: replace the contactor / cap / HPS — there is no universal outdoor board.
- 3Inverter / communicating outdoors: OEM drive only. There is no White-Rodgers or ICM outdoor universal.
Field wiring
Written landings for Rheem RA14AZ. Not a factory schematic.
One cool stage. Indoor transformer, stat Y, outdoor contactor coil. Dual cap on the outdoor. No data pair and no Y2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFThis indoor
Endeavor Classic 24V. E1/E2 stay empty.
24V single-stage
Plate is a one-contactor condensing unit.
Wall thermostat
Conventional 24V. One cool stage.
- R24V hot from indoor transformer24V
- C24V common24V
- YCool call — one stage24V
- GIndoor fan24V
- WHeat. Stays at the indoor.24V
Indoor IFC / AHU
Y in from the stat. Y out to the outdoor contactor. Same transformer.
- RTransformer hot — feeds the stat24V
- CTransformer common — must reach the outdoor24V
- YStat Y in24V
- YoutTo outdoor contactor coil24V
- GBlower / cool tap24V
- WHeat only24V
Outdoor — contactor coil
Two control screws. There is no outdoor IFC to interrogate.
- YContactor coil. ~24 VAC to C under a call.24V
- CContactor coil common24V
Outdoor line
208/230 through the disconnect to the contactor line side.
- L1LineLine
- L2LineLine
- GNDEquipment groundLine
Dual run capacitor
C / FAN / HERM on the can. An inverter outdoor does not have this part.
- CCommon — both windingsCap
- FANOutdoor fanCap
- HERMCompressorCap
Landing
- 24VIndoor Rstat R
~24 VAC hot
- 24VIndoor Cstat Coutdoor C
Common. Outdoor will not pull without it.
- 24VStat Yindoor Youtdoor Y
~24 VAC across Y–C at the contactor under a call
- 24VStat Gindoor G
Indoor blower. Does not go outdoors.
- LineL1 / L2disconnectcontactor line
208/230
- CapCap C / FAN / HERM
Both sections vs the can stamp
Prove it
- 24 VAC across outdoor Y and C under a Y call, measured at the outdoor.
- Contactor pulls and stays. Chatter is low 24V, a cooked coil, or HPS in series.
- Dual-cap FAN and HERM both in spec.
Do not
- Do not land a ComfortBridge / ABCD / iComfort data pair on this outdoor. It wants Y and C.
- There is no O/B. That screw is the heat-pump twin.
- There is no Y2.
Field landing, not a scanned OEM schematic. Photograph the outdoor silk if the screws are not labeled Y/C.
Sequence
- 1
Y
Indoor stat Y → 24 VAC across outdoor C and contactor coil. Contactor pulls in → compressor + outdoor fan on the dual cap.
- 2
HPS
High-pressure switch opening drops the coil. Contactor drops. No inverter alarm, just silence or chatter.
- 3
Charge
Piston indoor: set by superheat. TXV indoor: set by subcooling. Rating-plate weigh-in is a starting point, not the Greenspeed-only method.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
HPS
High pressure switch open
Outdoor HPS opened — coil circuit is dead. Not an inverter pressure fault and not an L-code.
1 Let it cool, then read the drive LED
On Rheem RA14AZ overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. HPS continuity, reset if manual, wiring in series with the coil.
Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.
2 Voltage and compressor windings
Incoming voltage in range (this plate’s line-voltage code). Compressor windings even, no ground. A shorted compressor will kill a new drive. Outdoor airflow: dirty coil, bent fins, fan not running (see ODF / cap).
Expect: Balanced windings. No winding to ground. Line voltage stable under load.
3 Charge and the drive last
A starved or flooded compressor will overcurrent. Confirm SH/SC and charge weight. Only then condemn the inverter. Overcharge or non-condensables — confirm indoor metering before you recover (SH vs SC).
Expect: Charge on the nameplate. Drive code gone after a cool-down and a clean coil.
ODF
Outdoor fan fail
Fan not turning. Compressor may still run and then HPS.
1 Heat rejection first
On Rheem RA14AZ high pressure is outdoor airflow until proven otherwise. Fan running the right direction, coil clean, fins not folded, no recirc over a fence or through a garage. Dual-cap FAN section µF vs sticker. A good HERM and a dead FAN is the usual Comfort call.
Expect: OD fan on, coil clean, discharge air leaving the top/side freely.
2 Head, subcooling, and liquid line
Liquid pressure and liquid-line temperature → SC. High head + high SC = overcharge or non-condensables. High head + low SC = restriction or a dying compressor. Do not add gas because suction is low. Fan motor ohms / ground, blade clearance, capacitor wiring (C / FAN / HERM).
Expect: SC vs the metering device on this plate (TXV ≠ piston).
3 Restriction vs the switch
Drier, liquid-line kink, TXV inlet screen, or a non-feed indoor coil will stack head. Ohm / jumper-test the HPS only as a momentary prove, then restore it. A switch that opens on a known-good charge and clean coil is the switch. Not an inverter fan module — there isn’t one.
Expect: HPS closed at a normal liquid pressure for this refrigerant and OD ambient.
Contactor
Contactor / coil
Will not pull, chatters, or is welded.
1 Is Y actually at the contactor?
On Rheem RA14AZ a silent outdoor is often no Y. Measure 24 VAC coil-to-C at the contactor on a cool call. 24 VAC at the coil under a Y call. Low voltage = long stat wire, weak indoor transformer, or a furnace 24 (fuse) problem.
Expect: ~24 VAC at the coil when the indoor is calling.
If fail: Indoor Y / IFC / stat — not a capacitor.
2 Cap and the compressor windings
Dual run cap: herm and fan MFD ±6%. Then windings. A bad cap with a good Y is still the first cheap part — but confirm MFD, do not guess. Coil ohms / burned turns. Pitted or welded points — replace, do not file and leave.
Expect: MFD on the can. Even windings. Fan and compressor both try.
3 Contactor and mechanical
Pitted contactor, no mechanical close, or a welded contactor that never drops out. Replace the failed part; do not file contacts as a repair. Chatter: low 24V, bad coil, weak transformer — not an inverter ramp.
Expect: Clean pull-in. Line voltage through to both loads.
Cap
Dual run capacitor
HERM and/or FAN section out of rating. Single-stage Comfort dies this way all summer.
1 Is Y actually at the contactor?
On Rheem RA14AZ a silent outdoor is often no Y. Measure 24 VAC coil-to-C at the contactor on a cool call. Both sections vs microfarad rating, not just one.
Expect: ~24 VAC at the coil when the indoor is calling.
If fail: Indoor Y / IFC / stat — not a capacitor.
2 Cap and the compressor windings
Dual run cap: herm and fan MFD ±6%. Then windings. A bad cap with a good Y is still the first cheap part — but confirm MFD, do not guess. Bulged can, open bleed, wrong replacement (single vs dual, voltage).
Expect: MFD on the can. Even windings. Fan and compressor both try.
3 Contactor and mechanical
Pitted contactor, no mechanical close, or a welded contactor that never drops out. Replace the failed part; do not file contacts as a repair. Hard-start add-ons do not fix a dead FAN section.
Expect: Clean pull-in. Line voltage through to both loads.
Charge
Charge (SH piston / SC TXV)
Wrong charge method is as common as wrong charge.
1 Airflow and freeze before you add gas
On Rheem RA14AZ low pressure / freeze is indoor airflow or a starved coil until proven otherwise. Filter, blower, dirty A-coil, closed supplies. In heat mode, a iced outdoor coil is the same family. Indoor piston: charge by superheat. Indoor TXV: charge by subcooling.
Expect: Indoor air moving. Coil not iced. OD coil clear in heat.
2 SH / SC after a thaw
Thaw fully. Then SH and SC vs the metering device. Low charge ices a piston. A TXV stuck closed ices with high SH. A restriction downstream of the ports fakes a low-charge chart. Do not use Greenspeed weigh-in-only as the only method unless the factory TXV rating plate on THIS outdoor says so. Most 24ACC are piston/TXV conventional.
Expect: SH/SC in range for this refrigerant and device after a stable 10-minute run.
3 Leak, TXV, then the LPS
Weigh-in if the chart says undercharge. Soap / electronic leak on joints and the coil. LPS that opens on a known-good charge and a clear coil is the switch — momentary test only, then restore. Line-set length and indoor coil match still matter. Weigh-in after a repair, then finish on SH or SC.
Expect: Charge on the nameplate. LPS closed at a normal suction for this OD ambient.
Workflows
RA14AZ charge / no-cool
Plate says R-454B, or a 410A tank is on the truck.
1 Prove the call and the live code
24 VAC, dual cap, then R-454B SH or SC.
Expect: Write whatever Endeavor contactor · R-454B nameplate is showing. Nothing stored.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Recover on an A2L-capable machine. Do not top off 410A.
Expect: HPS: High-pressure switch opening drops the coil. Contactor drops. No inverter alarm, just silence or chatter.
3 Confirm with a number, then the next part
RA17AZ is the two-stage Endeavor.
Expect: Contactor coil: Stable ~24 VAC on Y. Chatter = voltage, coil, or HPS. No ABCD to probe. · Dual cap: HERM and FAN both within ~6% (or OEM) of the stamped µF.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Contactor coil
Stable ~24 VAC on Y. Chatter = voltage, coil, or HPS. No ABCD to probe.
Dual cap
HERM and FAN both within ~6% (or OEM) of the stamped µF.
Charge
SH target on piston indoor; SC target on TXV indoor. Weigh-in is a start, not a Greenspeed-only finish.
HPS
Closed at rest. Open under high head = airflow/charge, not an inverter L-code.
Gotchas
- RA14 without AZ is 410A. The AZ (and the rating plate) is the whole call.
Related plates
Install this plate
Install Rheem RA14AZ as Endeavor Classic / Plus · single-stage · R-454B.
Endeavor Classic / Plus · single-stage · R-454B
This plate — not the sister SKU
- Not RA16 / RA14 (R-410A). Not RA17AZ two-stage. Not RA19AY inverter.
- RA14 without AZ is 410A. The AZ (and the rating plate) is the whole call.
Control on this outdoor
- No inverter. No Y2.
- Nameplate R-454B. RA16 410A ounces are the wrong book.
Hardware
- Refrigerant: R-454B (A2L)
- Stages: Single-stage · one Y
- Sister: RA15AZ Plus · RA16AZ · Ruud WA14AZ
First fire
- 124 VAC, dual cap, then R-454B SH or SC.
- 2Recover on an A2L-capable machine. Do not top off 410A.
- 3RA17AZ is the two-stage Endeavor.
Do not on Rheem RA14AZ
- Not RA16 / RA14 (R-410A). Not RA17AZ two-stage. Not RA19AY inverter.
- RA14 without AZ is 410A. The AZ (and the rating plate) is the whole call.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Rheem residential furnacesLiterature searchR96T / R96V / R801V / R802V / R98MV product cards. I/O is typically MyRheem / PTS dealer.Open manufacturer PDF
- Rheem supportLiterature searchOwner docs and registration. Full I/O is not hosted as a public PDF for most Endeavor plates.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
dealerRheem furnace warranty
Registered Endeavor / Classic furnace warranty · Dealer claims portal
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal